Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1.

Similar presentations


Presentation on theme: "Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1."— Presentation transcript:

1

2 Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

3 Instructions Click on the slide show ICON in the lower left hand corner of this screen to start the slide show. A question will appear and stay on the screen for 2 minutes. The question will then be replaced with the correct answer and code reference. This process will repeat until you reach a slide with a stop sign. You can then click on the slides and the questions and answers will be repeated without the timer so you can look up the answers or take notes. Do not worry about writing down the answers until after the timed portion of the program. Concentrate on finding the answer and improving your speed using the NEC. This drill is focused on changes to the 2008 NEC. (C) Copyright 2008 Ted "Smitty" Smith2

4 The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment. (C) Copyright 2008 Ted "Smitty" Smith3

5 Entirely independent 517.30(C)(1) (C) Copyright 2008 Ted "Smitty" Smith4

6 All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. (C) Copyright 2008 Ted "Smitty" Smith 5

7 An effective ground-fault current path 517.13(A) (C) Copyright 2008 Ted "Smitty" Smith6

8 The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason. (C) Copyright 2008 Ted "Smitty" Smith7

9 Limited amount 517.25 (C) Copyright 2008 Ted "Smitty" Smith8

10 Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility? Generator located on the premises Battery system A second external utility service, separate from the main external utility provided service An external utility service when the normal source of power consists of a generating unit located on premises. (C) Copyright 2008 Ted "Smitty" Smith9

11 A second external utility service 517.35(A) An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises. (C) Copyright 2008 Ted "Smitty" Smith10

12 The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________. (C) Copyright 2008 Ted "Smitty" Smith11

13 X-ray control 517.72(B) (C) Copyright 2008 Ted "Smitty" Smith12

14 The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source. (C) Copyright 2008 Ted "Smitty" Smith13

15 Delayed automatic 517.43(A) (C) Copyright 2008 Ted "Smitty" Smith14

16 The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation. (C) Copyright 2008 Ted "Smitty" Smith15

17 Equipment 517.30(B)(3) (C) Copyright 2008 Ted "Smitty" Smith16

18 Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment. (C) Copyright 2008 Ted "Smitty" Smith17

19 Critical care 517.19(F) (C) Copyright 2008 Ted "Smitty" Smith18

20 The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor. (C) Copyright 2008 Ted "Smitty" Smith19

21 100 517.13(B) (C) Copyright 2008 Ted "Smitty" Smith20

22 In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current. (C) Copyright 2008 Ted "Smitty" Smith21

23 Line isolation monitor 517.160(B) (C) Copyright 2008 Ted "Smitty" Smith22

24 The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater. (C) Copyright 2008 Ted "Smitty" Smith23

25 50 percent 517.72(A) (C) Copyright 2008 Ted "Smitty" Smith24

26 Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith25

27 Life safety 517.32(A) (C) Copyright 2008 Ted "Smitty" Smith26

28 Nurse call systems shall be provided power from the __________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith27

29 Critical branch 517.33(A)(5) (C) Copyright 2008 Ted "Smitty" Smith28

30 Each patient bed location shall be provided with a minimum of __________ receptacles. (C) Copyright 2008 Ted "Smitty" Smith29

31 Four 517.18(B) (C) Copyright 2008 Ted "Smitty" Smith30

32 The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG. (C) Copyright 2008 Ted "Smitty" Smith31

33 10 517.14 (C) Copyright 2008 Ted "Smitty" Smith32

34 End of Drill This is the end of the timed portion of the drill. You can now click on each slide and take your time reviewing the questions and answers. (C) Copyright 2008 Ted "Smitty" Smith33

35 The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment. (C) Copyright 2008 Ted "Smitty" Smith34

36 Entirely independent 517.30(C)(1) (C) Copyright 2008 Ted "Smitty" Smith35

37 All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. (C) Copyright 2008 Ted "Smitty" Smith 36

38 An effective ground-fault current path 517.13(A) (C) Copyright 2008 Ted "Smitty" Smith37

39 The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason. (C) Copyright 2008 Ted "Smitty" Smith38

40 Limited amount 517.25 (C) Copyright 2008 Ted "Smitty" Smith39

41 Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility? Generator located on the premises Battery system A second external utility service, separate from the main external utility provided service An external utility service when the normal source of power consists of a generating unit located on premises. (C) Copyright 2008 Ted "Smitty" Smith40

42 A second external utility service 517.35(A) An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises. (C) Copyright 2008 Ted "Smitty" Smith41

43 The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________. (C) Copyright 2008 Ted "Smitty" Smith42

44 X-ray control 517.72(B) (C) Copyright 2008 Ted "Smitty" Smith43

45 The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source. (C) Copyright 2008 Ted "Smitty" Smith44

46 Delayed automatic 517.43(A) (C) Copyright 2008 Ted "Smitty" Smith45

47 The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation. (C) Copyright 2008 Ted "Smitty" Smith46

48 Equipment 517.30(B)(3) (C) Copyright 2008 Ted "Smitty" Smith47

49 Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment. (C) Copyright 2008 Ted "Smitty" Smith48

50 Critical care 517.19(F) (C) Copyright 2008 Ted "Smitty" Smith49

51 The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor. (C) Copyright 2008 Ted "Smitty" Smith50

52 100 517.13(B) (C) Copyright 2008 Ted "Smitty" Smith51

53 In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current. (C) Copyright 2008 Ted "Smitty" Smith52

54 Line isolation monitor 517.160(B) (C) Copyright 2008 Ted "Smitty" Smith53

55 The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater. (C) Copyright 2008 Ted "Smitty" Smith54

56 50 percent 517.72(A) (C) Copyright 2008 Ted "Smitty" Smith55

57 Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith56

58 Life safety 517.32(A) (C) Copyright 2008 Ted "Smitty" Smith57

59 Nurse call systems shall be provided power from the __________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith58

60 Critical branch 517.33(A)(5) (C) Copyright 2008 Ted "Smitty" Smith59

61 Each patient bed location shall be provided with a minimum of __________ receptacles. (C) Copyright 2008 Ted "Smitty" Smith60

62 Four 517.18(B) (C) Copyright 2008 Ted "Smitty" Smith61

63 The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG. (C) Copyright 2008 Ted "Smitty" Smith62

64 10 517.14 (C) Copyright 2008 Ted "Smitty" Smith63