Presentation is loading. Please wait.

Presentation is loading. Please wait.

2014 NEC C ODE C HANGES C LASS P ART II Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc.

Similar presentations


Presentation on theme: "2014 NEC C ODE C HANGES C LASS P ART II Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc."— Presentation transcript:

1 2014 NEC C ODE C HANGES C LASS P ART II Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc

2 Conductors of Different Systems 300.6(C) We can have conductors of different voltages in the same raceway, junction box, and enclosure under the following conditions – All of the circuits are 1000v or less – All of the conductors are rated for the highest voltage in the box.

3 Secondary Wiring to High Discharge Lighting 310.6(C) The secondary wiring for EDL 1000V or less if insulated for the secondary voltage involved, can occupy the same luminaire, sign, or outline lighting enclosure

4 Corrosive Areas 330.6(A) Any field cut ferrous metal raceways, etc need to be suitably protected from corrosion in the environment – Field cuts have to have the corrosion protection replaced A new information note clarifies that a field cut is any cut made anywhere other than at the factory

5 300.22(C) Other spaces used for Environmental Air (Plenums) Nonmetallic cable ties and other nonmetallic cable accessories used to secure and support cables shall be listed as having low smoke and heat release properties

6 300.38 Raceways in Wet Locations above Grade Where raceways are installed in wet locations above grade the interior of the raceway shall be considered a wet location.

7 Cables and Raceways on Rooftops Exposed to Direct Sunlight (T310.15(B)(3)(c) XHHN conductors are now exempted from this requirement

8 314.15 Boxes in Damp or Wet Locations We can now drill drainage holes in boxes listed for damp and wet locations as long as the hole is no larger than ¼ inch. We can also install listed drain fittings in larger holes as long as it is done according to the manufacturers instructions.

9 314.16(B) Box Fill Clamp Assemblies New addition to cover clamp assemblies with terminations listed for use with non-metallic boxes This assembly is counted as a single cable clamp

10 200.4(B) Neutral Marking If there is more than one neutral associated with different circuits in an enclosure the neutrals have to identified or grouped so that they correspond with the ungrounded circuits for which they are associated. – This can be done by wire markers, cable ties, or similar means in at least one location within the enclosure.

11 210.5(c)(1) Branch Circuit Identification They have further clarified the requirement to identify ungrounded conductors of systems with multiple voltages at all terminations, connection and splices by phase, line and system. – This clarifies the requirement in houses or structures in single phase systems – This is easily enforceable and often violated

12 210.5(c)(2) They have added an entire new section about this for DC systems – More than 50 volts – 4 AWG or larger – Identified by Polarity – Ungrounded conductor – By marking tape, tagging – At all spices, terminations and connections

13 210.5(c)(2) They have added an entire new section about this for DC systems – More than 50 volts – 6 AWG and smaller – Positive Polarity Red outer finish Red stripe continuously and durable Imprinted plus signed or the work POSITIVE or POS repeated ate intervals of no less than 24 inches – Negative Polarity Black outer finish Black stripe continuously or durable Imprinted minus sign, or word NEGATIVE OR NEG repeated at intervals no less than 24 incues

14 Applies PV Systems This requirement has been added to 215 feeders as well And it is referenced in the PV article

15 225.56 Inspection and Tests Outside Branch Circuits and Feeders over 1000V Design including settings for protective devices, switching and control circuits have to be made available to the AHJ before energization And shall be performance tested when first installed on site

16 230.28 Service Masts New strength requirement or supported by guy wires Can not be connected to the mast between the weatherhead and the end of the conduit or coupling if the coupling is located above the last point of securement to the structure Weatherheads have to be identified for use as service-entrance equipment

17 230.30 Service Laterals Must be installed in only the following – RMC – IMC – NUCC – HDPE – PVC – RTRC – IGS cable – USE – MV or MC identified for direct burial

18 Conduit Fill Calculations Based on Tables 1, 4 and 5 in Chapter 9 Note 4 to Table 1 Can only use Annex C is all the conductors are the same size and insulation Start with Table 5 and get your volume used then find the conduit on Table 4 Metric and Standard, do not convert


Download ppt "2014 NEC C ODE C HANGES C LASS P ART II Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc."

Similar presentations


Ads by Google