Master Examination Practice Drill #5 2011 Ted “Smitty” Smith.

Slides:



Advertisements
Similar presentations
FIRE PUMP ELECTRICAL CONFIGURATIONS UNDER 600 VOLTS.
Advertisements

Master Examination Practice Drill # O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded.
DAY 4 CHAPTER 3 CONDUCTOR SIZES,TYPES, ETC.. Continuous Load. A load where the maximum current is expected to continue for 3 hours or more. Continuous.
Master Examination Practice Drill # O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at.
Master Examination Practice Drill # (16) O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles.
The Home Inspection Book: A Guide for Professionals By Marcia Darvin Spada Copyright, Thomson/South-Western, 2003, Revised, 2006.
©Ted “Smitty” Smith This speed drill focuses on calculations that will be required for the journeyman and masters examination. The question slide.
Copyright 2005 Ted "Smitty" Smith Two Minute Drill Number Three Improving your skill in code Look Up Increasing Speed Drill.
Two Minute Drill Number 32- Journeyman Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 25- Residential Improving your skill in code Look Up Increasing Speed Drill.
2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager.
©Ted “Smitty” Smith  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead.
Two Minute Drill #8 Copyright 2005 Ted "Smitty" Smith Practice Code Look Up.
Two Minute Drill Number 26- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.
Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage.
COMMERCIAL ELECTRICAL (Chapter 11)
Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith.
Two Minute Drill Number 27- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Calculation Speed Drill # NEC
Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1.
Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6.
Copyright 2008 Ted "Smitty" Smith.  Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. 
©Ted “Smitty” Smith This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.
Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 31- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 22- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 24- Residential.
2008 Code Drills (C) Copyright 2008 Ted "Smitty" Smith 1 Smitty’s Speed Drills.
Ag. Mechanics for Beginning Teachers
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 21- Residential Improving your skill in code Look Up Increasing Speed Drill.
2014 NEC C ODE C HANGES C LASS P ART III C ALCULATIONS Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc.
Starting Residential Wiring.  The most important element in wiring. Safety is proper grounding.  Grounding is the connection of all parts of a wiring.
ELECTRICAL WIRING WIRING BASICS Written by Bobby Joslin
ELECTRICAL INSTRUMENTS ( service and utilization )
N.E.C. Installation Techniques and Common Violations
Smitty’s Two Minute Drill Grounding
Smitty’s Two Minute Drill Grounding
Advanced Calculations Drill 1 for the 2011 NEC
License Examination Practice Drill
Chapter 12 Branch Circuits and Feeders. Chapter 12 Branch Circuits and Feeders.
2011 Changes Two Minute Drill
Smitty’s Two Minute Drills
Smitty’s Two Minute Drill Overcurrent Protection
Smitty’s Two Minute Drill Mixed Content -05
Theory and Calculations
Practice Code Look Up Two Minute Drill #7
Conductors and Cables 2017 NEC
Ampacity Calculations and Overcurrent Protection 1
Calculation Speed Drill #1
Engineering Project Cable Management.
Calculations: Transformers and Service Conductor Calculations
Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
Two Minute Drill: Raceways and Boxes 2017
Overcurrent Protection— Fuses and Circuit Breakers
EET 323 – Electrical System Design Lecture 9: Grounding
Two Minute Drill Number 29- Conductors and Raceways
EET 323 – Electrical System Design Lecture 6: Conductors and Over-Current Protection Radian Belu, PhD.
Smitty’s Two Minute Drill Grounding and Bonding
Smitty’s Two Minute Drill Services, Feeders, and Branch Circuits 1
Load Calculation Speed Drill
Two Minute Drill – Residential 3
Smitty’s Two Minute Drill Varied Number 7
Smitty’s Two Minute Drill The BIG 5 Drill 1
Two Minute Drill – Residential 2
Calculations Review Drill
Cooking , Electric Dryer and Appliance Calculations 3
Calculation Speed Drill Varied-1
Varied Calculations Drill 2
Presentation transcript:

Master Examination Practice Drill # Ted “Smitty” Smith

O Given: a 150 kVA service transformer has a 480Y/277 volt, 3-phase secondary. What is the approximate full-load ampere rating of the primary of the transformer? A. 180 amperes B. 312 amperes C. 542 amperes D. 416 amperes

O 1. A O A

O Where a conductor is marked RHW-2 on the insulation what does the -2 represent? A. The cable has 2 conductors B. The conductor is double insulated C. The conductor has a nylon outer jacket D. The conductor has a maximum operating temperature of 90°C.

O 2. D Table (A)

O For a grounded electrical system, the equipment grounding conductor shall be sized in accordance with ___________? A. The undergrounded circuit conductors B. The overcurrent protective device C. The service entrance conductors D. The grounding electrode

O 3. B O (B)(1) O Table

O Determine the allowable ampacity of a size kcmil THW aluminum conductor installed in a raceway with four (4) other current- carrying conductors when the expected ambient temperature is 44 deg. C. A. 151 amperes B. 164 amperes C. 210 amperes D. 146 amperes

O 4. B O Tbl (B)(16) O Tbl (B)(2)(a) O Tbl (B)(3)(a)

O Determine the MAXIMUM number of 120- volt, general-purpose duplex receptacles the NEC® permits to be protected by a 20- ampere, 120-volt single-pole circuit breaker in a commercial building. A. 18 B. 15 C. 13 D. 10

O 5. C O 120 volts x 20 amperes= 2400 VA O 2400 VA / 180 VA= 13 receptacles

O For4 lighting systems operating at 30 volts or less, the output circuits of the power supply are to be rated for NOT more than ___________? A. 15 amperes B. 20 amperes C. 25 amperes D. 30 amperes

O 6. C O 411.2

O Where there are tenant spaces in a retail shopping mall, each occupant shall have access to the main disconnecting means, EXCEPT: A. Where the service and maintenance are provided by the building management. B. Where there are more than six disconnecting means provided. C. Where the primary feeder transformer does not exceed 600 volts. D. Where the secondary of the service transformer does not exceed 240 volts to ground.

O 7. A O (B)(1)(1)

O Determine the conductor allowable ampacity given the following related information:  Ambient temperature of 44°C  250 kcmil THWN copper conductors  Four (4) current-carrying conductors in the raceway  Length of raceway is 50 feet. A. 160 amperes B. 167 amperes C. 200 amperes D. 209 amperes

O 8. B O Tble (B)(16) O Tbl (B)(2)(a) O Tbl (B)(3)(a) O 250 kcmil THWN copper ampacity 255 A O 255 A x.82 temp correction x.8 adj factor

O In general, the grounded conductor and the grounding conductor must be bonded together in _____________?  I. Panelboards used as service equipment  All sub-panels A. I only B. II only C. Both I and II D. Neither I not II

O 9. A O (A) O (A)(5) O 408.3(C)

O Using the standard method of calculation, what is the demand, in kW, on the undergrounded service-entrance conductors of an apartment complex that has thirty-five (35) electric ranges rated at 11.5 kW each? A. 403 kW B. 15 kW C. 280 kW D. 50 kW

O 10. D O Tbl , Col. C

O A grounding ring consisting of a size 2 AWG bare copper wire encircling a building, buried 36 in. deep, in direct contact with the earth, is required to have a MINIMUM length of ____________? A. 15 feet B. 20 feet C. 25 feet D. 50 feet

O 11. B O (A)(4)

O Where applying the optional method of calculation for one-family dwelling, what is the demand load for the heating and cooling, in kW, on the ungrounded service-entrance conductors for a residence that has the following?  One blower motor rated 1.2 kW, interlocked with both space heating and AC equipment.  One central electric space-heating unit rated 25 kW  One air-conditioning unit rated 6.5 kW A kW B kW C kW D kW

O 12. C O (C) and (C)(4) O Note: Use the large of the A/C or heating load

O Apply the general method of calculation for dwelling units and determine the Minimum demand load, in VA, where a one-family residence has the following fastened in place appliances.  Microwave oven – 1,250 VA  Trash compacter – 960VA  Dishwasher – 1,400 VA  Garage door opener – 960 VA A. 3,428 VA B. 3,656 VA C. C. 4,570 D. 4,883 VA

O 13. A O Microwave Oven: 1250 VA O Trash Compactor: 960 VA O Dish Washer:1400 VA O Garage Door Opener: 900 Va O Total: 4570 VA x.75= 3428 VA

O Where a service riser is installed in a wet location and contains THWN insulated conductors, the wiring method used ________________. A. Is permitted to be Type AC cable B. Shall be rigid metal conduit (RMC) C. Is permitted to be electrical metallic tubing (EMT) D. Shall be liquidtight flexible metal conduit (LFMC)

O 14. C230.43(5)

O What is the MAXIMUM distance between supports for straight horizontal runs of trade size 1 ½ in. threaded rigid metal conduit (RMC)? A. 10 feet B. 12 feet C. 14 feet D. 16 feet

O 15. C O Tbl (B)(2)

O At least one receptacle outlet shall be installed directly above a show window of a department store for each __________ linear feet of show window area. A. Six B. Eight C. Ten D. Twelve

O 16. D O

O A thermal barrier shall be required if the space between the resistors and reactors, of 600 volts or less, and combustible material is Less than __________________? A. 12 inches B. 18 inches C. 10 inches D. 6 inches

O 17. A O 470.3

O In movie theaters, all switches for controlling the emergency lighting systems shall be located __________. A. On the stage B. In the lobby C. In the manger’s office D. In the project booth

O 18. B O

O Where a 90 ampere, 240-volt, single-phase load is located 225 feet from a panelboard and is supplied with size 3 AWG copper conductors, determine the approximate voltage drop on the conductors. (K=12.9) A. 6 volts B. 4 volts C. 8 volts D. 10 volts

O 19. D O VD= 2KDI/CM O 2x12.9x225x90/52620= 9.92

O A one-family residence is served with insulated 120/240 colt service-drop conductors, supported with a grounded messenger wire from the utility company. This service-drop crosses the swimming pool; the pool has a diving board that is 5 feet above the water level. The NEC® requires the conductors to be a Minimum height of ______ above the pool water level. A. 25 feet B. 14 ¼ feet C. 22 ½ feet D. 19 ½ feet

O 20. C O Fig O Tbl

O Given: A trade size 2 in. electrical metallic tubing (EMT) containing four (4) size 2/0 AWG THWN copper conductors is to be installed in a pull box for a straight pull of the conductors. What is the MINIMUM required length of the pull box? A. 4 inches B. 12 inches C. 16 inches D. 24 inches

O 21. C O O 2x8= 16

O In a commercial garage work area, which of the following receptacles, if any, are required to have GFCI protection?  I. 15 ampere general-purpose receptacles for hand tools and portable lights.  II. 20 ampere receptacles serving electrical diagnostic equipment only. A. I only B. II only C. Both I and II D. Neither I and II

O 22. C O 210.8(B)(8) O

O Conductors tapped from a feeder and supplying the primary of a transformer need not have overcurrent protection, if the length of the tap conductors are not over 25 feet and have an ampacity of at LEAST ______ of the rating of the overcurrent device protecting the feeder conductors. A. One-third B. One-half C. 80 percent D. 75 percent

O 23. A O (B)(3)(1)

O Where conductors carrying alternating current are installed in ferrous metal raceways, ________. A. All phase conductors, the grounded conductor and equipment grounding conductors shall be grouped together B. The phase conductors shall not be grouped with the grounded conductor C. The equipment grounding conductor is not permitted to be in the same raceway with the grounded and ungrounded conductors D. The equipment grounding conductors are not permitted to be installed in a common raceway with the grounded conductors.

O 24. A O (A)

O When connecting utilization equipment to a 20-ampere rated branch-circuit that also serves luminaires (lighting fixtures), the utilization equipment shall have an ampere rating of NOT more than _______. A. 10 amperes B. 15 amperes C. 16 amperes D. 12 amperes

O 25. A O (A)(2) O 20A x 50%= 10 A

Click Here to Proceed without the timer

O Given: a 150 kVA service transformer has a 480Y/277 volt, 3-phase secondary. What is the approximate full-load ampere rating of the primary of the transformer? A. 180 amperes B. 312 amperes C. 542 amperes D. 416 amperes

O 1. A O A

O Where a conductor is marked RHW-2 on the insulation what does the -2 represent? A. The cable has 2 conductors B. The conductor is double insulated C. The conductor has a nylon outer jacket D. The conductor has a maximum operating temperature of 90°C.

O 2. D Table (A)

O For a grounded electrical system, the equipment grounding conductor shall be sized in accordance with ___________? A. The undergrounded circuit conductors B. The overcurrent protective device C. The service entrance conductors D. The grounding electrode

O 3. B O (B)(1) O Table

O Determine the allowable ampacity of a size kcmil THW aluminum conductor installed in a raceway with four (4) other current- carrying conductors when the expected ambient temperature is 44 deg. C. A. 151 amperes B. 164 amperes C. 210 amperes D. 146 amperes

O 4. B O Tbl (B)(16) O Tbl (B)(2)(a) O Tbl (B)(3)(a)

O Determine the MAXIMUM number of 120- volt, general-purpose duplex receptacles the NEC® permits to be protected by a 20- ampere, 120-volt single-pole circuit breaker in a commercial building. A. 18 B. 15 C. 13 D. 10

O 5. C O 120 volts x 20 amperes= 2400 VA O 2400 VA / 180 VA= 13 receptacles

O For4 lighting systems operating at 30 volts or less, the output circuits of the power supply are to be rated for NOT more than ___________? A. 15 amperes B. 20 amperes C. 25 amperes D. 30 amperes

O 6. C O 411.2

O Where there are tenant spaces in a retail shopping mall, each occupant shall have access to the main disconnecting means, EXCEPT: A. Where the service and maintenance are provided by the building management. B. Where there are more than six disconnecting means provided. C. Where the primary feeder transformer does not exceed 600 volts. D. Where the secondary of the service transformer does not exceed 240 volts to ground.

O 7. A O (B)(1)(1)

O Determine the conductor allowable ampacity given the following related information:  Ambient temperature of 44°C  250 kcmil THWN copper conductors  Four (4) current-carrying conductors in the raceway  Length of raceway is 50 feet. A. 160 amperes B. 167 amperes C. 200 amperes D. 209 amperes

O 8. B O Tble (B)(16) O Tbl (B)(2)(a) O Tbl (B)(3)(a) O 250 kcmil THWN copper ampacity 255 A O 255 A x.82 temp correction x.8 adj factor

O In general, the grounded conductor and the grounding conductor must be bonded together in _____________?  I. Panelboards used as service equipment  All sub-panels A. I only B. II only C. Both I and II D. Neither I not II

O 9. A O (A) O (A)(5) O 408.3(C)

O Using the standard method of calculation, what is the demand, in kW, on the undergrounded service-entrance conductors of an apartment complex that has thirty-five (35) electric ranges rated at 11.5 kW each? A. 403 kW B. 15 kW C. 280 kW D. 50 kW

O 10. D O Tbl , Col. C

O A grounding ring consisting of a size 2 AWG bare copper wire encircling a building, buried 36 in. deep, in direct contact with the earth, is required to have a MINIMUM length of ____________? A. 15 feet B. 20 feet C. 25 feet D. 50 feet

O 11. B O (A)(4)

O Where applying the optional method of calculation for one-family dwelling, what is the demand load for the heating and cooling, in kW, on the ungrounded service-entrance conductors for a residence that has the following?  One blower motor rated 1.2 kW, interlocked with both space heating and AC equipment.  One central electric space-heating unit rated 25 kW  One air-conditioning unit rated 6.5 kW A kW B kW C kW D kW

O 12. C O (C) and (C)(4) O Note: Use the large of the A/C or heating load

O Apply the general method of calculation for dwelling units and determine the Minimum demand load, in VA, where a one-family residence has the following fastened in place appliances.  Microwave oven – 1,250 VA  Trash compacter – 960VA  Dishwasher – 1,400 VA  Garage door opener – 960 VA A. 3,428 VA B. 3,656 VA C. C. 4,570 D. 4,883 VA

O 13. A O Microwave Oven: 1250 VA O Trash Compactor: 960 VA O Dish Washer:1400 VA O Garage Door Opener: 900 Va O Total: 4570 VA x.75= 3428 VA

O Where a service riser is installed in a wet location and contains THWN insulated conductors, the wiring method used ________________. A. Is permitted to be Type AC cable B. Shall be rigid metal conduit (RMC) C. Is permitted to be electrical metallic tubing (EMT) D. Shall be liquidtight flexible metal conduit (LFMC)

O 14. C230.43(5)

O What is the MAXIMUM distance between supports for straight horizontal runs of trade size 1 ½ in. threaded rigid metal conduit (RMC)? A. 10 feet B. 12 feet C. 14 feet D. 16 feet

O 15. C O Tbl (B)(2)

O At least one receptacle outlet shall be installed directly above a show window of a department store for each __________ linear feet of show window area. A. Six B. Eight C. Ten D. Twelve

O 16. D O

O A thermal barrier shall be required if the space between the resistors and reactors, of 600 volts or less, and combustible material is Less than __________________? A. 12 inches B. 18 inches C. 10 inches D. 6 inches

O 17. A O 470.3

O In movie theaters, all switches for controlling the emergency lighting systems shall be located __________. A. On the stage B. In the lobby C. In the manger’s office D. In the project booth

O 18. B O

O Where a 90 ampere, 240-volt, single-phase load is located 225 feet from a panelboard and is supplied with size 3 AWG copper conductors, determine the approximate voltage drop on the conductors. (K=12.9) A. 6 volts B. 4 volts C. 8 volts D. 10 volts

O 19. D O VD= 2KDI/CM O 2x12.9x225x90/52620= 9.92

O A one-family residence is served with insulated 120/240 colt service-drop conductors, supported with a grounded messenger wire from the utility company. This service-drop crosses the swimming pool; the pool has a diving board that is 5 feet above the water level. The NEC® requires the conductors to be a Minimum height of ______ above the pool water level. A. 25 feet B. 14 ¼ feet C. 22 ½ feet D. 19 ½ feet

O 20. C O Fig O Tbl

O Given: A trade size 2 in. electrical metallic tubing (EMT) containing four (4) size 2/0 AWG THWN copper conductors is to be installed in a pull box for a straight pull of the conductors. What is the MINIMUM required length of the pull box? A. 4 inches B. 12 inches C. 16 inches D. 24 inches

O 21. C O O 2x8= 16

O In a commercial garage work area, which of the following receptacles, if any, are required to have GFCI protection?  I. 15 ampere general-purpose receptacles for hand tools and portable lights.  II. 20 ampere receptacles serving electrical diagnostic equipment only. A. I only B. II only C. Both I and II D. Neither I and II

O 22. C O 210.8(B)(8) O

O Conductors tapped from a feeder and supplying the primary of a transformer need not have overcurrent protection, if the length of the tap conductors are not over 25 feet and have an ampacity of at LEAST ______ of the rating of the overcurrent device protecting the feeder conductors. A. One-third B. One-half C. 80 percent D. 75 percent

O 23. A O (B)(3)(1)

O Where conductors carrying alternating current are installed in ferrous metal raceways, ________. A. All phase conductors, the grounded conductor and equipment grounding conductors shall be grouped together B. The phase conductors shall not be grouped with the grounded conductor C. The equipment grounding conductor is not permitted to be in the same raceway with the grounded and ungrounded conductors D. The equipment grounding conductors are not permitted to be installed in a common raceway with the grounded conductors.

O 24. A O (A)

O When connecting utilization equipment to a 20-ampere rated branch-circuit that also serves luminaires (lighting fixtures), the utilization equipment shall have an ampere rating of NOT more than _______. A. 10 amperes B. 15 amperes C. 16 amperes D. 12 amperes

O 25. A O (A)(2) O 20A x 50%= 10 A