Elevators & Fire Alarm Systems: Understanding Interface Requirements Presented by: Antonio Torres- North Central Regional Sales Manager.

Slides:



Advertisements
Similar presentations
Elevator System Control Devices and Applications
Advertisements

Denver Fire Alarm Test FUNDAMENTAL, POWER SUPPLIES, CIRCUITS, INSPECTIONS, TESTING and MAINTENANCE.
Denver Fire Alarm Test Preparation Speed Drill © Ted Smitty Smith 2013.
NFPA 72 and NFPA 101 Supervised Automatic Sprinkler System Overview
State Fire Marshal Question and Answer Session with the Louisiana Automatic Fire Alarm Association March 19, 1999.
LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
Fire Investigation Case Studies Canadian Fire Alarm Association (CFAA) D. GOODYEAR FIRE CONSULTING.
DEPARTMENT OF DEVELOPMENT SERVICES BUILDING DIVISION Ronald L. Lynn, Director/Building Official Gregory J. Franklin, Assistant Director Neil Burning, Manager.
Steve Williams, P.E. | Brian Olsen, P.E.
Heating Control Devices
Foundations of Real Estate Management
Ted “Smitty” Smith  I have included in the following slides some key sections from each of the codes you will primarily encounter on the test. I recommend.
This training video is designed to explain: ◦MonIdor’s Purpose ◦System Applications ◦System Features ◦Technical Specifications ◦About the Code ◦Custom.
Presented April 16, 2009 at the ACG Annual Meeting in Chicago, IL. GAYLON RICHARDSON Engineered Air Balance Co., Inc. Houston, Texas 5/7/20151.
Four Learning Objectives Understand Smoke Control Theory Understand Design Methods Know Your Role in Commissioning Tests Be Familiar with Hardware, Test.
High-Rise Hotels New Codes General Fire Safety Information Ted Erb Fire Prevention Officer Bellevue Fire Department April
Cancer Center Training 2012 Cancer Center Training 2012 “Defend in Place” Strategy for Fire Alarm Activations Cancer Center Building #7559.
State of Kuwait 3rd Intl Fire & Safety Conference & Expo 4-6 March 2014 Building Performance for Emergency Response Incident Examination and Tactical Response.
Lab Inspections State Fire Marshal’s Office. Applicable Codes 1999 BOCA Business Occupancy 1999 BOCA Fire Prevention Code 2000 NFPA 101, Life Safety Code.
Fire Marshal & Medical Emergency Training Please Sign In
(Adapted from:D.T. Hall:Practical Marine Electrical Knowledge)
ONLINE SELF-STUDY Emergency Coordinator Annual Update.
Prevent False Alarms Eugene A. Cable, P.E., M.S.F.P.E. Life Safety Consultants NEHES Honorary Member 412 Horse Heaven Road Averill Park, New York
Inspection and Testing of Fire Alarm Systems (ITFAS)
Tulane University - Office of Environmental Health & Safety (OEHS) Emergency Action Plan (EAP) – Basics For All Departmental Safety Representatives (DSRs)
Retirement Home Regulated under the Retirement Home Act, 2010.
2012 International Fire Code Adopted as the minimum fire safety standard by the State of Wyoming City of Sheridan must adopt the minimum standard to retain.
FIRE ALARM SYSTEMS AND FUNDAMENTALS
WELCOME DBI & SFFD Meet the Pros October 11, 2007.
Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National.
EGRESS AND FIRE PROTECTION
Business Owners and Managers and the Fire Code
© 2012 Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code and the.
Commissioning of Fire Protection and Life Safety Systems Presented by: Charles Kilfoil Bechtel National Waste Treatment Plant Richland WA.
Motion Sensor Policy Reform  Brief review of Motion Sensor Policy History  Key Regulator Requirements  Potential for conflict with Fire Code  Case.
© 2008 Delmar, Cengage Learning Property Security, Emergency Response, and Fire Protection Systems Chapter 13.
© 2015 American Society for Healthcare Engineering, a personal membership group of the American Hospital Association 155 N. Wacker Drive, Suite 400 | Chicago,
MINNESOTA CHAPTER AUTOMATIC FIRE ALARM ASSOCIATION Requirements of the 2003 Minnesota State Fire Code relating to Group R Occupancies September 14, 2006.
Chapter 5 ID 234 Building Codes Fire Resistant Materials and Assemblies.
Floor Wardens Safety Monitors & Guests. Overview.
Area of Refuge It’s the Law!
Maine State Fire Marshals Office1 Laws and Codes Relating to Existing Apartment occupancies in the State of Maine Mark Stevens CFI-II, CFPS, CFPE Inspections.
1 © 2015 Eaton. All Rights Reserved.. Suggestion on How to Use Industry Trainers are encouraged to use this material in their sessions Download the presentation.
Southeast Financial Center
Jennie Sealy Hospital Patient Care Operations Orientation Click to Continue.
KEK, 04/28/061 Safety Plan Assumptions Break out of fire in the Beam Tunnel is negligible Cables in the Service Tunnel is main fire load They are combustible.
Incorporating Elevators and Escalators into Emergency Evacuation Models Richard W. Bukowski, P.E., FSFPE Senior Consultant Rolf Jensen and Associates Baltimore,
Building Construction
Fire Alarm Verification CAN/ULC-S561-03
Elevator Fire Service Mode Basic Operations Prepared by: Lt. Rob Fisher – L72C.
Southeast Financial Center
FIRE LIFT –DESIGN REQUIREMENTS in reference with NBC-2005
Family Law Center 1115 Congress
Proposed Changes to the 2009 International Building & Fire Codes
NICET Fire Alarm Tech Level 1 Practice Test
What Library Staff Should Know About Fire Safety
Fire Alarm Systems for Emergency Operations of Elevators
Wilson Hall Fire Protection Features
ARCHITECTURAL SAFETY FEATURES –Exit Separations –Continuation of Exit Stairs from lower to upper floors –Discharge from Exits FIRE PROTECTION FEATURES.
Design of Evacuation System for High-Rise Building Danqing Yu
Juvenile Justice Center 1200 Congress
Personal Protective Equipment
Emergency Electrical Power Supply for Buildings
February 2019.
Fire Alarm Tech Practice Test # 16 NICET
Area of Refuge It’s the Law!
Criminal Justice Center 1201 Franklin
Fire Alarm Practice Drill # 11 Denver Fire Department Journeyman Installer License Test © Ted Smith 2017.
FIRE ALARM DRILL 26 © Ted Smith 2017.
Denver Fire Depart. License Fire Alarm Practice Test # 12
Presentation transcript:

Elevators & Fire Alarm Systems: Understanding Interface Requirements Presented by: Antonio Torres- North Central Regional Sales Manager

Learning Objectives At the end of this program, participants will be able to: Improve installation coordination by identifying which elevators are subject to recall operations utilizing ASME 17.1 and 17.3 Improve installation coordination by identifying which elevators are subject to recall operations utilizing ASME 17.1 and 17.3 Eliminate job site ambiguities by incorporating code compliant sprinkler and fire alarm designs per NFPA 13, 72 and ASME 17.1(3) Eliminate job site ambiguities by incorporating code compliant sprinkler and fire alarm designs per NFPA 13, 72 and ASME 17.1(3)

Learning Objectives (cont.) At the end of this program, participants will be able to: Ensure proper design by correctly locating building systems control and annunciation equipment using ASME 17.1(3), NFPA 72 and municipal codes Understand recall sequence requirements and specify accordingly per ASME 17.1(3), NFPA 72 and municipal codes

Let’s get started!

1. When it’s required 2. How it’s initiated 3. Installation requirements Recall Codes & Standards

Elevator Recall Definition  The override of an automatic elevator’s operation by a building's fire safety system upon activation of a specific set of initiation devices.

Purpose of Elevator Recall  Safety of the public Prevents travel to fire floor Prevents occupants from getting trapped in car Controlled stoppage of cabs  Firefighters’ use Cars available upon arrival Cars available upon arrival Can be key initiated if not activated Can be key initiated if not activated

When is recall required? New Installations:  The original requirement was in the 1973 supplement to ASME A  Required recall when car traveled 25 feet above or below designated level

When is recall required? New Installations:  The 1992 supplement to A revised the recall requirements  The 25 foot requirement allowance was eliminated  All automatic elevators must now recall regardless of travel distance

When is recall required? Existing Installations:  If capability is not present, no recall required unless:  Equipment is substantially altered in some other fashion  Equipment fails  Equipment is deemed unsafe by the municipality

Systems that initiate recall sequence  Required building fire alarm system  Used for recalling the elevators  Has fire alarm notification duties  Co-located with the elevator control and status panel

Systems that initiate recall sequence  Local System  If no alarm system exists, a system with the sole purpose of recalling the elevators may be installed Marked "Elevator Recall Control and Supervisory Panel." Marked "Elevator Recall Control and Supervisory Panel." No occupant evacuation notification No occupant evacuation notification Not monitored by central station Not monitored by central station

Installation standards  ANSI/ASME A17.1, A17.3 Safety Code for Elevators and Escalators  NFPA 101, 72, 13, 70  Local or state adopted rules May not be part of your building code Overseen by an official Elevator Inspection Department

Installation standards  Electrical  Elevator shaft may be used for raceway if the circuitry serves elevator purposes only Elevator lobby smoke detectors Elevator lobby smoke detectors Top and bottom of hoistway detectors Top and bottom of hoistway detectors  Smoke detectors not allowed in unsprinkled hoistway unless opening a hoistway exhaust vent

Installation standards  Sprinkler  Chicago does not allow sprinklers in elevator machine rooms for required systems  Sprinklers in machine rooms & hoistway require a separate, system monitored shutoff valve and waterflow switch  Sprinkler heads in hoistway must be fed from the level it’s mounted on. Sprinkler risers are not allowed in the hoistway!

1. Terminology 2. How it’s initiated 3. Installation requirements Fireman’s Emergency Operations

1. Phase I (Recall) a.Primary Level b.Alternate Level 2. Phase II (Fireman’s Operation) 3. Fireman’s Hat 4. Shunt

Elevator Recall Floor Designations 1. Designated Level (Primary)  Main floor of direct egress  Egress must be at exterior grade 2. Alternate Level  Building egress available, not usually direct  Generally through exterior egress stairwells  Loading docks, parking garages

Elevator Recall Floor Designations  Designated Level (Primary) contains the following equipment: Firefighter’s Command Center (FCC) –Fire panel status and control –Emergency voice communication equipment –May contain graphic annunciation

Elevator Recall Floor Designations  Designated Level (Primary) contains: Elevator Annunciator Panel (EAP) –Shows car locations –May have recall key switches –AKA Elevator Control Panel (ECP)

 Designated Level (Primary) contains: Aux controls –Fans HOA switches May show fan status May be located in FCC –Stairwell doors Usually located in FCC (always in Chicago) –Dampers Elevator Recall Floor Designations

1. Phase I  Also referred to as Elevator Recall  Car reports to appropriate level Primary Recall Primary Recall  Elevator lobby smoke detectors from any level above designated primary level  Detectors from pit if alternate level is below primary Fireman’s Emergency Operations

Primary Recall (cont.)Primary Recall (cont.)  Buzzer sounds continuously, fireman’s hat illuminates  Cab reports to primary floor  Doors automatically open, remain open Fireman’s Emergency Operations

1. Phase One (cont.)  Accomplished with two programmable relays  Can be activated manually via Firefighter’s recall switch at ECP or primary lobby  Lobby detector can be a supervisory type device if not part of public area coverage Fireman’s Emergency Operations

1. Phase One (cont.)  Municipal codes may require two cross zoned smoke detectors per elevator lobby Cross zoning not required per NFPA 72 nor ASME 17.1(3)  Waterflow may be used in Chicago if entire building is sprinkled  Only municipality may allow other devices to activate recall Fireman’s Emergency Operations

1. Phase I (cont.)  Alternate Recall Detectors from primary level elevator lobby Detectors from primary level elevator lobby Detectors from pit if alternate level is above primary level Detectors from pit if alternate level is above primary level Buzzer sounds continuously, fireman’s hat illuminates Buzzer sounds continuously, fireman’s hat illuminates Cab reports to AHJ approved alternate floor of egress Cab reports to AHJ approved alternate floor of egress Doors open, remain open Doors open, remain open Fireman’s Emergency Operations

Lobby Detector Location Locate smoke detector(s) within 21 feet of centerline of each elevator door of the bank under control of the detector

2. Phase II  Also referred to as Firefighter’s Service  Allows firefighters to use cars after Phase I has been activated  Cars are hand operated by firefighters  Key activated from inside the car  Employs “Dead Man Drop” door operation Fireman’s Emergency Operations

3. Fireman’s Hat  Detectors in machine room and/or hoistway activate sequence Smoke detectors not allowed in hoistways that are not sprinkled unless opening a hoistway exhaust vent Heat detectors may be used in hostile environments Fireman’s Emergency Operations

3. Fireman’s Hat  Warns firefighters that loss of elevator may be imminent  Sequence activates the flashing fireman’s hat in the car(s)  Accomplished with programmable relay Fireman’s Emergency Operations

4. Shunt Trip  Why do we need it? –Controlled shutdown before sprinklers –Water on brakes may cause: Brake failure Elevator car to stop between floors and leave the hoistway exposed –Door operation circuitry on top of cab could short circuit when wet, allowing cab to travel up and down with open doors Fireman’s Emergency Operations

4. Shunt Trip (cont.)  Sequence activates shutdown of elevator power  Heat detectors in machine room and/or hoistway activate sequence Dedicated, non-delayed waterflow may be used  Must be implemented if sprinklers are in machine room and/or hoistway  Power source of shunt trip activation must be monitored for availability by fire alarm system  Accomplished by programmable relay Fireman’s Emergency Operations

4. Shunt Trip (cont.)  Hoistway Sprinklers A. Head not required in pit if: Hoistway is an enclosed, non- combustible shaft No combustible hydralic fluids B.Head not required at top of shaft if: Hoistway is an enclosed, non- combustible (or limited combustible) shaft Cab enclosure materials meet ASME 17.1 Fireman’s Emergency Operations

4.Shunt Trip (cont.)  Rate-of-rise heat detector activates shunt trip Must be located within two feet of each sprinkler head Temperature rating below and sensitivity rating above that of the sprinkler –Sprinkler head is usually 165°, standard response –Heat detector is usually 135°, but can be adjusted –Sensitivity is Response Time Index (RTI) of both sprinkler head and heat detector If unknown, a fixed temperature heat detector used Fireman’s Emergency Operations

Typical Elevator Shunt Trip Wiring

A. Fireman’s Emergency Operations B. Fire alarm equipment needed C. Takeaways Elevator Emergency Operations Review

Review of Elevator Firefighter’s Emergency Operations 1. Phase I  Primary or alternate level recall  Remains at recall level until  Bypassed with key  Phase II activated with key  Fire panel reset 2. Phase II  Firefighter operates car via special key  Car remains on floor of travel until sequence repeated

Review of Elevator Firefighter’s Emergency Operations (cont.) 3. Firefighter’s Hat  Warns of possible fire in machine room and/or hoistway  Loss of car power may be imminent 4. Elevator Shutdown  Shunt trip  Newer equipment brings car to nearest floor to let occupants out before shunting power

Fire Alarm Interface Requirements 1. Phase I  Smoke detector(s) in each elevator lobby  Two addressable relays in elevator machine room (primary and alternate recall) 2. Phase II  None 3. Firefighter’s Hat  Smoke detector(s) in elevator machine room  Smoke detector in pit and top of shaft (if sprinkled)  Addressable relay in elevator machine room

Fire Alarm Interface Requirements 4. Elevator Shunt Trip (only if sprinkled)  Heat detector within 24” of each sprinkler head Elevator machine room Elevator machine room Pit Pit Top of shaft Top of shaft  Addressable relay in elevator machine room  High voltage relay powered by shunt power Some newer shunt trip breakers contain a relay Some newer shunt trip breakers contain a relay  Addressable module to monitor shunt power relay

1. All automatic elevators must recall. 2. All sprinkled elevators must shunt. 3. Check with municipality for any additional recall criteria. 4. Ensure coordination between fire alarm and elevator contractors. 5. Ensure the correct sequences are demonstrated before final elevator and occupancy inspections. Final Takeaways

Thanks for your participation. Questions? Antonio Torres