1 GE job title/1 GE internal information - Not for external distribution 1 GE Security EMEA NPI template – v1 1X Series (phase 1) Conventional Fire Panel

2 GE job title/2 GE internal information - Not for external distribution 2 GE Security EMEA NPI template – v1 Signaling Devices Up to 4 conventional zones with up to 32* devices per zone FACP Detection Devices *Detector line dependent 2 x Inputs 240/110 PSU The 1X-F4 System Up to 8 additional supervised or un-supervised auxiliary relay outputs Auxiliary Boards

3 GE job title/3 GE internal information - Not for external distribution 3 GE Security EMEA NPI template – v1 The 1X-F4 System We decide to offer the customer the 1X-F4 2.8 kg

4 GE job title/4 GE internal information - Not for external distribution 4 GE Security EMEA NPI template – v1 Preparation Cable Specifications System Specifications Bills of Quantities Standby Time Default System Configuration Planning the Installation

5 GE job title/5 GE internal information - Not for external distribution 5 GE Security EMEA NPI template – v1 System Specifications System specifications (power supply for 2 and 4 zone panels) Mains Supply: 110/240 VAC 50/60Hz (+10%/−15%)-< 2 A 24 VDC Supply: (±2%) -< 2 A Batteries: (SLA) - < 7.2 Ah Battery charger: 27.3 V @ 20ºC (−36mV/ºC)- < 0.5 A Auxiliary supply: - < 250 mA @ 21 - 28 VDC (24 V Nominal)

6 GE job title/6 GE internal information - Not for external distribution 6 GE Security EMEA NPI template – v1 System Specifications System specifications (power supply for 8 zone panels) Mains Supply: 110 VAC 60Hz (+10%/−15%)-< 3.15 A 240 VAC 50 Hz (+10%/−15%)-< 3.15 A 24 VDC Supply: (±2%) - < 4 A Batteries: (SLA) - < 12 Ah Battery charger: 27.3 V @ 20ºC (−36mV/ºC)- < 0.7 A Auxiliary supply: - 250 mA @ 21 to 28 VDC (24 V Nominal)

7 GE job title/7 GE internal information - Not for external distribution 7 GE Security EMEA NPI template – v1 System Specifications System specifications (others - for 2 and 4 zone panels) Zone Supply: -< 65 mA @ 18-24 VDC (22 V nominal) Zone equipment spec -< 2.6 mA Supervised Outputs: -< 250 mA @ 28 VDC Supervision Voltage--15 VDC Unsupervised Outputs: -< 2 A @ 30 VDC Auxiliary Boards: Standard Relay Board-< 2 A @ 30 VDC Supervised Relay Board- < 2.5 A @ 28 VDC

8 GE job title/8 GE internal information - Not for external distribution 8 GE Security EMEA NPI template – v1 Zone Supply: -< 65 mA @ 18-24 VDC (22 V nominal) Zone equipment-< 2.6 mA Supervised Outputs: -500 mA @ 28 VDC Supervision Voltage--15 VDC Unsupervised Outputs: -2 A @ 30 VDC Auxiliary Boards: Standard Relay Board-0.5 A Supervised Relay Board-0.7 A System Specifications System specifications (others - for 8 zone panels)

9 GE job title/9 GE internal information - Not for external distribution 9 GE Security EMEA NPI template – v1 System Specifications Environmental specifications Temperature Specifications: Storage Temperature--10 to +70°C Operating temperature--10 to +40°C Humidity: (non condensing) -10 to 95% IP Rating: -IP30

10 GE job title/10 GE internal information - Not for external distribution 10 GE Security EMEA NPI template – v1 Installing the Hardware in the Cabinet The hardware of the 1X-F4 (and 1X-F2) Back Box Battery Plate BS127N 7.5 Ah Batteries Mains Power Connector 1X-4F-MB 2010-1-RB / 2010-1-SB 2010-PS- 20 1X-C2

11 GE job title/11 GE internal information - Not for external distribution 11 GE Security EMEA NPI template – v1 Connecting the Field Equipment System installation INPUT1:unused INPUT2:to the intrusion panel Z1:to the showroom Z2:to the office area Z3:to the canteen Z 4:unused OUT1:showroom notification devices OUT2:offices notification devices OUT3:canteen notification devices OUT4:unused 24V AUX:unused FAULT:unused FIRE:unused Only required if non GE devices are used

12 GE job title/12 GE internal information - Not for external distribution 12 GE Security EMEA NPI template – v1 Optional relay board required for door control 2010-1-RBUn-supervised (4 relays COM-NO-NC) Connected behind the main PCB with a ribbon cable supplied with the relay board. Connectors are still visible and pluggable. Connecting the Field Equipment Connecting any auxiliary boards SHOWROOM OFFICES/ TOILETS CANTEEN

13 GE job title/13 GE internal information - Not for external distribution 13 GE Security EMEA NPI template – v1 SHOWROOM OFFICES/ TOILETS CANTEEN The User Interface Localisation Easy language/country variant implementation allows for the panel to be available in local language using customised language inserts Common control/indicator locations on all X series panels Main indications Main controls/indicators Sounder controls/indicators Fire routing controls/indicators Maintenance controls/indicators

14 GE job title/14 GE internal information - Not for external distribution 14 GE Security EMEA NPI template – v1 The User Interface Front panel (for everyone) SHOWROOM OFFICES/ TOILETS CANTEEN

15 GE job title/15 GE internal information - Not for external distribution 15 GE Security EMEA NPI template – v1 The 7-Segment Display 7-Segment display (for the installer and maintenance engineer) SHOWROOM OFFICES/ TOILETS CANTEEN

16 GE job title/16 GE internal information - Not for external distribution 16 GE Security EMEA NPI template – v1 The 7-Segment Display Features Mode Value Provides the possibility to eliminate DIP switches and jumpers and makes the panel ready for PC programming Provides clear English menu extensions for easy configuration options Indicates default values ad user selections on 8th- segment LEDs ONDefault setting LEDs BlinkingNew selection LEDs OFFNo selection Indicates if in a main or sub menu with indication LEDs

17 GE job title/17 GE internal information - Not for external distribution 17 GE Security EMEA NPI template – v1 Basic Programming Entering basic programming mode Default BASIC MENU password = 3333 and  The LED on RESET button indicates programming mode by blinking ON and OFF SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE

18 GE job title/18 GE internal information - Not for external distribution 18 GE Security EMEA NPI template – v1 Basic Programming The basic menu Mode Value 43 12 The basic menu allows the installer to set up most common parameters (if necessary) that are different to the factory default configuration. Use the ^ (1) and v (3) keys to navigate through the menus.

19 GE job title/19 GE internal information - Not for external distribution 19 GE Security EMEA NPI template – v1 Basic Programming The basic menu Mode Value 43 12 Panel configuration using regional defaults sets all system parameters up for immediate use. Press  to access the sub-menu to change the basic operating mode. Mode Value Default value = 01 Use the ^ (2) and v (4) keys to navigate through the available options.

20 GE job title/20 GE internal information - Not for external distribution 20 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Modes of operation 43 12 Mode Value Check/verify the default operating mode selected in the basic menu. Press  to access the sub-menu to view the basic operating mode. Mode Value Default value = En

21 GE job title/21 GE internal information - Not for external distribution 21 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Sounder Delay Mode Value 43 12 Set the required sounder delay time. Press  to access the sub-menu to change the sounder delay time. Mode Value Default value = 00 Use the ^ (2) and v (4) keys to navigate through the available options. Options:01 to 10 minutes in 1 minute intervals

22 GE job title/22 GE internal information - Not for external distribution 22 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Fire Routing Delay Mode Value 43 12 Here we set the required fire routing (fire brigade) delay time. Press  to access the sub-menu to change the fire routing delay time. Mode Value Default value = 00 Use the ^ (2) and v (4) keys to navigate through the available options. Options:01 to 10 minutes in 1 minute intervals

23 GE job title/23 GE internal information - Not for external distribution 23 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Fire Routing Extended Delay Mode Value 43 12 Mode Value Here we set the required extended fire routing (fire brigade) delay time. Press  to access the sub-menu to change the extended fire routing delay time. Default value = Not available Use the ^ (2) and v (4) keys to navigate through the available options. Options:01 to 10 minutes in 1 minute intervals

24 GE job title/24 GE internal information - Not for external distribution 24 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Number of modules Mode Value 43 12 Set the number of auxiliary modules installed in the panel. Press  to access the sub-menu to change the number of auxiliary boards installed in the panel. Mode Value Default value = 00 Use the ^ (2) and v (4) keys to navigate through the available options. Options:00 to 04 in 1 unit increments

25 GE job title/25 GE internal information - Not for external distribution 25 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Module A (only available when modules are configured) Mode Value 43 12 Module A through D is assigned from left to right in the cabinet housing. Press  to access the sub-menu to change the module functionality. Mode Value Default = 01 Use the ^ (2) and v (4) keys to navigate through the available options. Options:01 to 92 in unit increments

26 GE job title/26 GE internal information - Not for external distribution 26 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Restore configuration Mode Value 43 12 Returns the panel to the previous saved configuration. Press  to restore the panel to its previous configuration.

27 GE job title/27 GE internal information - Not for external distribution 27 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Factory configuration Mode Value 43 12 Returns the panel to the factory default configuration. Press  to return the panel to the factory default configuration.

28 GE job title/28 GE internal information - Not for external distribution 28 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Exit without saving Mode Value 43 12 Exits the basic menu without saving. Press  to exit the menu and abandon all changes. The panel returns to normal operating mode.

29 GE job title/29 GE internal information - Not for external distribution 29 GE Security EMEA NPI template – v1 Basic Programming The basic menu – Exit & Save Mode Value 43 12 Exits the basic menu and stores the latest configuration. The previous configuration is also saved as a backup. Press  to exit the menu and abandon all changes. The panel returns to normal operating mode.

30 GE job title/30 GE internal information - Not for external distribution 30 GE Security EMEA NPI template – v1 Basic Programming Exiting programming mode After exiting the menu, the panel returns to normal operation. Our application is set-up! SHOWROOM OFFICES/ TOILETS CANTEEN Remember that enabling the sounder delay is a manual operation at EN54 level 2!

31 GE job title/31 GE internal information - Not for external distribution 31 GE Security EMEA NPI template – v1 Advanced Programming Entering advanced programming mode Default ADVANCED MENU password = 4444 and  The LED on RESET button indicates programming mode by flashing ON and OFF SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE

32 GE job title/32 GE internal information - Not for external distribution 32 GE Security EMEA NPI template – v1 Advanced Programming The advanced menu - Mode Value 43 12 The advanced menu allows the installer to set up all configurations options. Default Access Code = 4444 and  Use the ^ (1) and v (3) keys to navigate through the menu.

33 GE job title/33 GE internal information - Not for external distribution 33 GE Security EMEA NPI template – v1 Advanced Programming The advanced menu – Auxiliary Reset Mode Value 43 12 Allows the configuration mode of the auxiliary supply. Press  to access the sub-menu to change the module functionality. Mode Value Default = OF Use the ^ (2) and v (4) keys to navigate through the available options. Options:0N or OF

34 GE job title/34 GE internal information - Not for external distribution 34 GE Security EMEA NPI template – v1 Faultfinding Extensive diagnostic LEDs on the front panel Faultfinding panel indications General Fault LED (Blinking) This indication will always be accompanied by one of the other fault indicators (zone, device or function LEDs) to indicate the exact location of a problem. Depending on the type of fault, this fault may reset automatically when the condition is removed or require user intervention. SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE

35 GE job title/35 GE internal information - Not for external distribution 35 GE Security EMEA NPI template – v1 Faultfinding panel indications Fire Routing Fault (blinking) Supervision (open & short circuit detection) or overload fault on one of the fire routing outputs This fault does not reset automatically SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE Faultfinding Extensive diagnostic LEDs on the front panel

36 GE job title/36 GE internal information - Not for external distribution 36 GE Security EMEA NPI template – v1 Faultfinding panel indications Supply Fault (blinking) Indicates a battery failure – no batteries, low batteries or high resistance failure Supply Fault (constant) Indicates a mains or mains fuse failure These faults reset automatically when the conditions are removed. SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE Faultfinding Extensive diagnostic LEDs on the front panel

37 GE job title/37 GE internal information - Not for external distribution 37 GE Security EMEA NPI template – v1 Faultfinding panel indications Earth Fault (constant) Indicates a connection (+ or -) to earth somewhere in the panel or field wiring. This fault does not reset automatically. SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE Faultfinding Extensive diagnostic LEDs on the front panel

38 GE job title/38 GE internal information - Not for external distribution 38 GE Security EMEA NPI template – v1 Faultfinding panel indications Out of Service (Constant) The control panel is in-operative. It does not have sufficient power to operate on either mains or batteries. SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE Faultfinding Extensive diagnostic LEDs on the front panel

39 GE job title/39 GE internal information - Not for external distribution 39 GE Security EMEA NPI template – v1 Faultfinding panel indications System fault µProcessor failure SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE Faultfinding Extensive diagnostic LEDs on the front panel

40 GE job title/40 GE internal information - Not for external distribution 40 GE Security EMEA NPI template – v1 Faultfinding panel indications Sounder Fault (blinking) Supervision (open & short circuit detection) or overload fault on one of the sounder outputs. This fault does not reset automatically SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE Faultfinding Extensive diagnostic LEDs on the front panel

41 GE job title/41 GE internal information - Not for external distribution 41 GE Security EMEA NPI template – v1 Faultfinding panel indications Service Detector (constant) Indicates that one or more detectors require servicing (CleanMe  )* Enter a valid password. Hold the silence buzzer key for 3 seconds. The zone in maintenance will be indicated on the zone fault LED for the affected zone. *available on Dx700 series detectors only This fault does not reset automatically. SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE Faultfinding Extensive diagnostic LEDs on the front panel

42 GE job title/42 GE internal information - Not for external distribution 42 GE Security EMEA NPI template – v1 Faultfinding panel indications Expansion IO Fault Communication and supervision (if applicable) fault on any of the auxiliary boards. SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE Faultfinding Extensive diagnostic LEDs on the front panel

43 GE job title/43 GE internal information - Not for external distribution 43 GE Security EMEA NPI template – v1 Faultfinding panel indications Zone fault Supervision (open & short circuit detection) or overload fault on the indicated zone. This fault resets automatically when the condition is removed. SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE Faultfinding Extensive diagnostic LEDs on the front panel

44 GE job title/44 GE internal information - Not for external distribution 44 GE Security EMEA NPI template – v1 Testing Lamp Test Can be performed at level EN54 level 1 Push and hold the test button for 3 seconds SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE

45 GE job title/45 GE internal information - Not for external distribution 45 GE Security EMEA NPI template – v1 Testing Entering test mode Default EN54-2 level 2 password = 2222 and  LED on RESET button indicates LEVEL 2 mode by being constantly ON Use the TEST button together with the test/disable buttons for: Zones–to test up to 4 zones simultaneously Fire Routing–to test the fire routing outputs Sounder–to test the sounder outputs (if required)  -to test the auxiliary board outputs SHOWROOM OFFICES/ TOILETS CANTEEN WAREHOUSE