Calculation Speed Drill Varied-1

Similar presentations


Presentation on theme: "Calculation Speed Drill Varied-1"— Presentation transcript:

1 Calculation Speed Drill Varied-1
©Ted “Smitty” Smith 2011,2017

2 Click on the left mouse button to begin.
Instructions This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead of two minutes. Attempt to answer the questions and then when the slide show completes, Check your answer. When you reach the end of the drill all of the slides will be repeated without the timer so you will have time to check and verify your answers at that time. Click on the left mouse button to begin.

3 What is the minimum sized THHN conductor that can be used for conductors between the controller and the motor of a part winding connected, 5 HP, single phase, 208 volt motor that has a nameplate rating of amperes? All equipment has a 75 degree C temperature rating.

4 14 AWG

5 What is the demand on the main service entrance of an apartment complex that has a three phase, 480V service for 10 single phase, 208V ranges that have a nameplate rating of 14.2 kW?

6 37,950 VA

7 What size copper bonding jumper is required for the load side of a service if the service conductors are 4/0 copper and the main breaker is 200 amperes?

8 6 AWG

9 What is the maximum size inverse-time circuit breaker allowed for a 30 HP, three-phase, 208 volt, Design B motor for branch circuit, short circuit protection?

10 225 Amp

11 What is the demand on the main service entrance of a restaurant that has the following kitchen equipment? (3) Booster heaters for dishwashing equipment rated at 3.9 kW each (2) Deep fryers rated at 5.9 kW each (2) Electric grills rated at 11.2 kW each (1) Warming table rated at 2.9 kW

12 31.72 kVA

13 What is the minimum sized service that can be used for an office building that has a 480V, three phase service if the total calculated demand on the service is VA?

14 1000 Amp

15 What is the minimum circular mill rating for the feeder conductors that are run 100 ft from the service to an 84 amp calculated load supplied by 240 volt, three-wire system with a voltage drop of 3 percent applied? (CM is based on VD calculation)

16 30,100 CM

17 What size THWN copper conductors are required to supply a load on the secondary side of a transformer if the load is a continuous load of 50 amps and non-continuous load of 20 amps?

18 3 AWG

19 Calculate at continuous operation
What is the load in VA for the following luminaires: VA (each) recess luminaires VA (each) incandescent luminaires VA (each) electric discharge luminaires Calculate at continuous operation

20 VA

21 What size copper grounding electrode conductor is required to a ground rod if the service conductors are rated 250 KCMIL copper?

22 6 AWG

23 What is the demand load in VA for 55-11 kW ranges installed in an apartment complex?

24 66,250 VA

25 What is the lighting load in VA for 140 ft of show window used at continuous operation?

26 35,000 VA

27 What is the general lighting load and receptacle load and small-appliance plus laundry load for sq. ft dwelling units in a complex? (Calculate the load in VA)

28 51,150 VA

29 What is the demand load in VA for a range with a 16 kW rating?

30 9,600 VA

31 What is the load in VA for the general-purpose lighting load in a hotel or motel with 50 units of 420 sq. ft each?

32 18,800 VA

33 What is the demand on the main service entrance for 23- 4
What is the demand on the main service entrance for kW rated electric dryers?

34 40,250 VA

35 What is the load in VA for the general-purpose lighting load in a sq. ft beauty salon used continuously?

36 9,000 VA

37 What is the demand on the main service entrance in VA for a 11 kW range?

38 8,000 VA

39 What size THWN copper conductors are required to supply the secondary load of a transformer having a continuous load output of 212 amps? All terminations are rated at 90 degrees C.

40 300 kCMIL

41 What is the general lighting load and receptacle load and small-appliance plus laundry loads for a sq. Ft dwelling unit? (Calculate the load in VA)

42 6,675 VA

43 What is the maximum size nontime-delay fuse allowed for branch circuit, short circuit protection for a 40 HP, three-phase, 460 volt, Design B motor?

44 175 Amp

45 What is the demand on the main service of a dwelling unit for a 1
What is the demand on the main service of a dwelling unit for a 1.2 kW garbage disposal, a 3.2 kW water heater and a 2.1 kW dishwasher? None of the appliances are cord and plug connected.

46 6500 VA

47 What is the general lighting demand and receptacle demand and small-appliance plus laundry loads on the service entrance for a sq. ft dwelling unit? (Calculate the load in VA)

48 10,140 VA

49 What is the minimum volume allowance required in a plastic box for a duplex receptacle and (3) 14/2 NM cables?

50 12

51 What is the general lighting load and receptacle load and small-appliance plus laundry load for sq. ft dwelling units in a complex? (Calculate the load in VA)

52 45,225 VA

53 What is minimum sized EMT which can be used for the installation of (4) 6 THHN, (3) 2 TW and (1) 12 THHN conductors?

54 1 ½ Inch

55 What is the general lighting demand and receptacle demand and small-appliance plus laundry in a multifamily dwelling unit with the following area? (Calculate the load in VA) sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units

56 69,037.5 VA

57 What is the demand in VA for the general- purpose lighting load and core receptacle demand in a 7000 sq. ft office facility?

58 24,500 VA

59 What is the load in VA for a 208 volt, three- phase, 68 amp load operating for six hours and supplied by an individual branch circuit?

60 30,622 VA

61 What is the maximum size instantaneous trip breaker allowed for branch circuit, short circuit protection for a 20 HP, three-phase, 230 volt, Design A motor?

62 450 Amp

63 What is the minimum rating of an overload device required for a 5 horsepower, single phase, 208V motor with a marked service factor of 1.15 and a full load current of amperes?

64 28.25 amps

65 What is the load in VA for the general-purpose lighting load in a sq. ft bank used continuously?

66 29,750 VA

67 What is the load in VA for the general- purpose lighting load in a school building with the following area: (Calculate at continuous operation) 20,000 sq. ft classroom area 5000 sq. ft auditorium area

68 81,250 VA

69 What is the minimum sized THHN conductor that can be used between the controller and the motor for a 15 HP, three phase, 208V, wye start, delta run connected motor that has a nameplate rating of amperes, a marked service factor of 1.15 if all equipment is rated at 90 degrees C?

70 10 AWG

71 What is the demand load in VA for three pieces of cooking equipment with a 10 kW, 14 kW, and 16 kW rating installed in a dwelling unit?

72 15,400 VA

73 What is the demand load in VA and amps for 15, 208 volt, single phase cooking units rated 10 kW each on a three phase service?

74 37,500 VA

75 What is the minimum ampacity required for the secondary conductors of a transformer which are 23 feet in length when protected by a 300 amp overcurrent protection device on the primary side. The transformer has a 480 volt primary and 208 volt secondary?

76 230 Amps

77 What is the demand load in VA for a 5 kW dryer?

78 5000 VA

79 What size RHW copper conductors are required to supply a feeder with a continuous load of 172 amps and a non- continuous load of 80 amps? All terminations are rated at 90 degrees C.

80 350 kCMIL

81 What minimum sized SO cord which can be used to feed a 50 ampere, three phase, 208V load?

82 Size 5

83 What is the maximum sized time delay fuse allowed for branch circuit, short circuit protection of a 20 HP, three-phase, 208 volt, Design B motor?

84 110 Amp

85 What is the load in VA for the general- purpose lighting load in a 40,000 sq. ft store if 20,000 sq. ft is warehouse space? (Used at continuous operation)

86 81,250 VA

87 What is the load in VA for 50, 120 volt, lighting ballast rated at 1
What is the load in VA for 50, 120 volt, lighting ballast rated at 1.5 amps each and used for 8 hours a day?

88 11,250 VA

89 What is the demand load in VA for 10-3 kW cooktops and 10- 8
What is the demand load in VA for kW cooktops and kW ovens installed in an apartment complex?

90 35,000 VA

91 What is the maximum sized time delay fuse which can be used to protect the feeder conductors for five, 10 HP, 480V three motors? Each motor has a name plate rating of 12.1 A, a marked service factor of 1.15, and they are design B. Each motor has a 20 Ampere time delay fuse branch circuit short circuit protection.

92 70 amps

93 What is the lighting load in VA for 140 ft of show window used at non- continuous operation?

94 28000 VA

95 A separate over load device shall be selected to trip at ____________ amperes for overload protection of a 7.5 HP, two phase, 230 V motor with a marked full load current of amperes and a marked service factor of

96 17 amps

97 What is the total current which can be carried by a 10 THHN aluminum conductor if it is installed in a conduit with a total of 8 current carrying conductors and the conduit is installed in an ambient temperature of 99 degrees F? All terminations will be rated at 90 degrees C.

98 22.3 Amps

99 What is the lighting load in VA for 100 ft of track lighting used at non-continuous operation?

100 7500 VA

101 What is the demand on the main service entrance for two cooktops with a 3 kW rating?

102 4500 VA

103 What size copper grounding electrode conductor is required to concrete encased electrode if the service conductors are four parallel runs of 500 KCMIL copper?

104 4 AWG

105 What is the lighting load in VA for the patient bedrooms in a 52,000 sq. ft hospital? Assume all loads will be used for 3 hours or more at a time.

106 13,500 VA

107 What is the demand on the main service entrance, in VA, for a 12 kW cooktop, 8 kW oven, and 4kW oven installed in a dwelling unit?

108 14,000 VA

109 What is the lighting load in VA for 15 continuous operated luminaires with a 75 VA ballast in each unit and 15 non-continuous operated luminaires with 75 VA in each unit?

110 VA

111 What is the lighting load in VA for 50 continuous operated luminaires with a 150 VA ballast in each unit?

112 9375 VA

113 What is the general lighting demand including the receptacle load and small-appliance plus laundry demand in a multifamily dwelling unit with the following area? (Calculate the load in VA and round answer to nearest whole number) sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units

114 53,438 VA

115 What size THWN copper conductors are required to supply the secondary side of a 480V to 208V, three phase transformer having a continuous load output of 194 amps? The transformer secondary conductors will not have overcurrent protection. They are 8 feet in length. The transformer primary conductors are protected by a 90 ampere inverse time circuit breaker. The secondary conductors terminate into a 200 A main breaker for a 208V three phase panel. The secondary conductors leave the transformer enclosure. All terminations are rated for 90 degrees C.

116 3/0 THWN

117 What is the voltage drop experienced on a 6 AWG aluminum conductor which is supplying a load of 23 amperes if the load is located 116 meters from the source of power? (Round answer to the nearest whole number)

118 14 Volts

119 What is the minimum sized THHN conductor which can be used to feed eight 5 HP, thee phase motors rated at 208V and FLA, Design C and 1.15 service factor?

120 1/0 THHN

121 What is the primary line current of a 480 to 208 V three phase, delta-wye transformer if the secondary line current is 278 amperes? ( Assume 100% efficiency and round your answer to the nearest whole number.)

122 120 amps

123 What is the demand load in VA for five 10 kW and six 13 kW cooking units?

124 27,300 VA

125 What is the lighting load in VA for 203 ft
What is the lighting load in VA for 203 ft. of track lighting used at continuous operation?

126 19,125 VA

127 What is the minimum sized THHN conductor which can be used to feed five arc welders. Each arc welder has a rating of 60 duty cycle and 28 amps I1eff.

128 1/0 THHN

129 What is the demand load in VA for 28-12 kW ranges installed in an apartment complex?

130 43,000 VA

131 What is the maximum sized inverse time circuit breaker which can be used to protect from overcurrent the RHW feeder conductors which are feeding four resistance welders which are rated at 30 duty cycle and 23 amperes? The feeders are 2 AWG aluminum.

132 300 amps

133 What is the load in VA for the general- purpose lighting load in a 8400 sq. ft church used continuously?

134 10,500 VA

135 What is the demand load in VA for 12-2
What is the demand load in VA for kW ovens and a kW cooktops installed in an apartment complex? ( Give your answer in kVA)

136 20.46 kVA

137 What is the load in VA for 150 ft of multioutlet assembly used to cord-and- plug connect loads that are used simultaneously?

138 27,000 VA

139 What is the minimum sized TW conductor which can be used to feed a 2 HP, single phase, 120V motor which is rated for 15 minute running and will be used for intermittent duty? The motor is rated at FLA.

140 12 AWG

141 What is the ampacity of an XHHW aluminum, 8 AWG conductor installed in an ambient temperature of 102 degrees F? The conductor and all terminations are rated 90 degrees C.

142 39.5 amps

143 A 200 ampere, 208V single phase panel is installed for a single family dwelling. What is the minimum sized aluminum RHW conductor which can be used as a service entrance conductor?

144 4/0 RHW

145 What size copper grounding electrode conductor is required to a metal water main pipe if the service conductors are rated 350 KCMIL copper?

146 2 AWG

147 What is the demand load in VA for twenty five 15 kW ranges installed in an apartment complex?

148 46,000 VA

149 What is the maximum setting for the overload relay for a 30 HP, 480V, synchronous motor with a FLC of 26.1 amperes and a temperature rise of 40 degrees C? Assume the minimum setting has been tried and the motor will not start. Round your answer DOWN to the nearest whole number.)

150 36 amperes

151 What is the demand on the main service entrance of an apartment complex that has a single phase, 240V service for 31 dryers that have a nameplate rating of 4.3 KW? Copyright 2005 Ted "Smitty" Smith

152 48050 VA

153 What is the minimum required bending space required for four parallel runs of 250 kCMIL compact AA conductors if the conductors will enter the enclosure on the side opposite the termination lugs?

154 6.5 inches

155 A run of 4/0 THHN conductors will be ran vertically in a raceway
A run of 4/0 THHN conductors will be ran vertically in a raceway. The total vertical length of the raceway is 376 feet. What is the minimum number of conductor supports that will need to be ordered for each conductor?

156 6

157 What is the demand load in VA for a 4 kW dryer?

158 5000 VA

159 What size copper equipment grounding conductor is required to ground to be ran with the ungrounded 4 THHN conductors feeding a piece of equipment which pulls a load of 18.2 amps. The conductors are fed by a 20 ampere circuit breaker? The ungrounded conductors in the circuit are size 4 THHN.

160 4 AWG

161 What is the fixed-appliance demand in VA for the ungrounded (phase) conductors with the following fastened in place appliances: 6000 VA water heater 1400 VA disposal 1050 VA compactor

162 8450 VA

163 What is the demand load in VA for 45 dryers rated at 6500 VA each?

164 73,125 VA

165 A recreational vehicle park will have ten 50A sites, fifteen 30A sites, ten 20A sites and five sites reserved for tent sites. What is the minimum demand on the main service entrance for all the sites?

166 38,130 VA

167 What is the minimum sized THHN conductor which can be used to feed a fixed storage type water heater rated at 100 gallons and amperes?

168 6 AWG

169 What is the load in VA for 148 general- purpose duplex receptacles used to serve non- continuous operated loads in an office building?

170 36640 VA

171 What is the minimum number of 120V, 20 A circuits which can be used to feed 145 ft of multioutlet assembly used to cord-and-plug connect loads that are not used simultaneously? The assembly will have a duplex receptacle mounted every 12 inches.

172 3

173 What is the demand load in VA and amps for 15, 208 volt, single-phase cooking units rated 9 kW each?

174 30,000 VA

175 What is the demand in VA for a group of 208 volt, three-phase motors rated at 30 HP, 20 HP, and 10 HP? ( Assume these are the only motor loads on the service.) Round your answer to the nearest whole number.

176 69,035 VA

177 What minimum sized copper bonding jumper is required on the line side of a service if the service conductors are five parallel runs of 500 kCMIL copper?

178 350 kCMIL

179 Stop This is the end of the presentation.
You can now review the slides and answers without the timer. Click the slide to advance to the next slide

180 What is the minimum sized THHN conductor that can be used for conductors between the controller and the motor of a part winding connected, 5 HP, single phase, 208 volt motor that has a nameplate rating of amperes? All equipment has a 75 degree C temperature rating.

181 14 AWG

182 What is the demand on the main service entrance of an apartment complex that has a three phase, 480V service for 10 single phase, 208V ranges that have a nameplate rating of 14.2 kW?

183 37,950 VA

184 What size copper bonding jumper is required for the load side of a service if the service conductors are 4/0 copper and the main breaker is 200 amperes?

185 6 AWG

186 What is the maximum size inverse-time circuit breaker allowed for a 30 HP, three-phase, 208 volt, Design B motor for branch circuit, short circuit protection?

187 225 Amp

188 What is the demand on the main service entrance of a restaurant that has the following kitchen equipment? (3) Booster heaters for dishwashing equipment rated at 3.9 kW each (2) Deep fryers rated at 5.9 kW each (2) Electric grills rated at 11.2 kW each (1) Warming table rated at 2.9 kW

189 31.72 kVA

190 What is the minimum sized service that can be used for an office building that has a 480V, three phase service if the total calculated demand on the service is VA?

191 1000 Amp

192 What is the minimum circular mill rating for the feeder conductors that are run 100 ft from the service to an 84 amp calculated load supplied by 240 volt, three-wire system with a voltage drop of 3 percent applied? (CM is based on VD calculation)

193 30,100 CM

194 What size THWN copper conductors are required to supply a load on the secondary side of a transformer if the load is a continuous load of 50 amps and non-continuous load of 20 amps?

195 3 AWG

196 Calculate at continuous operation
What is the load in VA for the following luminaires: VA (each) recess luminaires VA (each) incandescent luminaires VA (each) electric discharge luminaires Calculate at continuous operation

197 VA

198 What size copper grounding electrode conductor is required to a ground rod if the service conductors are rated 250 KCMIL copper?

199 6 AWG

200 What is the demand load in VA for 55-11 kW ranges installed in an apartment complex?

201 66,250 VA

202 What is the lighting load in VA for 140 ft of show window used at continuous operation?

203 35,000 VA

204 What is the general lighting load and receptacle load and small-appliance plus laundry load for sq. ft dwelling units in a complex? (Calculate the load in VA)

205 51,150 VA

206 What is the demand load in VA for a range with a 16 kW rating?

207 9,600 VA

208 What is the load in VA for the general-purpose lighting load in a hotel or motel with 50 units of 420 sq. ft each?

209 18,800 VA

210 What is the demand on the main service entrance for 23- 4
What is the demand on the main service entrance for kW rated electric dryers?

211 40,250 VA

212 What is the load in VA for the general-purpose lighting load in a sq. ft beauty salon used continuously?

213 9,000 VA

214 What is the demand on the main service entrance in VA for a 11 kW range?

215 8,000 VA

216 What size THWN copper conductors are required to supply the secondary load of a transformer having a continuous load output of 212 amps? All terminations are rated at 90 degrees C.

217 300 kCMIL

218 What is the general lighting load and receptacle load and small-appliance plus laundry loads for a sq. Ft dwelling unit? (Calculate the load in VA)

219 6,675 VA

220 What is the maximum size nontime-delay fuse allowed for branch circuit, short circuit protection for a 40 HP, three-phase, 460 volt, Design B motor?

221 175 Amp

222 What is the demand on the main service of a dwelling unit for a 1
What is the demand on the main service of a dwelling unit for a 1.2 kW garbage disposal, a 3.2 kW water heater and a 2.1 kW dishwasher? None of the appliances are cord and plug connected.

223 6500 VA

224 What is the general lighting demand and receptacle demand and small-appliance plus laundry loads on the service entrance for a sq. ft dwelling unit? (Calculate the load in VA)

225 10,140 VA

226 What is the minimum volume allowance required in a plastic box for a duplex receptacle and (3) 14/2 NM cables?

227 12

228 What is the general lighting load and receptacle load and small-appliance plus laundry load for sq. ft dwelling units in a complex? (Calculate the load in VA)

229 45,225 VA

230 What is minimum sized EMT which can be used for the installation of (4) 6 THHN, (3) 2 TW and (1) 12 THHN conductors?

231 1 ½ Inch

232 What is the general lighting demand and receptacle demand and small-appliance plus laundry in a multifamily dwelling unit with the following area? (Calculate the load in VA) sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units

233 69,037.5 VA

234 What is the demand in VA for the general- purpose lighting load and core receptacle demand in a 7000 sq. ft office facility?

235 24,500 VA

236 What is the load in VA for a 208 volt, three- phase, 68 amp load operating for six hours and supplied by an individual branch circuit?

237 30,622 VA

238 What is the maximum size instantaneous trip breaker allowed for branch circuit, short circuit protection for a 20 HP, three-phase, 230 volt, Design A motor?

239 450 Amp

240 What is the minimum rating of an overload device required for a 5 horsepower, single phase, 208V motor with a marked service factor of 1.15 and a full load current of amperes?

241 28.25 amps

242 What is the load in VA for the general-purpose lighting load in a sq. ft bank used continuously?

243 29,750 VA

244 What is the load in VA for the general- purpose lighting load in a school building with the following area: (Calculate at continuous operation) 20,000 sq. ft classroom area 5000 sq. ft auditorium area

245 81,250 VA

246 What is the minimum sized THHN conductor that can be used between the controller and the motor for a 15 HP, three phase, 208V, wye start, delta run connected motor that has a nameplate rating of amperes, a marked service factor of 1.15 if all equipment is rated at 90 degrees C?

247 10 AWG

248 What is the demand load in VA for three pieces of cooking equipment with a 10 kW, 14 kW, and 16 kW rating installed in a dwelling unit?

249 15,400 VA

250 What is the demand load in VA and amps for 15, 208 volt, single phase cooking units rated 10 kW each on a three phase service?

251 37,500 VA

252 What is the minimum ampacity required for the secondary conductors of a transformer which are 23 feet in length when protected by a 300 amp overcurrent protection device on the primary side. The transformer has a 480 volt primary and 208 volt secondary?

253 230 Amps

254 What is the demand load in VA for a 5 kW dryer?

255 5000 VA

256 What size RHW copper conductors are required to supply a feeder with a continuous load of 172 amps and a non- continuous load of 80 amps? All terminations are rated at 90 degrees C.

257 350 kCMIL

258 What minimum sized SO cord which can be used to feed a 50 ampere, three phase, 208V load?

259 Size 5

260 What is the maximum sized time delay fuse allowed for branch circuit, short circuit protection of a 20 HP, three-phase, 208 volt, Design B motor?

261 110 Amp

262 What is the load in VA for the general- purpose lighting load in a 40,000 sq. ft store if 20,000 sq. ft is warehouse space? (Used at continuous operation)

263 81,250 VA

264 What is the load in VA for 50, 120 volt, lighting ballast rated at 1
What is the load in VA for 50, 120 volt, lighting ballast rated at 1.5 amps each and used for 8 hours a day?

265 11,250 VA

266 What is the demand load in VA for 10-3 kW cooktops and 10- 8
What is the demand load in VA for kW cooktops and kW ovens installed in an apartment complex?

267 35,000 VA

268 What is the maximum sized time delay fuse which can be used to protect the feeder conductors for five, 10 HP, 480V three motors? Each motor has a name plate rating of 12.1 A, a marked service factor of 1.15, and they are design B. Each motor has a 20 Ampere time delay fuse branch circuit short circuit protection.

269 70 amps

270 What is the lighting load in VA for 140 ft of show window used at non- continuous operation?

271 28000 VA

272 A separate over load device shall be selected to trip at ____________ amperes for overload protection of a 7.5 HP, two phase, 230 V motor with a marked full load current of amperes and a marked service factor of

273 17 amps

274 What is the total current which can be carried by a 10 THHN aluminum conductor if it is installed in a conduit with a total of 8 current carrying conductors and the conduit is installed in an ambient temperature of 99 degrees F? All terminations will be rated at 90 degrees C.

275 22.3 Amps

276 What is the lighting load in VA for 100 ft of track lighting used at non-continuous operation?

277 7500 VA

278 What is the demand on the main service entrance for two cooktops with a 3 kW rating?

279 4500 VA

280 What size copper grounding electrode conductor is required to concrete encased electrode if the service conductors are four parallel runs of 500 KCMIL copper?

281 4 AWG

282 What is the lighting load in VA for the patient bedrooms in a 52,000 sq. ft hospital? Assume all loads will be used for 3 hours or more at a time.

283 13,500 VA

284 What is the demand on the main service entrance, in VA, for a 12 kW cooktop, 8 kW oven, and 4kW oven installed in a dwelling unit?

285 14,000 VA

286 What is the lighting load in VA for 15 continuous operated luminaires with a 75 VA ballast in each unit and 15 non-continuous operated luminaires with 75 VA in each unit?

287 VA

288 What is the lighting load in VA for 50 continuous operated luminaires with a 150 VA ballast in each unit?

289 9375 VA

290 What is the general lighting demand including the receptacle load and small-appliance plus laundry demand in a multifamily dwelling unit with the following area? (Calculate the load in VA and round answer to nearest whole number) sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units sq. ft dwelling units

291 53,438 VA

292 What size THWN copper conductors are required to supply the secondary side of a 480V to 208V, three phase transformer having a continuous load output of 194 amps? The transformer secondary conductors will not have overcurrent protection. They are 8 feet in length. The transformer primary conductors are protected by a 90 ampere inverse time circuit breaker. The secondary conductors terminate into a 200 A main breaker for a 208V three phase panel. The secondary conductors leave the transformer enclosure. All terminations are rated for 90 degrees C.

293 3/0 THWN

294 What is the voltage drop experienced on a 6 AWG aluminum conductor which is supplying a load of 23 amperes if the load is located 116 meters from the source of power? (Round answer to the nearest whole number)

295 14 Volts

296 What is the minimum sized THHN conductor which can be used to feed eight 5 HP, thee phase motors rated at 208V and FLA, Design C and 1.15 service factor?

297 1/0 THHN

298 What is the primary line current of a 480 to 208 V three phase, delta-wye transformer if the secondary line current is 278 amperes? ( Assume 100% efficiency and round your answer to the nearest whole number.)

299 120 amps

300 What is the demand load in VA for five 10 kW and six 13 kW cooking units?

301 27,300 VA

302 What is the lighting load in VA for 203 ft
What is the lighting load in VA for 203 ft. of track lighting used at continuous operation?

303 19,125 VA

304 What is the minimum sized THHN conductor which can be used to feed five arc welders. Each arc welder has a rating of 60 duty cycle and 28 amps I1eff.

305 1/0 THHN

306 What is the demand load in VA for 28-12 kW ranges installed in an apartment complex?

307 43,000 VA

308 What is the maximum sized inverse time circuit breaker which can be used to protect from overcurrent the RHW feeder conductors which are feeding four resistance welders which are rated at 30 duty cycle and 23 amperes? The feeders are 2 AWG aluminum.

309 300 amps

310 What is the load in VA for the general- purpose lighting load in a 8400 sq. ft church used continuously?

311 10,500 VA

312 What is the demand load in VA for 12-2
What is the demand load in VA for kW ovens and a kW cooktops installed in an apartment complex? ( Give your answer in kVA)

313 20.46 kVA

314 What is the load in VA for 150 ft of multioutlet assembly used to cord-and- plug connect loads that are used simultaneously?

315 27,000 VA

316 What is the minimum sized TW conductor which can be used to feed a 2 HP, single phase, 120V motor which is rated for 15 minute running and will be used for intermittent duty? The motor is rated at FLA.

317 12 AWG

318 What is the ampacity of an XHHW aluminum, 8 AWG conductor installed in an ambient temperature of 102 degrees F? The conductor and all terminations are rated 90 degrees C.

319 39.5 amps

320 A 200 ampere, 208V single phase panel is installed for a single family dwelling. What is the minimum sized aluminum RHW conductor which can be used as a service entrance conductor?

321 4/0 RHW

322 What size copper grounding electrode conductor is required to a metal water main pipe if the service conductors are rated 350 KCMIL copper?

323 2 AWG

324 What is the demand load in VA for twenty five 15 kW ranges installed in an apartment complex?

325 46,000 VA

326 What is the maximum setting for the overload relay for a 30 HP, 480V, synchronous motor with a FLC of 26.1 amperes and a temperature rise of 40 degrees C? Assume the minimum setting has been tried and the motor will not start. Round your answer DOWN to the nearest whole number.)

327 36 amperes

328 What is the demand on the main service entrance of an apartment complex that has a single phase, 240V service for 31 dryers that have a nameplate rating of 4.3 KW? Copyright 2005 Ted "Smitty" Smith

329 48050 VA

330 What is the minimum required bending space required for four parallel runs of 250 kCMIL compact AA conductors if the conductors will enter the enclosure on the side opposite the termination lugs?

331 6.5 inches

332 A run of 4/0 THHN conductors will be ran vertically in a raceway
A run of 4/0 THHN conductors will be ran vertically in a raceway. The total vertical length of the raceway is 376 feet. What is the minimum number of conductor supports that will need to be ordered for each conductor?

333 6

334 What is the demand load in VA for a 4 kW dryer?

335 5000 VA

336 What size copper equipment grounding conductor is required to ground to be ran with the ungrounded 4 THHN conductors feeding a piece of equipment which pulls a load of 18.2 amps. The conductors are fed by a 20 ampere circuit breaker? The ungrounded conductors in the circuit are size 4 THHN.

337 4 AWG

338 What is the fixed-appliance demand in VA for the ungrounded (phase) conductors with the following fastened in place appliances: 6000 VA water heater 1400 VA disposal 1050 VA compactor

339 8450 VA

340 What is the demand load in VA for 45 dryers rated at 6500 VA each?

341 73,125 VA

342 A recreational vehicle park will have ten 50A sites, fifteen 30A sites, ten 20A sites and five sites reserved for tent sites. What is the minimum demand on the main service entrance for all the sites?

343 38,130 VA

344 What is the minimum sized THHN conductor which can be used to feed a fixed storage type water heater rated at 100 gallons and amperes?

345 6 AWG

346 What is the load in VA for 148 general- purpose duplex receptacles used to serve non- continuous operated loads in an office building?

347 36640 VA

348 What is the minimum number of 120V, 20 A circuits which can be used to feed 145 ft of multioutlet assembly used to cord-and-plug connect loads that are not used simultaneously? The assembly will have a duplex receptacle mounted every 12 inches.

349 3

350 What is the demand load in VA and amps for 15, 208 volt, single-phase cooking units rated 9 kW each?

351 30,000 VA

352 What is the demand in VA for a group of 208 volt, three-phase motors rated at 30 HP, 20 HP, and 10 HP? ( Assume these are the only motor loads on the service.) Round your answer to the nearest whole number.

353 69,035 VA

354 What minimum sized copper bonding jumper is required on the line side of a service if the service conductors are five parallel runs of 500 kCMIL copper?

355 350 kCMIL