Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith.

Similar presentations


Presentation on theme: "Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith."— Presentation transcript:

1 Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

2  Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide.  Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 10 seconds. You may also left click on the slide to manually transition.  Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill  Good luck  Remember to start the slide show to activate the timer. Copyright 2005 Ted "Smitty" Smith

3  This drill is a mixture of calculations and code look up questions. You have seen many of them before. Focus on time. Try to find all the answers before the slide transitions.  Remember do not worry about writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then.  Click on the slide to proceed. Copyright 2005 Ted "Smitty" Smith

4  Where handhold enclosures without bottoms are installed, all enclosed conductors and any splices or terminations, if present, shall be listed as suitable for ____________.  Corosive atmospheres  Special locations  Wet locations  None of the above

5 Copyright 2005 Ted "Smitty" Smith  wet locations 314.30(D)

6  What is the minimum headroom of working space required above a motor control center?  10 feet  3 feet  6.5 feet  5 feet Copyright 2005 Ted "Smitty" Smith

7  6.5 ft 110.26(E) Copyright 2005 Ted "Smitty" Smith

8  What is the minimum sized service required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts?  100 A  110 A  125 A  150 A

9 Copyright 2005 Ted "Smitty" Smith  125 A Article 220 Part III

10  How thick must sealing compound be in a ½” seal off in a class I, div. 1 area?  ½”  5/8”  ¾”  1” Copyright 2005 Ted "Smitty" Smith

11  5/8 “ 501.15(C)(3) Copyright 2005 Ted "Smitty" Smith

12  The non-heating leads on heating cables must be a minimum of _______________ in length.  2 feet  3 feet  6 feet  7 feet Copyright 2005 Ted "Smitty" Smith

13  7 ft 424.34 Copyright 2005 Ted "Smitty" Smith

14  Each unit length of heating cable shall have a lead wire with a color code of ______________ if it is rated to operate at 208V.  Yellow  Blue  Orange  Red Copyright 2005 Ted "Smitty" Smith

15  Blue 424.35 Copyright 2005 Ted "Smitty" Smith

16  The requirement of “shall be listed” indicates that a piece of material or equipment must ______________.  be accepted by an authority having jurisdiction  be tested by a qualified person  be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose. Copyright 2005 Ted "Smitty" Smith

17  be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose.  Article 100 Copyright 2005 Ted "Smitty" Smith

18  Where submersible pump is used in a metal well casing, the well casing shall be bonded to the pump circuit __________ conductor.  Equipment grounding  Bonding jumper  Grounded conductor  None of the above

19 Copyright 2005 Ted "Smitty" Smith  Equipment grounding 250.112(M)

20 Copyright 2005 Ted "Smitty" Smith  A single grounding electrode conductor can be used to connect multiple grounding electrodes.  True  False

21 Copyright 2005 Ted "Smitty" Smith  True 250.64(F)

22 Copyright 2005 Ted "Smitty" Smith  A single rod or pipe electrode shall have a resistance of _________ ohms or less to ground.  10 ohms  15 ohms  25 ohms  50 ohms

23 Copyright 2005 Ted "Smitty" Smith  25 250.56

24 Copyright 2005 Ted "Smitty" Smith  A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________.  Disconnecting means  Switching means  Thermal protection  None of the above

25 Copyright 2005 Ted "Smitty" Smith  Thermal Protection 410.73(E)(4)

26 Copyright 2005 Ted "Smitty" Smith  Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors?  Yes  No

27 Copyright 2005 Ted "Smitty" Smith  NO 240.21(C)

28 Copyright 2005 Ted "Smitty" Smith  All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system.  Present  Approved  Required  Inspected

29 Copyright 2005 Ted "Smitty" Smith  Present 250.50

30 Copyright 2005 Ted "Smitty" Smith  An enclosure mounted to structural or supporting elements of a suspended ceiling shall be not more than ______________________ in size and shall be securely fastened in place.  25 cubic inches  50 cubic inches  75 cubic inches  100 cubic inches

31 Copyright 2005 Ted "Smitty" Smith  100 cubic inches 314.23(D)

32 Copyright 2005 Ted "Smitty" Smith  Sheet metal boxes not over 100 cubic inches in size shall be made from steel not less than ______ inches thick.  1 inches .5 inches .0814 inches .0625 inches

33 Copyright 2005 Ted "Smitty" Smith .0625 inches 314.40(B)

34 Copyright 2005 Ted "Smitty" Smith  What is the minimum sized main bonding jumper, copper, required if a conductor is used and the supply conductors consist of 4 parallel runs of 500 kcmil copper conductors?  1/0 AWG  3/0 AWG  250 kcmil  500 kcmil

35 Copyright 2005 Ted "Smitty" Smith  250 kcmil 250.28(C) and Table 8  500 x 4= 2000 kcmil. 12.5% of 2000 kcmil is 250 A minimum of 250 kcmil wire is needed.

36 Copyright 2005 Ted "Smitty" Smith  The service entrance of a building may be located less than three feet from a window as long as the conductors are installed so that they___________ of the window.  Run parallel to the vertical edge  Run above the top level  Run along the bottom leve  None of the above

37 Copyright 2005 Ted "Smitty" Smith  Run above the top level 230.9(A)Ex

38 Copyright 2005 Ted "Smitty" Smith  What is the maximum sized duel element time delay fuse that can be used to provide branch circuit short circuit protection for a 40 hp, 208V, three-phase, induction motor, that has a nameplate full load current of 96.5 amperes? The motor is a design B motor with a marked service factor of 1.15.  100 A  150 A  200 A  225 A

39 Copyright 2005 Ted "Smitty" Smith  200A 430.52 Table and Exception

40 Copyright 2005 Ted "Smitty" Smith  Sheet metals screws shall not be used to connect grounding conductors or _______________ to enclosures as applied to grounding requirements.  Connection devices  Neutral bus bars  Mounting hardware  None of the above

41 Copyright 2005 Ted "Smitty" Smith  connection devices 250.8

42  Which of the following best describes the definition of accessible as applied to wiring methods:  Easy  Do not have to leave ground to access  Can be rendered accessible without damaging the structure or finish  No sweat Copyright 2005 Ted "Smitty" Smith

43  Can be rendered accessible without damaging the structure or finish  Article 100 Copyright 2005 Ted "Smitty" Smith

44  What is the minimum sized grounding electrode conductor required for a service that is supplied by (4) parallel runs of 500 kCMIL service entrance conductors? The conductors are copper and the grounding electrode conductor will also be copper.  3/0 AWG  300 kcmil  500 kcmil  1/0 AWG

45 Copyright 2005 Ted "Smitty" Smith  3/0 Table 250.66

46 Copyright 2005 Ted "Smitty" Smith  What is the minimum sized main bonding jumper that can be used for a service that is supplied by (3) parallel runs of 750 kcmil service entrance conductors? The service entrance conductors are copper.  1/0 AWG  2/0 AWG  300 kcmil  500 kcmil

47 Copyright 2005 Ted "Smitty" Smith  300 kcmil 250.28(D) and Table 8 for circular mills

48 Copyright 2005 Ted "Smitty" Smith  What is the minimum sized equipment grounding conductor that is required for a circuit that is protected by a 50 ampere overcurrent protective device if the ungrounded conductors are increased in size from a number 6 AWG, THHN to a number 2 AWG, THHN? All conductors are copper.  10 AWG  8 AWG  6 AWG  4 AWG

49 Copyright 2005 Ted "Smitty" Smith  4 AWG 250.22(B) and Table 8 for circular mills

50 Copyright 2005 Ted "Smitty" Smith  A junction box that is 18" x 18" x 6" that has two 1 1/2" EMT conduits entering and exiting through concentric knockouts and the conduits contain conductor that are number 4 AWG, THHN must be equipped with grounding bushings, threaded bosses or bonding lock nuts to accommodate the bonding and continuity requirements of article 250 of the NEC. The circuits in the junction box are operating at 208 volts, three-phase.  True  False

51 Copyright 2005 Ted "Smitty" Smith  False 250.96 and 250.97 would only be required if circuits were operating at more than 250 volts to ground.

52 Copyright 2005 Ted "Smitty" Smith  The earth shall not be considered as an effective ground fault current path.  True  False

53 Copyright 2005 Ted "Smitty" Smith  True 250.4(A)(5)

54 Copyright 2005 Ted "Smitty" Smith  Only those conduit bodies that are durably and visibly marked by the manufacturer with __________ shall be permitted to contain splices, taps, or devices.  Their size  Their volume allowance  Their dimensions  Their manufacturer

55 Copyright 2005 Ted "Smitty" Smith  their volume allowance 314.16(C)(2)

56 Copyright 2005 Ted "Smitty" Smith  An emergency system shall be suitable for the ___________________ available fault current at its terminals.  Minimum  Maximum  Listed  rated

57 Copyright 2005 Ted "Smitty" Smith  Maximum 700.5

58 Copyright 2005 Ted "Smitty" Smith  When grounding the outer conductive shield of a coaxial cable the maximum sized ground required shall be ______________ AWG copper  2 AWG  4 AWG  6 AWG  8 AWG

59 Copyright 2005 Ted "Smitty" Smith  6 820.100(A)(3)

60 Copyright 2005 Ted "Smitty" Smith  If a system is a three phase, three wire Delta configured system, operating at 230 Volts, is it required to be a grounded system?  Yes  No

61 Copyright 2005 Ted "Smitty" Smith  No  250.20(B)

62 Copyright 2005 Ted "Smitty" Smith  What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts?  8000 VA  8800 VA  9600 VA  10000 VA

63 Copyright 2005 Ted "Smitty" Smith  8800 VA Table 220.55 Note 1

64 Copyright 2005 Ted "Smitty" Smith  What is the minimum number of 15 ampere lighting circuits required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts?  1  2  3  5

65 Copyright 2005 Ted "Smitty" Smith  3 4500 VA of lighting load/120= 37.5A

66 Copyright 2005 Ted "Smitty" Smith  Raceways that carry service-conductors that are embedded in masonry shall be __________.  Sealed  Arranged to drain  Weatherproof  None of the above

67 Copyright 2005 Ted "Smitty" Smith  Arranged to drain 230.53

68 Copyright 2005 Ted "Smitty" Smith  What is the minimum sized grounding electrode conductor that can be used if the service entrance conductors are 250 kCMIL copper?  1 AWG  2 AWG  3 AWG  3/0 AWG

69 Copyright 2005 Ted "Smitty" Smith  2 AWG T250.66

70 Copyright 2005 Ted "Smitty" Smith  A cable tray may serve to carry service-entrance conductors along with other conductors as long as there is a ________.  Constraint  Listed device  Approved means  None of the above

71 Copyright 2005 Ted "Smitty" Smith  None of the above.  The actual answer is: Barrier 230.44Ex

72 Copyright 2005 Ted "Smitty" Smith  True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service.  True  False

73 Copyright 2005 Ted "Smitty" Smith  True 230.71(A)

74 Copyright 2005 Ted "Smitty" Smith  The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet.  1 feet  2 feet  3 feet  8 feet

75 Copyright 2005 Ted "Smitty" Smith  2 feet 230.54(C) Ex

76 Copyright 2005 Ted "Smitty" Smith  The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel.  250.122, 250.122(F)  110.14(C), 130.4  220.55, 310.16  None of the above

77 Copyright 2005 Ted "Smitty" Smith  250.122, 250.122(F) 215.2(A)

78 Copyright 2005 Ted "Smitty" Smith  Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________.  Phase  Color code  System  supply

79 Copyright 2005 Ted "Smitty" Smith  System 210.5(C)

80  Each of the slides will now be repeated.  They are not timed in this segment. To change a slide, click on the side with your left mouse button.  Be sure to physically look up the answers in your code book to improve your look up speed and skill. Copyright 2005 Ted "Smitty" Smith

81  Where handhold enclosures without bottoms are installed, all enclosed conductors and any splices or terminations, if present, shall be listed as suitable for ____________.  Corosive atmospheres  Special locations  Wet locations  None of the above

82 Copyright 2005 Ted "Smitty" Smith  wet locations 314.30(D)

83  What is the minimum headroom of working space required above a motor control center?  10 feet  3 feet  6.5 feet  5 feet Copyright 2005 Ted "Smitty" Smith

84  6.5 ft 110.26(E) Copyright 2005 Ted "Smitty" Smith

85  What is the minimum sized service required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts?  100 A  110 A  125 A  150 A

86 Copyright 2005 Ted "Smitty" Smith  125 A Article 220 Part III

87  How thick must sealing compound be in a ½” seal off in a class I, div. 1 area?  ½”  5/8”  ¾”  1” Copyright 2005 Ted "Smitty" Smith

88  5/8 “ 501.15(C)(3) Copyright 2005 Ted "Smitty" Smith

89  The non-heating leads on heating cables must be a minimum of _______________ in length.  2 feet  3 feet  6 feet  7 feet Copyright 2005 Ted "Smitty" Smith

90  7 ft 424.34 Copyright 2005 Ted "Smitty" Smith

91  Each unit length of heating cable shall have a lead wire with a color code of ______________ if it is rated to operate at 208V.  Yellow  Blue  Orange  Red Copyright 2005 Ted "Smitty" Smith

92  Blue 424.35 Copyright 2005 Ted "Smitty" Smith

93  The requirement of “shall be listed” indicates that a piece of material or equipment must ______________.  be accepted by an authority having jurisdiction  be tested by a qualified person  be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose. Copyright 2005 Ted "Smitty" Smith

94  be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose.  Article 100 Copyright 2005 Ted "Smitty" Smith

95  Where submersible pump is used in a metal well casing, the well casing shall be bonded to the pump circuit __________ conductor.  Equipment grounding  Bonding jumper  Grounded conductor  None of the above

96 Copyright 2005 Ted "Smitty" Smith  Equipment grounding 250.112(M)

97 Copyright 2005 Ted "Smitty" Smith  A single grounding electrode conductor can be used to connect multiple grounding electrodes.  True  False

98 Copyright 2005 Ted "Smitty" Smith  True 250.64(F)

99 Copyright 2005 Ted "Smitty" Smith  A single rod or pipe electrode shall have a resistance of _________ ohms or less to ground.  10 ohms  15 ohms  25 ohms  50 ohms

100 Copyright 2005 Ted "Smitty" Smith  25 250.56

101 Copyright 2005 Ted "Smitty" Smith  A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________.  Disconnecting means  Switching means  Thermal protection  None of the above

102 Copyright 2005 Ted "Smitty" Smith  Thermal Protection 410.73(E)(4)

103 Copyright 2005 Ted "Smitty" Smith  Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors?  Yes  No

104 Copyright 2005 Ted "Smitty" Smith  NO 240.21(C)

105 Copyright 2005 Ted "Smitty" Smith  All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system.  Present  Approved  Required  Inspected

106 Copyright 2005 Ted "Smitty" Smith  Present 250.50

107 Copyright 2005 Ted "Smitty" Smith  An enclosure mounted to structural or supporting elements of a suspended ceiling shall be not more than ______________________ in size and shall be securely fastened in place.  25 cubic inches  50 cubic inches  75 cubic inches  100 cubic inches

108 Copyright 2005 Ted "Smitty" Smith  100 cubic inches 314.23(D)

109 Copyright 2005 Ted "Smitty" Smith  Sheet metal boxes not over 100 cubic inches in size shall be made from steel not less than ______ inches thick.  1 inches .5 inches .0814 inches .0625 inches

110 Copyright 2005 Ted "Smitty" Smith .0625 inches 314.40(B)

111 Copyright 2005 Ted "Smitty" Smith  What is the minimum sized main bonding jumper, copper, required if a conductor is used and the supply conductors consist of 4 parallel runs of 500 kcmil copper conductors?  1/0 AWG  3/0 AWG  250 kcmil  500 kcmil

112 Copyright 2005 Ted "Smitty" Smith  250 kcmil 250.28(C) and Table 8  500 x 4= 2000 kcmil. 12.5% of 2000 kcmil is 250 A minimum of 250 kcmil wire is needed.

113 Copyright 2005 Ted "Smitty" Smith  The service entrance of a building may be located less than three feet from a window as long as the conductors are installed so that they___________ of the window.  Run parallel to the vertical edge  Run above the top level  Run along the bottom leve  None of the above

114 Copyright 2005 Ted "Smitty" Smith  Run above the top level 230.9(A)Ex

115 Copyright 2005 Ted "Smitty" Smith  What is the maximum sized duel element time delay fuse that can be used to provide branch circuit short circuit protection for a 40 hp, 208V, three-phase, induction motor, that has a nameplate full load current of 96.5 amperes? The motor is a design B motor with a marked service factor of 1.15.  100 A  150 A  200 A  225 A

116 Copyright 2005 Ted "Smitty" Smith  200A 430.52 Table and Exception

117 Copyright 2005 Ted "Smitty" Smith  Sheet metals screws shall not be used to connect grounding conductors or _______________ to enclosures as applied to grounding requirements.  Connection devices  Neutral bus bars  Mounting hardware  None of the above

118 Copyright 2005 Ted "Smitty" Smith  connection devices 250.8

119  Which of the following best describes the definition of accessible as applied to wiring methods:  Easy  Do not have to leave ground to access  Can be rendered accessible without damaging the structure or finish  No sweat Copyright 2005 Ted "Smitty" Smith

120  Can be rendered accessible without damaging the structure or finish  Article 100 Copyright 2005 Ted "Smitty" Smith

121  What is the minimum sized grounding electrode conductor required for a service that is supplied by (4) parallel runs of 500 kCMIL service entrance conductors? The conductors are copper and the grounding electrode conductor will also be copper.  3/0 AWG  300 kcmil  500 kcmil  1/0 AWG

122 Copyright 2005 Ted "Smitty" Smith  3/0 Table 250.66

123 Copyright 2005 Ted "Smitty" Smith  What is the minimum sized main bonding jumper that can be used for a service that is supplied by (3) parallel runs of 750 kcmil service entrance conductors? The service entrance conductors are copper.  1/0 AWG  2/0 AWG  300 kcmil  500 kcmil

124 Copyright 2005 Ted "Smitty" Smith  300 kcmil 250.28(D) and Table 8 for circular mills

125 Copyright 2005 Ted "Smitty" Smith  What is the minimum sized equipment grounding conductor that is required for a circuit that is protected by a 50 ampere overcurrent protective device if the ungrounded conductors are increased in size from a number 6 AWG, THHN to a number 2 AWG, THHN? All conductors are copper.  10 AWG  8 AWG  6 AWG  4 AWG

126 Copyright 2005 Ted "Smitty" Smith  4 AWG 250.22(B) and Table 8 for circular mills

127 Copyright 2005 Ted "Smitty" Smith  A junction box that is 18" x 18" x 6" that has two 1 1/2" EMT conduits entering and exiting through concentric knockouts and the conduits contain conductor that are number 4 AWG, THHN must be equipped with grounding bushings, threaded bosses or bonding lock nuts to accommodate the bonding and continuity requirements of article 250 of the NEC. The circuits in the junction box are operating at 208 volts, three-phase.  True  False

128 Copyright 2005 Ted "Smitty" Smith  False 250.96 and 250.97 would only be required if circuits were operating at more than 250 volts to ground.

129 Copyright 2005 Ted "Smitty" Smith  The earth shall not be considered as an effective ground fault current path.  True  False

130 Copyright 2005 Ted "Smitty" Smith  True 250.4(A)(5)

131 Copyright 2005 Ted "Smitty" Smith  Only those conduit bodies that are durably and visibly marked by the manufacturer with __________ shall be permitted to contain splices, taps, or devices.  Their size  Their volume allowance  Their dimensions  Their manufacturer

132 Copyright 2005 Ted "Smitty" Smith  their volume allowance 314.16(C)(2)

133 Copyright 2005 Ted "Smitty" Smith  An emergency system shall be suitable for the ___________________ available fault current at its terminals.  Minimum  Maximum  Listed  rated

134 Copyright 2005 Ted "Smitty" Smith  Maximum 700.5

135 Copyright 2005 Ted "Smitty" Smith  When grounding the outer conductive shield of a coaxial cable the maximum sized ground required shall be ______________ AWG copper  2 AWG  4 AWG  6 AWG  8 AWG

136 Copyright 2005 Ted "Smitty" Smith  6 820.100(A)(3)

137 Copyright 2005 Ted "Smitty" Smith  If a system is a three phase, three wire Delta configured system, operating at 230 Volts, is it required to be a grounded system?  Yes  No

138 Copyright 2005 Ted "Smitty" Smith  No  250.20(B)

139 Copyright 2005 Ted "Smitty" Smith  What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts?  8000 VA  8800 VA  9600 VA  10000 VA

140 Copyright 2005 Ted "Smitty" Smith  8800 VA Table 220.55 Note 1

141 Copyright 2005 Ted "Smitty" Smith  What is the minimum number of 15 ampere lighting circuits required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts?  1  2  3  5

142 Copyright 2005 Ted "Smitty" Smith  3 4500 VA of lighting load/120= 37.5A

143 Copyright 2005 Ted "Smitty" Smith  Raceways that carry service-conductors that are embedded in masonry shall be __________.  Sealed  Arranged to drain  Weatherproof  None of the above

144 Copyright 2005 Ted "Smitty" Smith  Arranged to drain 230.53

145 Copyright 2005 Ted "Smitty" Smith  What is the minimum sized grounding electrode conductor that can be used if the service entrance conductors are 250 kCMIL copper?  1 AWG  2 AWG  3 AWG  3/0 AWG

146 Copyright 2005 Ted "Smitty" Smith  2 AWG T250.66

147 Copyright 2005 Ted "Smitty" Smith  A cable tray may serve to carry service-entrance conductors along with other conductors as long as there is a ________.  Constraint  Listed device  Approved means  None of the above

148 Copyright 2005 Ted "Smitty" Smith  None of the above.  The actual answer is: Barrier 230.44Ex

149 Copyright 2005 Ted "Smitty" Smith  True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service.  True  False

150 Copyright 2005 Ted "Smitty" Smith  True 230.71(A)

151 Copyright 2005 Ted "Smitty" Smith  The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet.  1 feet  2 feet  3 feet  8 feet

152 Copyright 2005 Ted "Smitty" Smith  2 feet 230.54(C) Ex

153 Copyright 2005 Ted "Smitty" Smith  The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel.  250.122, 250.122(F)  110.14(C), 130.4  220.55, 310.16  None of the above

154 Copyright 2005 Ted "Smitty" Smith  250.122, 250.122(F) 215.2(A)

155 Copyright 2005 Ted "Smitty" Smith  Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________.  Phase  Color code  System  supply

156 Copyright 2005 Ted "Smitty" Smith  System 210.5(C)


Download ppt "Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith."