Presentation is loading. Please wait.

Presentation is loading. Please wait.

Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6.

Similar presentations


Presentation on theme: "Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6."— Presentation transcript:

1 Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6

2 Copyright 2005 Ted "Smitty" Smith Directions Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 5 seconds. Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill Good luck

3 Further More You have seen all of these questions before. This time the slides will transition at different rates of speed. Remember do not worry about writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then. Copyright 2005 Ted "Smitty" Smith

4 Raceways LFMC shall be securely fastened in place by an approved means with in _______ inches of each box, cabinet, conduit body, or other conduit termination.

5 Copyright 2005 Ted "Smitty" Smith Raceways 12” 350.30(A)

6 Copyright 2005 Ted "Smitty" Smith Equipment Any wiring behind heating or heating panel sets located in interior walls or partitions shall be considered as operating at an ambient temperature of _______________ degrees Celsius and the ampacity shall be calculated on the basis of the correction factors given Article 310.

7 Copyright 2005 Ted "Smitty" Smith Equipment 40 degrees 424.95(B)

8 Copyright 2005 Ted "Smitty" Smith Overcurrent Protection According to Article ___________________ of the 2005 NEC, nonstandard fuses are permitted.

9 Copyright 2005 Ted "Smitty" Smith Overcurrent Protection True 240.6(A)

10 Copyright 2005 Ted "Smitty" Smith Services A cable tray may serve to carry service- entrance conductors along with other conductors as long as there is a ________.

11 Copyright 2005 Ted "Smitty" Smith Services Barrier 230.44Ex

12 Copyright 2005 Ted "Smitty" Smith Services True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service.

13 Copyright 2005 Ted "Smitty" Smith Services True 230.71(A)

14 Copyright 2005 Ted "Smitty" Smith Services The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet.

15 Copyright 2005 Ted "Smitty" Smith Services 2 feet 230.54(C) Ex

16 Copyright 2005 Ted "Smitty" Smith Grounding For multiple separately derived systems the common grounding electrode conductor shall not be smaller than __________________.

17 Copyright 2005 Ted "Smitty" Smith Grounding 3/0 CU or 250Kcm AL 250.30(A)(4)(a)

18 Copyright 2005 Ted "Smitty" Smith Raceways The minimum burial depth for a nonmetallic raceway with no vehicular traffic shall be __________________ inches.

19 Copyright 2005 Ted "Smitty" Smith Raceways 4" Table 300.5 Col. 3

20 Copyright 2005 Ted "Smitty" Smith Calculations A conductor passing through a junction box with a loop length of ______________ shall be counted twice for box fill calculations.

21 Copyright 2005 Ted "Smitty" Smith Calculations Twice the minimum length required by Article 300.14 314.16(B)(1)

22 Copyright 2005 Ted "Smitty" Smith Grounding When bonding equipment, __________shall not be used for this connection and the termination shall not depend solely on__________________.

23 Copyright 2005 Ted "Smitty" Smith Grounding Sheet metal screws, solder 250.8

24 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel.

25 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 250.122, 250.122(F) 215.2(A)

26 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________.

27 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits System 210.5(C)

28 Copyright 2005 Ted "Smitty" Smith Equipment Use The size of the industrial control panel supply conductor shall have an ampacity not less than ________ percent of the full load current of all resistance heating loads plus 125% of the full load current rating of the highest rated motor plus the sum of the full load current ratings of all connected motors and apparatus based on their duty cycle that may be in operation at the same time.

29 Copyright 2005 Ted "Smitty" Smith Equipment Use 125% 409.20

30 Copyright 2005 Ted "Smitty" Smith Equipment Use A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________.

31 Copyright 2005 Ted "Smitty" Smith Equipment Use Thermal Protection 410.73(E)(4)

32 Copyright 2005 Ted "Smitty" Smith Grounding The earth shall not be considered as an effective ground fault current path. True or False

33 Copyright 2005 Ted "Smitty" Smith Grounding True 250.4(A)(5)

34 Copyright 2005 Ted "Smitty" Smith Overcurrent Protection Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors?

35 Copyright 2005 Ted "Smitty" Smith Overcurrent Protection NO 240.21(C)

36 Copyright 2005 Ted "Smitty" Smith Grounding All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system.

37 Copyright 2005 Ted "Smitty" Smith Grounding Present 250.50

38 Copyright 2005 Ted "Smitty" Smith Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure.

39 Copyright 2005 Ted "Smitty" Smith Equipment Use identifying mark or logo 314.30(D)

40 Copyright 2005 Ted "Smitty" Smith Conductors and Cable Assemblies Type MC cable does not have to be supported if it is not more than 2 feet long and it is being used to provide flexibility to a termination. True or False

41 Copyright 2005 Ted "Smitty" Smith Conductors and Cable Assemblies True 320.30(D)

42 Copyright 2005 Ted "Smitty" Smith Equipment Use Wiring installed in aircraft hangars in unclassified locations that are adjacent to areas in which flammable liquids or vapors are not likely to be released, such as stock rooms or electrical control rooms, which are adequately ventilated and are effectively cut off from the hangar itself by walls or partitions, shall be permitted to be of any suitable type wiring method recognized by chapter 3 of the NEC. True or False

43 Copyright 2005 Ted "Smitty" Smith Equipment Use True Exception to 513.7

44 Copyright 2005 Ted "Smitty" Smith Equipment Use A 1/2" knockout will be made in a fluorescent light fixture that will be mounted over a junction box. The light fixture will be mounted with toggle bolts. A 1/2" chase nipple will be installed so that the conductors from the box can be brought into the fixture for make up. Is this is legal installation according to the NEC?

45 Copyright 2005 Ted "Smitty" Smith Equipment Use No 410.14(A)

46 Copyright 2005 Ted "Smitty" Smith Equipment Use Is thermal protection required for the ballast of a fluorescent exit light?

47 Copyright 2005 Ted "Smitty" Smith Equipment Use No 410.73(E)(3)

48 Copyright 2005 Ted "Smitty" Smith Equipment Use The 480 volt auxiliary equipment of an electric discharge lamp is permanently installed in a luminaire and the luminaire is mounted on a pole for the illumination of a highway. What is the minimum height above the ground the auxiliary equipment must be mounted?

49 Copyright 2005 Ted "Smitty" Smith Equipment Use 22 ft 210.6(D)(1)(a)

50 Copyright 2005 Ted "Smitty" Smith Equipment Use Is the terminal of an electric discharge lamp rated in excess of 1000V considered to be a live part according to the NEC?

51 Copyright 2005 Ted "Smitty" Smith Equipment Use Yes 410.80 (C)

52 Copyright 2005 Ted "Smitty" Smith Grounding Is an equipment grounding conductor required to be installed in listed metal flexible conduit that is 2 feet in length and is used only to provide flexible connection to a motor?

53 Copyright 2005 Ted "Smitty" Smith Grounding Yes 250.118(5)(d)

54 Copyright 2005 Ted "Smitty" Smith Grounding Exposed, non-current carrying, metal parts of motion picture projection equipment that is fastened in place shall be grounded regardless of voltage. True or False

55 Copyright 2005 Ted "Smitty" Smith Grounding True 250.112 (H

56 Copyright 2005 Ted "Smitty" Smith Grounding Exposed, non-current carrying, metal parts of equipment that is connected by cord and plug, regardless of voltage, that is installed in non-hazardous locations shall be grounded. True or False

57 Copyright 2005 Ted "Smitty" Smith Grounding False 250.114 (1) and (2)

58 Copyright 2005 Ted "Smitty" Smith Grounding The connection of a grounding electrode conductor or bonding jumper to fire-proofed structural steel shall not be required to be accessible if it is made with an irreversible compression connection. True or False

59 Copyright 2005 Ted "Smitty" Smith Grounding True 250.68 (A) Exep. 2

60 Copyright 2005 Ted "Smitty" Smith Grounding A ground rod of 8 feet in length must be installed so that the connection point of the grounding electrode conductor remains accessible and above the ground. True or False

61 Copyright 2005 Ted "Smitty" Smith Grounding False 250.53 (G) and 250.68 (A) Exp. 1

62 Copyright 2005 Ted "Smitty" Smith Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure.

63 Copyright 2005 Ted "Smitty" Smith Equipment Use identifying mark or logo 314.30(D)

64 Copyright 2005 Ted "Smitty" Smith Grounding The ground fault current path of the equipment grounding system is intended to return fault current back to the earth. True or False

65 Copyright 2005 Ted "Smitty" Smith Grounding False 250.2 Back to the source

66 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Where calculations result in a fraction of an ampere that is less than __________, such fractions shall be permitted to be dropped.

67 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits.5 220.5(B)

68 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Outlets for heavy duty lamp holders shall be calculated at a minimum of _______ volt- amperes.

69 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 600 220.14(E)

70 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits A load not less than ___________ volt amperes shall be included for each 2-wire laundry branch circuit installed as required by 210.11(C)(2).

71 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 1500 220.52(B)

72 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits An alternate load calculation for determine if the existing service or feeder is of sufficient capacity to serve additional loads in an existing dwelling unit is found in __________________.

73 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 220.83

74 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits The rules for calculating the load on fixed multi-outlet assemblies are found in _______________.

75 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 220.14(H)

76 Copyright 2005 Ted "Smitty" Smith The End Each of the slides will now be repeated. They are not timed in this segment. To change a slide, click on the side with your left mouse button. Be sure to physically look up the answers in your code book to improve your look up speed and skill.

77 Copyright 2005 Ted "Smitty" Smith Raceways LFMC shall be securely fastened in place by an approved means with in _______ inches of each box, cabinet, conduit body, or other conduit termination.

78 Copyright 2005 Ted "Smitty" Smith Raceways 12” 350.30(A)

79 Copyright 2005 Ted "Smitty" Smith Equipment Any wiring behind heating or heating panel sets located in interior walls or partitions shall be considered as operating at an ambient temperature of _______________ degrees Celsius and the ampacity shall be calculated on the basis of the correction factors given Article 310.

80 Copyright 2005 Ted "Smitty" Smith Equipment 40 degrees 424.95(B)

81 Copyright 2005 Ted "Smitty" Smith Overcurrent Protection According to Article ___________________ of the 2005 NEC, nonstandard fuses are permitted.

82 Copyright 2005 Ted "Smitty" Smith Overcurrent Protection True 240.6(A)

83 Copyright 2005 Ted "Smitty" Smith Services A cable tray may serve to carry service- entrance conductors along with other conductors as long as there is a ________.

84 Copyright 2005 Ted "Smitty" Smith Services Barrier 230.44Ex

85 Copyright 2005 Ted "Smitty" Smith Services True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service.

86 Copyright 2005 Ted "Smitty" Smith Services True 230.71(A)

87 Copyright 2005 Ted "Smitty" Smith Services The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet.

88 Copyright 2005 Ted "Smitty" Smith Services 2 feet 230.54(C) Ex

89 Copyright 2005 Ted "Smitty" Smith Grounding For multiple separately derived systems the common grounding electrode conductor shall not be smaller than __________________.

90 Copyright 2005 Ted "Smitty" Smith Grounding 3/0 CU or 250Kcm AL 250.30(A)(4)(a)

91 Copyright 2005 Ted "Smitty" Smith Raceways The minimum burial depth for a nonmetallic raceway with no vehicular traffic shall be __________________ inches.

92 Copyright 2005 Ted "Smitty" Smith Raceways 4" Table 300.5 Col. 3

93 Copyright 2005 Ted "Smitty" Smith Calculations A conductor passing through a junction box with a loop length of ______________ shall be counted twice for box fill calculations.

94 Copyright 2005 Ted "Smitty" Smith Calculations Twice the minimum length required by Article 300.14 314.16(B)(1)

95 Copyright 2005 Ted "Smitty" Smith Grounding When bonding equipment, __________shall not be used for this connection and the termination shall not depend solely on__________________.

96 Copyright 2005 Ted "Smitty" Smith Grounding Sheet metal screws, solder 250.8

97 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel.

98 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 250.122, 250.122(F) 215.2(A)

99 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________.

100 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits System 210.5(C)

101 Copyright 2005 Ted "Smitty" Smith Equipment Use The size of the industrial control panel supply conductor shall have an ampacity not less than ________ percent of the full load current of all resistance heating loads plus 125% of the full load current rating of the highest rated motor plus the sum of the full load current ratings of all connected motors and apparatus based on their duty cycle that may be in operation at the same time.

102 Copyright 2005 Ted "Smitty" Smith Equipment Use 125% 409.20

103 Copyright 2005 Ted "Smitty" Smith Equipment Use A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________.

104 Copyright 2005 Ted "Smitty" Smith Equipment Use Thermal Protection 410.73(E)(4)

105 Copyright 2005 Ted "Smitty" Smith Grounding The earth shall not be considered as an effective ground fault current path. True or False

106 Copyright 2005 Ted "Smitty" Smith Grounding True 250.4(A)(5)

107 Copyright 2005 Ted "Smitty" Smith Overcurrent Protection Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors?

108 Copyright 2005 Ted "Smitty" Smith Overcurrent Protection NO 240.21(C)

109 Copyright 2005 Ted "Smitty" Smith Grounding All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system.

110 Copyright 2005 Ted "Smitty" Smith Grounding Present 250.50

111 Copyright 2005 Ted "Smitty" Smith Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure.

112 Copyright 2005 Ted "Smitty" Smith Equipment Use identifying mark or logo 314.30(D)

113 Copyright 2005 Ted "Smitty" Smith Conductors and Cable Assemblies Type MC cable does not have to be supported if it is not more than 2 feet long and it is being used to provide flexibility to a termination. True or False

114 Copyright 2005 Ted "Smitty" Smith Conductors and Cable Assemblies True 320.30(D)

115 Copyright 2005 Ted "Smitty" Smith Equipment Use Wiring installed in aircraft hangars in unclassified locations that are adjacent to areas in which flammable liquids or vapors are not likely to be released, such as stock rooms or electrical control rooms, which are adequately ventilated and are effectively cut off from the hangar itself by walls or partitions, shall be permitted to be of any suitable type wiring method recognized by chapter 3 of the NEC. True or False

116 Copyright 2005 Ted "Smitty" Smith Equipment Use True Exception to 513.7

117 Copyright 2005 Ted "Smitty" Smith Equipment Use A 1/2" knockout will be made in a fluorescent light fixture that will be mounted over a junction box. The light fixture will be mounted with toggle bolts. A 1/2" chase nipple will be installed so that the conductors from the box can be brought into the fixture for make up. Is this is legal installation according to the NEC?

118 Copyright 2005 Ted "Smitty" Smith Equipment Use No 410.14(A)

119 Copyright 2005 Ted "Smitty" Smith Equipment Use Is thermal protection required for the ballast of a fluorescent exit light?

120 Copyright 2005 Ted "Smitty" Smith Equipment Use No 410.73(E)(3)

121 Copyright 2005 Ted "Smitty" Smith Equipment Use The 480 volt auxiliary equipment of an electric discharge lamp is permanently installed in a luminaire and the luminaire is mounted on a pole for the illumination of a highway. What is the minimum height above the ground the auxiliary equipment must be mounted?

122 Copyright 2005 Ted "Smitty" Smith Equipment Use 22 ft 210.6(D)(1)(a)

123 Copyright 2005 Ted "Smitty" Smith Equipment Use Is the terminal of an electric discharge lamp rated in excess of 1000V considered to be a live part according to the NEC?

124 Copyright 2005 Ted "Smitty" Smith Equipment Use Yes 410.80 (C)

125 Copyright 2005 Ted "Smitty" Smith Grounding Is an equipment grounding conductor required to be installed in listed metal flexible conduit that is 2 feet in length and is used only to provide flexible connection to a motor?

126 Copyright 2005 Ted "Smitty" Smith Grounding Yes 250.118(5)(d)

127 Copyright 2005 Ted "Smitty" Smith Grounding Exposed, non-current carrying, metal parts of motion picture projection equipment that is fastened in place shall be grounded regardless of voltage. True or False

128 Copyright 2005 Ted "Smitty" Smith Grounding True 250.112 (H

129 Copyright 2005 Ted "Smitty" Smith Grounding Exposed, non-current carrying, metal parts of equipment that is connected by cord and plug, regardless of voltage, that is installed in non-hazardous locations shall be grounded. True or False

130 Copyright 2005 Ted "Smitty" Smith Grounding False 250.114 (1) and (2)

131 Copyright 2005 Ted "Smitty" Smith Grounding The connection of a grounding electrode conductor or bonding jumper to fire-proofed structural steel shall not be required to be accessible if it is made with an irreversible compression connection. True or False

132 Copyright 2005 Ted "Smitty" Smith Grounding True 250.68 (A) Exep. 2

133 Copyright 2005 Ted "Smitty" Smith Grounding A ground rod of 8 feet in length must be installed so that the connection point of the grounding electrode conductor remains accessible and above the ground. True or False

134 Copyright 2005 Ted "Smitty" Smith Grounding False 250.53 (G) and 250.68 (A) Exp. 1

135 Copyright 2005 Ted "Smitty" Smith Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure.

136 Copyright 2005 Ted "Smitty" Smith Equipment Use identifying mark or logo 314.30(D)

137 Copyright 2005 Ted "Smitty" Smith Grounding The ground fault current path of the equipment grounding system is intended to return fault current back to the earth. True or False

138 Copyright 2005 Ted "Smitty" Smith Grounding False 250.2 Back to the source

139 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Where calculations result in a fraction of an ampere that is less than __________, such fractions shall be permitted to be dropped.

140 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits.5 220.5(B)

141 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Outlets for heavy duty lamp holders shall be calculated at a minimum of _______ volt- amperes.

142 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 600 220.14(E)

143 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits A load not less than ___________ volt amperes shall be included for each 2-wire laundry branch circuit installed as required by 210.11(C)(2).

144 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 1500 220.52(B)

145 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits An alternate load calculation for determine if the existing service or feeder is of sufficient capacity to serve additional loads in an existing dwelling unit is found in __________________.

146 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 220.83

147 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits The rules for calculating the load on fixed multi-outlet assemblies are found in _______________.

148 Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits 220.14(H)

149 Copyright 2005 Ted "Smitty" Smith The End Each of the slides will now be repeated. They are not timed in this segment. To change a slide, click on the side with your left mouse button. Be sure to physically look up the answers in your code book to improve your look up speed and skill.


Download ppt "Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6."

Similar presentations


Ads by Google