Denver Fire Alarm Test Preparation Speed Drill © Ted Smitty Smith 2013.

Similar presentations


Presentation on theme: "Denver Fire Alarm Test Preparation Speed Drill © Ted Smitty Smith 2013."— Presentation transcript:

1

2 Denver Fire Alarm Test Preparation Speed Drill © Ted Smitty Smith 2013

3 Instructions This drill is designed to help you practice finding things in the National Fire Alarm and Signaling Code 2010 version. In order to receive the maximum benefit put the power point presention into presentation mode by clicking on the icon of projector screen in the lower right hand corner. When you are ready to begin, click on the slide and the timed drill will begin. Each question will remain in the screen for 2 minutes and then transition to the next question. Do not worry if you dont find the answer, just keep trying your best until the timed portion is complete. When the timed potion is complete a STOP sign will appear. Click on the slide again and the questions will be presented again without the timer and the answers will also be on the slides along with the code reference. The purpose of the drills is to help you get to the point that you can find the correct answer to our question in under 2 minutes. CLICK ON THE SLIDE TO CONTINUE

4 1.Which of the following statements are true concerning an electrical circuit that is the primary power supply for a fire alarm system? a)The location of the branch circuit disconnect must be permanently identified at the disconnecting location b)The disconnecting means shall be identified as Fire Alarm Control Panel Power Source c)The disconnecting means shall have a red marking or be clearly labeled using black letters on a white background d)The disconnecting means shall be accessible to any qualified personnel.

5 2. In the absence of specific performance based design criteria, smooth ceiling smoke detector spacing shall be a nominal ________ feet. a)10 b)15 c)20 d)30

6 3. The lead acid batteries in a central station facility shall be charger tested at initial installation and then _______________. a)Weekly b)Monthly c)Quarterly d)Annually

7 4. An average ambient sound level greater than ____________dBA shall require the use of a visible notification appliance. a. 90 b. 105 c. 115 d. 120

8 5. The secondary power supply of a fire alarm system shall have sufficient capacity to operate the system under quiescent load for a minimum of 24 hours and at the end of that period, shall be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location of an emergency for ________ minutes. A.30 B.10 C.5 D.1

9 6. All fire alarm system shall test free of ______________. a. failures b. grounds c. surges d. faults

10 7. Which of the following areas are not required to have an approved single or multiple station smoke alarm installed in single family dwellings a. In all sleeping rooms and guest rooms b. On the floor loft that is only a recreation room c. In the basement d. In the garage

11 8. Which of the following statements are not true concerning monitoring for integrity? A. It is not required for central station circuits serving notification appliances within a central station B. It is not required for a trouble circuit C. It is not required for notification appliances D. It is not required for shorts between conductors

12 9. A fire alarm systems smoke detectors must be tested for functionality at the initial installation and then again ____________? A. Monthly B. Quarterly C. Annually D. Not required after initial test

13 10. A _______________ is any circuit, conductor, optic fiber, radio carrier, or other means connecting two or more locations. A. Circuit B. Path or Pathway C. Raceway D. None of the above

14 11. Activation of the initiating device for a sprinkler waterflow shall occur within ________ seconds of waterflow at the alarm initiating device when flow occurs that is equal to or greater than that from a single sprinkler of the smallest orifice size installed in the system. A. 10 B. 30 C. 60 D. 90

15 12. Actuation of alarm notification appliances for emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ______ seconds after the activation of an initiating device. A. 10 B. 30 C. 60 D. 90

16 13. Which of the following is not a performance requirement of a Class A pathway? A. It includes a redundant path B. Operational capability continues past a single open C. Conditions that affect the intended operation of the path are annuciated D. A loss of end to end communication is annuciated

17 14. For sloping ceilings with beams running parallel up slope, spot type detectors shall be located _____________________________? A. at the bottom of the beams B. on the ceiling within beam pockets C. spaced not less than 25% of the rating D. with detector at the top of slope only

18 15. The number of waterflow alarm initiating devices permitted to be connected to a single initiating device circuit shall not exceed ______. A. 1 B. 3 C. 5 D. 7

19

20 A. 10.5.5.2 1.Which of the following statements are true concerning an electrical circuit that is the primary power supply for a fire alarm system? a)The location of the branch circuit disconnect must be permanently identified at the disconnecting location b)The disconnecting means shall be identified as Fire Alarm Control Panel Power Source c)The disconnecting means shall have a red marking or be clearly labeled using black letters on a white background d)The disconnecting means shall be accessible to any qualified personnel.

21 C 10.5.6.3 2. In the absence of specific performance based design criteria, smooth ceiling smoke detector spacing shall be a nominal ________ feet. a)10 b)15 c)20 d)30

22 D 17.7.3.2.3.1 3. The lead acid batteries in a central station facility shall be charger tested at initial installation and then _______________. a)Weekly b)Monthly c)Quarterly d)Annually

23 B 18.4.1.1 4. An average ambient sound level greater than ____________dBA shall require the use of a visible notification appliance. a. 90 b. 105 c. 115 d. 120

24 D. T14.4.5 5. The secondary power supply of a fire alarm system shall have sufficient capacity to operate the system under quiescent load for a minimum of 24 hours and at the end of that period, shall be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location of an emergency for ________ minutes. A.30 B.10 C.5 D.1

25 B 12.2.4.4 6. All fire alarm system shall test free of ______________. a. failures b. grounds c. surges d. faults

26 D 29.5.1 7. Which of the following areas are not required to have an approved single or multiple station smoke alarm installed in single family dwellings a. In all sleeping rooms and guest rooms b. On the floor loft that is only a recreation room c. In the basement d. In the garage

27 C 10.17.1.1 8. Which of the following statements are not true concerning monitoring for integrity? A. It is not required for central station circuits serving notification appliances within a central station B. It is not required for a trouble circuit C. It is not required for notification appliances D. It is not required for shorts between conductors

28 C T14.4.5 9. A fire alarm systems smoke detectors must be tested for functionality at the initial installation and then again ____________? A. Monthly B. Quarterly C. Annually D. Not required after initial test

29 B 3.3.175 10. A _______________ is any circuit, conductor, optic fiber, radio carrier, or other means connecting two or more locations. A. Circuit B. Path or Pathway C. Raceway D. None of the above

30 D 17.12.3 11. Activation of the initiating device for a sprinkler waterflow shall occur within ________ seconds of waterflow at the alarm initiating device when flow occurs that is equal to or greater than that from a single sprinkler of the smallest orifice size installed in the system. A. 10 B. 30 C. 60 D. 90

31 A 23.8.1.1 12. Actuation of alarm notification appliances for emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ______ seconds after the activation of an initiating device. A. 10 B. 30 C. 60 D. 90

32 D 12.3.1 13. Which of the following is not a performance requirement of a Class A pathway? A. It includes a redundant path B. Operational capability continues past a single open C. Conditions that affect the intended operation of the path are annuciated D. A loss of end to end communication is annuciated

33 B. 17.7.3.2.4.3 14. For sloping ceilings with beams running parallel up slope, spot type detectors shall be located _____________________________? A. at the bottom of the beams B. on the ceiling within beam pockets C. spaced not less than 25% of the rating D. with detector at the top of slope only

34 C 23.8.5.5.2 15. The number of waterflow alarm initiating devices permitted to be connected to a single initiating device circuit shall not exceed ______. A. 1 B. 3 C. 5 D. 7