1 Smitty’s Two Minute Drill Mixed Content -05
© Ted Smith 2017 Electrical Experts Consulting

2 Click on the slide to start the timer and begin the test
Be sure to place this presentation in Slide Show Mode if it is not already in that mode before proceeding The purpose of this drill is to help you improve your skill at finding answers to questions using the applicable fire codes and also to help increase your knowledge of the Fire Alarm codes. Each slide will contain a question. The question will remain in the screen for a period of 2 minutes then a notification will sound and the slide will transition to the next slide with the answer. After 15 seconds the next question will appear. During the test do not worry about the correct answers when those slide appear. You will be given an opportunity to review the answers with out the time at the end of the test. Click on the slide to start the timer and begin the test Instructions

3 NEC 1. A meeting room in a non-dwelling unit measures 15’ by 25’. What is the minimum number of floor box receptacle outlets required for this room? 1 2 3 4

4 Answer B. 2 210.71(b)(2)

5 NEC 2. In a ventilated trough cable tray, four conductor 10 AWG TC cable will be installed for 480V loads. The vented cable tray is 24” wide and is divided into two sections, One section is 18” and used for data and other cables. The 480V cables will be installed in the other 6” section reserved for power and light conductors. The cross sectional area of the cable is inches. What is the maximum number of TC cables which can be installed in this cable tray? 7 10 13 15

6 Answer C. 13 392.22(1)(b)

7 NEC 3. High density polyethylene conduit (HDPE) size 3” may be used within a building. True False

8 Answer False 353.12(2)

9 NEC 4. A three phase, delta-wye transformer is rated at 480V/ 208V. It is feeding a 200 A, three phase, 208V panel with a 200A main breaker. The transformer is fed with an 100 ampere circuit breaker from a 480V panel. The secondary conductors are THHN 3/0 conductors and they are 8 feet in length. Is this an acceptable installation? Yes No

10 Answer Yes 240.21(C)(2)

11 NEC 5. A three, phase 480V to 208V transformer has a power rating of 35 kVA. What is the maximum sized circuit breaker that can be used for overcurrent protection for the transformer if it is protected only on the primary side? 45 amperes 50 amperes 60 amperes 75 amperes

12 Answer C. 60 amperes T 450.3(B) and 240.6

13 NEC 6. A three-phase, 208V piece of equipment is installed in a commercial building and located on the rooftop. The equipment is rated 50 amperes. The equipment is cord and plug connected. Is a GFCI receptacle required in this instance? Yes No

14 Answer A. Yes 210.8(B)(3)

15 NEC 7. A junction box which will contain conductors smaller than 6 AWG has a divider installed to separate power conductors from non-power conductors. The barrier is made of plastic and its volume allowance is not marked. What volume allowance shall be used for this barrier when calculating box fill? 1 cubic inch .75 cubic inch .66 cubic inch .5 cubic inch

16 Answer A. 1 cubic inch 314.16(A)

17 NEC 8. A ceiling mounted box used exclusively for lighting shall be designed or installed to support a luminaire weighing __________ pounds minimum. 16 25 50 100

18 Answer C. 50 314.27(A)(2)

19 NEC 9. A 208/120V circuit is installed in concrete and PVC conduit. The circuit will carry a load of 20 amperes. The overcurrent protection for the circuit is an inverse time 20 A circuit breaker. The ungrounded conductors for the circuit are 6 AWG copper conductors. What is the minimum sized equipment grounding conductor required for this installation? 12 10 8 6

20 Answer D. 6 (B)

21 NEC 10. When calculating conductor derating for NM cable, the ________ degrees C rating shall be used as long as the final calculated ampacity does not exceed that of a ________ degrees C rated conductor. 90/60 90/75 75/60 75/90

22 Answer A. 90/60 334.80

23 NEC 11. For electrical equipment mounted indoors, the space equal to the width of the equipment and extending from the floor to a height of ________ feet above the equipment or to the structural ceiling, whichever is lower, shall be dedicated to the electrical installation. 3 4 6 10

24 Answer C. 6 110.26(E)(1)

25 NEC 12. A non-metallic sheathed cable shall be secured and supported within ________ inches of a nonmetallic outlet box without cable clamps if installed in a park trailer. 10 12 6 8

26 Answer D. 8 552.48(I)

27 NEC 13. The auxiliary equipment of electric-discharge lamps mounted in a permanently installed luminaire where the luminaire are used for stadium lighting and mounted on poles shall be mounted no lower than _________ feet above the ground. 10 12 18 22

28 Answer A. 10 550.15(G)(1)

29 NEC 14. Luminaires in an agricultural building that may be exposed to water from condensation, cleansing water or solution shall be _____________ for use in wet locations. Approved Identified Labeled Listed

30 Answer D. Listed 547.8(C)

31 NEC 15. Each operating room in a health care facility shall be provided with a minimum of 36 receptacles divided between at least two branch circuits. At least ________, but no more than ______, shall be connected to either the normal system branch circuit or a critical branch circuit supplied by a different transfer switch than the other receptacles at the same location. 18/24 12/24 6/12 10/20

32 Answer B. 12/24 517.19(C)(1)

33 END of QUIz. THE TIME WILL STOP NOW
END of QUIz. THE TIME WILL STOP NOW. PLEASE CLICK ON THE SLIDE TO CONTINUE WITHOUT THE TIMER AND REVIEW EACH QUESTION.

34 NEC 1. A meeting room in a non-dwelling unit measures 15’ by 25’. What is the minimum number of floor box receptacle outlets required for this room? 1 2 3 4

35 Answer B. 2 210.71(b)(2)

36 NEC 2. In a ventilated trough cable tray, four conductor 10 AWG TC cable will be installed for 480V loads. The vented cable tray is 24” wide and is divided into two sections, One section is 18” and used for data and other cables. The 480V cables will be installed in the other 6” section reserved for power and light conductors. The cross sectional area of the cable is inches. What is the maximum number of TC cables which can be installed in this cable tray? 7 10 13 15

37 Answer C. 13 392.22(1)(b)

38 NEC 3. High density polyethylene conduit (HDPE) size 3” may be used within a building. True False

39 Answer False 353.12(2)

40 NEC 4. A three phase, delta-wye transformer is rated at 480V/ 208V. It is feeding a 200 A, three phase, 208V panel with a 200A main breaker. The transformer is fed with an 100 ampere circuit breaker from a 480V panel. The secondary conductors are THHN 3/0 conductors and they are 8 feet in length. Is this an acceptable installation? Yes No

41 Answer Yes 240.21(C)(2)

42 NEC 5. A three, phase 480V to 208V transformer has a power rating of 35 kVA. What is the maximum sized circuit breaker that can be used for overcurrent protection for the transformer if it is protected only on the primary side? 45 amperes 50 amperes 60 amperes 75 amperes

43 Answer C. 60 amperes T 450.3(B) and 240.6

44 NEC 6. A three-phase, 208V piece of equipment is installed in a commercial building and located on the rooftop. The equipment is rated 50 amperes. The equipment is cord and plug connected. Is a GFCI receptacle required in this instance? Yes No

45 Answer A. Yes 210.8(B)(3)

46 NEC 7. A junction box which will contain conductors smaller than 6 AWG has a divider installed to separate power conductors from non-power conductors. The barrier is made of plastic and its volume allowance is not marked. What volume allowance shall be used for this barrier when calculating box fill? 1 cubic inch .75 cubic inch .66 cubic inch .5 cubic inch

47 Answer A. 1 cubic inch 314.16(A)

48 NEC 8. A ceiling mounted box used exclusively for lighting shall be designed or installed to support a luminaire weighing __________ pounds minimum. 16 25 50 100

49 Answer C. 50 314.27(A)(2)

50 NEC 9. A 208/120V circuit is installed in concrete and PVC conduit. The circuit will carry a load of 20 amperes. The overcurrent protection for the circuit is an inverse time 20 A circuit breaker. The ungrounded conductors for the circuit are 6 AWG copper conductors. What is the minimum sized equipment grounding conductor required for this installation? 12 10 8 6

51 Answer D. 6 (B)

52 NEC 10. When calculating conductor derating for NM cable, the ________ degrees C rating shall be used as long as the final calculated ampacity does not exceed that of a ________ degrees C rated conductor. 90/60 90/75 75/60 75/90

53 Answer A. 90/60 334.80

54 NEC 11. For electrical equipment mounted indoors, the space equal to the width of the equipment and extending from the floor to a height of ________ feet above the equipment or to the structural ceiling, whichever is lower, shall be dedicated to the electrical installation. 3 4 6 10

55 Answer C. 6 110.26(E)(1)

56 NEC 12. A non-metallic sheathed cable shall be secured and supported within ________ inches of a nonmetallic outlet box without cable clamps if installed in a park trailer. 10 12 6 8

57 Answer D. 8 552.48(I)

58 NEC 13. The auxiliary equipment of electric-discharge lamps mounted in a permanently installed luminaire where the luminaire are used for stadium lighting and mounted on poles shall be mounted no lower than _________ feet above the ground. 10 12 18 22

59 Answer A. 10 550.15(G)(1)

60 NEC 14. Luminaires in an agricultural building that may be exposed to water from condensation, cleansing water or solution shall be _____________ for use in wet locations. Approved Identified Labeled Listed

61 Answer D. Listed 547.8(C)

62 NEC 15. Each operating room in a health care facility shall be provided with a minimum of 36 receptacles divided between at least two branch circuits. At least ________, but no more than ______, shall be connected to either the normal system branch circuit or a critical branch circuit supplied by a different transfer switch than the other receptacles at the same location. 18/24 12/24 6/12 10/20

63 Answer B. 12/24 517.19(C)(1)