Master Examination Practice Drill # Ted “Smitty” Smith.
Advertisements

EET Survey of Electronics
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE.
Master Examination Practice Drill # (16) O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles.
2014 CHANGES TWO MINUTE DRILL COPYRIGHT TED “SMITTY” SMITH ©2014.
By Carlin Bright. Electricity The flow of electrons in a conductor.
©Ted “Smitty” Smith This speed drill focuses on calculations that will be required for the journeyman and masters examination. The question slide.
Copyright 2005 Ted "Smitty" Smith Two Minute Drill Number Three Improving your skill in code Look Up Increasing Speed Drill.
Two Minute Drill Number 32- Journeyman Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 25- Residential Improving your skill in code Look Up Increasing Speed Drill.
©Ted “Smitty” Smith  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead.
Two Minute Drill #8 Copyright 2005 Ted "Smitty" Smith Practice Code Look Up.
Two Minute Drill Number 26- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.
Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage.
Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith.
Two Minute Drill Number 27- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Calculation Speed Drill # NEC
Electrical Safety in Construction. Objectives In this course, we will discuss the following: Common electrical hazards Standards relating to those hazards.
Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1.
Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6.
Copyright 2008 Ted "Smitty" Smith.  Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. 
©Ted “Smitty” Smith This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.
Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 31- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 22- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 24- Residential.
2008 Code Drills (C) Copyright 2008 Ted "Smitty" Smith 1 Smitty’s Speed Drills.
Ag. Mechanics for Beginning Teachers
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 21- Residential Improving your skill in code Look Up Increasing Speed Drill.
2014 NEC C ODE C HANGES C LASS P ART II Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc.
P RACTICE C ODE L OOK U P Two Minute Drill #7 Copyright 2005 Ted "Smitty" Smith.
Smitty’s Two Minute Drill Grounding
Smitty’s Two Minute Drill Grounding
Planning The Electrical System
Advanced Calculations Drill 1 for the 2011 NEC
License Examination Practice Drill
Chapter 12 Branch Circuits and Feeders. Chapter 12 Branch Circuits and Feeders.
2011 Changes Two Minute Drill
Smitty’s Two Minute Drills
Smitty’s Two Minute Drill Overcurrent Protection
Smitty’s Two Minute Drill Mixed Content -05
Smitty’s Two Minute Drill #9: Special Occupancies
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
Smitty’s Super Speed Drill for Memorization No. 2
Conductors and Cables 2017 NEC
Ampacity Calculations and Overcurrent Protection 1
Calculation Speed Drill #1
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Calculations: Transformers and Service Conductor Calculations
Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
Two Minute Drill: Raceways and Boxes 2017
Smitty’s Two Minute Drill Photovoltaic Systems
2014 Changes Two Minute Drill
EET 323 – Electrical System Design Lecture 9: Grounding
Two Minute Drill Number 29- Conductors and Raceways
EET 323 – Electrical System Design Lecture 11: Panel-boards and Switch-boards Instructor: Radian Belu, PhD.
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Smitty’s Two Minute Drill Grounding and Bonding
2008 Code Drills Health Care Facilities
Two Minute Drill – Residential 3
Smitty’s Two Minute Drill Services, Feeders, and Branch Circuits 1
Two Minute Drill – Residential 3
Smitty’s Two Minute Drill Varied Number 7
Smitty’s Two Minute Drill The BIG 5 Drill 1
Two Minute Drill – Residential 2
Calculation Speed Drill Varied-1
Varied Calculations Drill 2
Presentation transcript:

Practice Code Look Up Two Minute Drill #7 Copyright 2005 Ted "Smitty" Smith Two Minute Drill #7

Directions Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:30 minutes or less. The correct answer will transition in 10 seconds. Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill Good luck Copyright 2005 Ted "Smitty" Smith

Further More Remember do not worry about writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then. This presentation is set up with varying time limits. Click on the slide to proceed. Copyright 2005 Ted "Smitty" Smith

Grounding Nonconductive coatings such as paint shall be removed from threads and other contact areas on equipment to be grounded. True False Copyright 2005 Ted "Smitty" Smith

Grounding True   250.12 Copyright 2005 Ted "Smitty" Smith

Equipment An appliance is rated 1200VA at 208 volts, three phase. It is a cord and plug connected. The cord plug and receptacle are not accessible from the location of the appliance. The disconnecting means for the appliance is the circuit breaker located in the panel. The panel is installed 65 feet from the appliance and can be seen when standing at the appliance. The circuit breaker can be locked in the open temporarily by use of a breaker lock out supplied by the manufacturer. Is this an acceptable installation? Copyright 2005 Ted "Smitty" Smith

Equipment No   422.33 requires the cord and plug to be accessible. If not accessible it refers you back to 422.31(B). 422.31(B) allows the breaker to be the disconnecting means if the breaker is within sight from the appliance or has a permanent means of locking the breaker open that remains in place regardless of whether the lock is in use or not. Article 100 defines “within sight from” as being within 50 feet of the appliance. This is located 65 feet away so it is not within sight from. The breaker can be locked out but only temporarily. This installation would require a separate disconnecting means. Copyright 2005 Ted "Smitty" Smith

Grounding All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(7) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system. Copyright 2005 Ted "Smitty" Smith

Grounding Present     250.50 Copyright 2005 Ted "Smitty" Smith

Equipment In a health care system, sump pumps required to operate for the safety of major apparatus, shall be installed and connected to the equipment system and the alternate power source such that the they will be automatically restored to operation at _____________ time lag intervals following the energizing of the emergency system. Copyright 2005 Ted "Smitty" Smith

Equipment appropriate 517.34 (A)(2) Copyright 2005 Ted "Smitty" Smith

Special Occupancies A site isolating device shall be installed at the ______________________ where two or more agricultural buildings or structures are supplied from the distribution point. Copyright 2005 Ted "Smitty" Smith

Special Occupancies Distribution point 547.9(A)(1) Copyright 2005 Ted "Smitty" Smith

Equipment Use Portable electric luminaries shall not be used in a spray area during spray operations unless they are required for operations in spaces not readily illuminated by fixed lighting within the spraying area and they are of the type identified for Class I, Division 1 or Class 1, Zone 1 locations where readily ignitable residues may be present. True or False Copyright 2005 Ted "Smitty" Smith

Equipment Use True 516.4(D) Exception 1 Copyright 2005 Ted "Smitty" Smith

Special Occupancies A pit that is 10 feet in diameter and 18” in depth, without mechanical ventilation, located within a bulk fuel storage plant and within a class 1, division 2 area is considered to be a class 1, division __________ area. Copyright 2005 Ted "Smitty" Smith

Services Division 1 Table 515.3 Page 416 Copyright 2005 Ted "Smitty" Smith

Special Occupancies In a recreational vehicle, receptacles shall be located so that no point along the floor line is more than 6 feet, measured horizontally, from an outlet in that space, this includes bathrooms and hall areas. True False Copyright 2005 Ted "Smitty" Smith

Special Occupancies False 551.41(A) Exception 1 Copyright 2005 Ted "Smitty" Smith

Equipment The 480 volt auxiliary equipment of an electric discharge lamp is permanently installed in a luminaire and the luminaire is mounted on a pole for the illumination of a highway. What is the minimum height above the ground the auxiliary equipment must be mounted? Copyright 2005 Ted "Smitty" Smith

Equipment Use 22 ft   210.6(D)(1)(a) Copyright 2005 Ted "Smitty" Smith

Raceways ENT must be secured in place every ______. A. 12 inches B. 18 inches C. 24 inches D. 36 inches Copyright 2005 Ted "Smitty" Smith

Raceways D. 36 inches 362.30(A) Copyright 2005 Ted "Smitty" Smith

Raceways High Density Polyethlyene conduit may be used above ground if enclosed in not less than ________ of concrete. Copyright 2005 Ted "Smitty" Smith

Raceways 2” 353.10(5) Copyright 2005 Ted "Smitty" Smith

Calculations A conductor passing through a junction box with a loop length of ______________ shall be counted twice for box fill calculations.  Copyright 2005 Ted "Smitty" Smith

Calculations Twice the minimum length required by Article 300.14 Copyright 2005 Ted "Smitty" Smith

Overcurrent protection Equipment intended to break current at other than fault levels shall have an interrupting rating of the system voltage sufficient for the current that must be interrupted. True or False Copyright 2005 Ted "Smitty" Smith

Overcurrent Protection True 110.9 Copyright 2005 Ted "Smitty" Smith

Services Where exposed to the weather, raceways enclosing service-entrance conductors shall be suitable for use _______________ and arranged to drain. Where embedded in masonry, raceways shall be arranged to drain. Copyright 2005 Ted "Smitty" Smith

Services In wet locations 250.53 Copyright 2005 Ted "Smitty" Smith

Equipment Use For electric discharge lighting systems a disconnecting means shall be located so as to be accessible to _________________ before servicing or maintaining the ballast. The disconnecting means shall be internal to the luminaire or if external, shall be a single device, and shall be attached to the luminaire or located within sight of the luminaire. Copyright 2005 Ted "Smitty" Smith

Equipment Use Qualified persons 410.130(G)(3) Copyright 2005 Ted "Smitty" Smith

Grounding The earth shall not be considered as an effective ground fault current path. True or False Copyright 2005 Ted "Smitty" Smith

Grounding True                               250.4(A)(5) Copyright 2005 Ted "Smitty" Smith

Overcurrent Protection Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors if the overcurrent protection for the secondary conductors is provided by the primary conductors overcurrent protection? Copyright 2005 Ted "Smitty" Smith

Overcurrent Protection NO   240.21(C) Copyright 2005 Ted "Smitty" Smith

Feeders and Branch Circuits Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________. Copyright 2005 Ted "Smitty" Smith

Feeders and Branch Circuits Phase or line and system                          210.5(C) Copyright 2005 Ted "Smitty" Smith

Equipment Use The size of the industrial control panel supply conductor shall have an ampacity not less than ________ percent of the full load current of all resistance heating loads plus 125% of the full load current rating of the highest rated motor plus the sum of the full load current ratings of all connected motors and apparatus based on their duty cycle that may be in operation at the same time. Copyright 2005 Ted "Smitty" Smith

Equipment Use 125%                             409.20 Copyright 2005 Ted "Smitty" Smith

Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure. Copyright 2005 Ted "Smitty" Smith

Equipment Use identifying mark or logo 314.30(D) Copyright 2005 Ted "Smitty" Smith

Conductors and Cable Assemblies Type MC cable does not have to be supported if it is not more than 2 feet long and it is being used to provide flexibility to a termination.  True or False Copyright 2005 Ted "Smitty" Smith

Conductors and Cable Assemblies True    320.30(D) Copyright 2005 Ted "Smitty" Smith

Equipment Use A 1/2" knockout will be made in a fluorescent light fixture that will be mounted over a junction box. The light fixture will be mounted with toggle bolts. A 1/2" chase nipple will be installed so that the conductors from the box can be brought into the fixture for make up. Is this is legal installation according to the NEC? Copyright 2005 Ted "Smitty" Smith

Equipment Use No    410.24(B) Copyright 2005 Ted "Smitty" Smith

Equipment Use Is thermal protection required for the ballast of a fluorescent exit light? Copyright 2005 Ted "Smitty" Smith

Equipment Use No    410.130(E)(3) Copyright 2005 Ted "Smitty" Smith

Equipment Use Is the terminal of an electric discharge lamp rated in excess of 1000V considered to be a live part according to the NEC? Copyright 2005 Ted "Smitty" Smith

Equipment Use Yes   410.140 (C) Copyright 2005 Ted "Smitty" Smith

Grounding Is an equipment grounding conductor required to be installed in listed metal flexible conduit that is 2 feet in length and is used only to provide flexible connection to a motor? Copyright 2005 Ted "Smitty" Smith

Grounding Yes  250.118(5)(d) Copyright 2005 Ted "Smitty" Smith

The End Each of the slides will now be repeated. They are not timed in this segment. To change a slide, click on the side with your left mouse button. Be sure to physically look up the answers in your code book to improve your look up speed and skill. Copyright 2005 Ted "Smitty" Smith

Grounding Nonconductive coatings such as paint shall be removed from threads and other contact areas on equipment to be grounded. True False Copyright 2005 Ted "Smitty" Smith

Grounding True   250.12 Copyright 2005 Ted "Smitty" Smith

Equipment An appliance is rated 1200VA at 208 volts, three phase. It is a cord and plug connected. The cord plug and receptacle are not accessible from the location of the appliance. The disconnecting means for the appliance is the circuit breaker located in the panel. The panel is installed 65 feet from the appliance and can be seen when standing at the appliance. The circuit breaker can be locked in the open temporarily by use of a breaker lock out supplied by the manufacturer. Is this an acceptable installation? Copyright 2005 Ted "Smitty" Smith

Equipment No   422.33 requires the cord and plug to be accessible. If not accessible it refers you back to 422.31(B). 422.31(B) allows the breaker to be the disconnecting means if the breaker is within sight from the appliance or has a permanent means of locking the breaker open that remains in place regardless of whether the lock is in use or not. Article 100 defines “within sight from” as being within 50 feet of the appliance. This is located 65 feet away so it is not within sight from. The breaker can be locked out but only temporarily. This installation would require a separate disconnecting means. Copyright 2005 Ted "Smitty" Smith

Grounding All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(7) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system. Copyright 2005 Ted "Smitty" Smith

Grounding Present     250.50 Copyright 2005 Ted "Smitty" Smith

Equipment In a health care system, sump pumps required to operate for the safety of major apparatus, shall be installed and connected to the equipment system and the alternate power source such that the they will be automatically restored to operation at _____________ time lag intervals following the energizing of the emergency system. Copyright 2005 Ted "Smitty" Smith

Equipment appropriate 517.34 (A)(2) Copyright 2005 Ted "Smitty" Smith

Special Occupancies A site isolating device shall be installed at the ______________________ where two or more agricultural buildings or structures are supplied from the distribution point. Copyright 2005 Ted "Smitty" Smith

Special Occupancies Distribution point 547.9(A)(1) Copyright 2005 Ted "Smitty" Smith

Equipment Use Portable electric luminaries shall not be used in a spray area during spray operations unless they are required for operations in spaces not readily illuminated by fixed lighting within the spraying area and they are of the type identified for Class I, Division 1 or Class 1, Zone 1 locations where readily ignitable residues may be present. True or False Copyright 2005 Ted "Smitty" Smith

Equipment Use True 516.4(D) Exception 1 Copyright 2005 Ted "Smitty" Smith

Special Occupancies A pit that is 10 feet in diameter and 18” in depth, without mechanical ventilation, located within a bulk fuel storage plant and within a class 1, division 2 area is considered to be a class 1, division __________ area. Copyright 2005 Ted "Smitty" Smith

Services Division 1 Table 515.3 Page 416 Copyright 2005 Ted "Smitty" Smith

Special Occupancies In a recreational vehicle, receptacles shall be located so that no point along the floor line is more than 6 feet, measured horizontally, from an outlet in that space, this includes bathrooms and hall areas. True False Copyright 2005 Ted "Smitty" Smith

Special Occupancies False 551.41(A) Exception 1 Copyright 2005 Ted "Smitty" Smith

Equipment The 480 volt auxiliary equipment of an electric discharge lamp is permanently installed in a luminaire and the luminaire is mounted on a pole for the illumination of a highway. What is the minimum height above the ground the auxiliary equipment must be mounted? Copyright 2005 Ted "Smitty" Smith

Equipment Use 22 ft   210.6(D)(1)(a) Copyright 2005 Ted "Smitty" Smith

Raceways ENT must be secured in place every ______. A. 12 inches B. 18 inches C. 24 inches D. 36 inches Copyright 2005 Ted "Smitty" Smith

Raceways D. 36 inches 362.30(A) Copyright 2005 Ted "Smitty" Smith

Raceways High Density Polyethlyene conduit may be used above ground if enclosed in not less than ________ of concrete. Copyright 2005 Ted "Smitty" Smith

Raceways 2” 353.10(5) Copyright 2005 Ted "Smitty" Smith

Calculations A conductor passing through a junction box with a loop length of ______________ shall be counted twice for box fill calculations.  Copyright 2005 Ted "Smitty" Smith

Calculations Twice the minimum length required by Article 300.14 Copyright 2005 Ted "Smitty" Smith

Overcurrent protection Equipment intended to break current at other than fault levels shall have an interrupting rating of the system voltage sufficient for the current that must be interrupted. True or False Copyright 2005 Ted "Smitty" Smith

Overcurrent Protection True 110.9 Copyright 2005 Ted "Smitty" Smith

Services Where exposed to the weather, raceways enclosing service-entrance conductors shall be suitable for use _______________ and arranged to drain. Where embedded in masonry, raceways shall be arranged to drain. Copyright 2005 Ted "Smitty" Smith

Services In wet locations 250.53 Copyright 2005 Ted "Smitty" Smith

Equipment Use For electric discharge lighting systems a disconnecting means shall be located so as to be accessible to _________________ before servicing or maintaining the ballast. The disconnecting means shall be internal to the luminaire or if external, shall be a single device, and shall be attached to the luminaire or located within sight of the luminaire. Copyright 2005 Ted "Smitty" Smith

Equipment Use Qualified persons 410.130(G)(3) Copyright 2005 Ted "Smitty" Smith

Grounding The earth shall not be considered as an effective ground fault current path. True or False Copyright 2005 Ted "Smitty" Smith

Grounding True                               250.4(A)(5) Copyright 2005 Ted "Smitty" Smith

Overcurrent Protection Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors if the overcurrent protection for the secondary conductors is provided by the primary conductors overcurrent protection? Copyright 2005 Ted "Smitty" Smith

Overcurrent Protection NO   240.21(C) Copyright 2005 Ted "Smitty" Smith

Feeders and Branch Circuits Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________. Copyright 2005 Ted "Smitty" Smith

Feeders and Branch Circuits Phase or line and system                          210.5(C) Copyright 2005 Ted "Smitty" Smith

Equipment Use The size of the industrial control panel supply conductor shall have an ampacity not less than ________ percent of the full load current of all resistance heating loads plus 125% of the full load current rating of the highest rated motor plus the sum of the full load current ratings of all connected motors and apparatus based on their duty cycle that may be in operation at the same time. Copyright 2005 Ted "Smitty" Smith

Equipment Use 125%                             409.20 Copyright 2005 Ted "Smitty" Smith

Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure. Copyright 2005 Ted "Smitty" Smith

Equipment Use identifying mark or logo 314.30(D) Copyright 2005 Ted "Smitty" Smith

Conductors and Cable Assemblies Type MC cable does not have to be supported if it is not more than 2 feet long and it is being used to provide flexibility to a termination.  True or False Copyright 2005 Ted "Smitty" Smith

Conductors and Cable Assemblies True    320.30(D) Copyright 2005 Ted "Smitty" Smith

Equipment Use A 1/2" knockout will be made in a fluorescent light fixture that will be mounted over a junction box. The light fixture will be mounted with toggle bolts. A 1/2" chase nipple will be installed so that the conductors from the box can be brought into the fixture for make up. Is this is legal installation according to the NEC? Copyright 2005 Ted "Smitty" Smith

Equipment Use No    410.24(B) Copyright 2005 Ted "Smitty" Smith

Equipment Use Is thermal protection required for the ballast of a fluorescent exit light? Copyright 2005 Ted "Smitty" Smith

Equipment Use No    410.130(E)(3) Copyright 2005 Ted "Smitty" Smith

Equipment Use Is the terminal of an electric discharge lamp rated in excess of 1000V considered to be a live part according to the NEC? Copyright 2005 Ted "Smitty" Smith

Equipment Use Yes   410.140 (C) Copyright 2005 Ted "Smitty" Smith

Grounding Is an equipment grounding conductor required to be installed in listed metal flexible conduit that is 2 feet in length and is used only to provide flexible connection to a motor? Copyright 2005 Ted "Smitty" Smith

Grounding Yes  250.118(5)(d) Copyright 2005 Ted "Smitty" Smith