1 Nexus 1-8 Loop (XP95) Analogue Addressable Control Panels From 1 to 8 loops Powerful processing and extensive panel and loop I/O capability Fully compatible with all XP95 devices User-friendly controls and a clear, unambiguous screen Alarm threshold adjustments by device Day/night alarm delay feature Messages edited by PC or keyboard

2 Nexus 1-8 Loop (XP95) Analogue Addressable Control Panels Multiple, fully functional panel displays Radio pager facility Easy to use, Windows-based PC software package Fully networkable with graphics package, network repeaters & other Nexus panels Designed to meet BS5839 Part 4

3 Panel Enhancements Individual panels and Nexus panel networks are programmable via Windows PC package. Up to 31 8-way panel enhancement boards may be added. Two types are available: 1) fully-programmable inputs and relay outputs 2) fully-programmable inputs and alarm outputs Up to 31 8-way panel enhancement boards may be added. Two types are available: 1) fully-programmable inputs and relay outputs 2) fully-programmable inputs and alarm outputs Up to 13 remote panel displays, providing full user & engineer facilities may be connected via RS485 cable. Fully programmable network comprising other Nexus multi-loop panels, graphics systems and network repeaters. Remote Inputs for Silence Alarms, Reset, Evacuate, Class Change, Fault, Buzzer Silence. A wide variety of loop devices are supported, including XP95 detectors, call points, loop sounders, outstations and intrinsically safe devices.

4 Cabinet Options For details of panel dimensions see Application Guide. For details of panel dimensions see Application Guide. Surface Cabinets Cabinet colour reference is: RAL 7035 textured (Light Grey) All cabinets are manufactured from sheet steel and finished in satin texture epoxy powder stove paint. Semi-Flush Cabinets The semi-flush bezel locates to the rear of the bevelled edge of the back box, leaving the bevelled edge and door raised out from the wall. It is finished in the same colour as the back box and is fitted by means of pinch bolts, thus avoiding the need to drill the cabinet. Fully Flush Cabinet (Illustrated) Custom-made to a high quality, full-flush bezels are available in brass, stainless steel, or painted. This option is achieved by fixing a flat bezel assembly to the standard back box, replacing the standard door. The panel comes with assembly already fitted but may be supplied for later on-site fitting (this may be a little time- consuming). Surface Cabinets Cabinet colour reference is: RAL 7035 textured (Light Grey) All cabinets are manufactured from sheet steel and finished in satin texture epoxy powder stove paint. Semi-Flush Cabinets The semi-flush bezel locates to the rear of the bevelled edge of the back box, leaving the bevelled edge and door raised out from the wall. It is finished in the same colour as the back box and is fitted by means of pinch bolts, thus avoiding the need to drill the cabinet. Fully Flush Cabinet (Illustrated) Custom-made to a high quality, full-flush bezels are available in brass, stainless steel, or painted. This option is achieved by fixing a flat bezel assembly to the standard back box, replacing the standard door. The panel comes with assembly already fitted but may be supplied for later on-site fitting (this may be a little time- consuming).

5 Mechanical Assembly Motherboard holds Konex network card and 2 loop cards. Display assembly located on removable door. Motherboard and power supply located on removable chassis to assist cabinet installation. Zone LEDs and option printer are located on display board. Space for internal 12Ah battery set. A1535 programmable relay board / A1536 programmable alarm board - a maximum of 2 boards may be housed internally and up to 29 externally. Loop extension motherboard - this chassis is located in the right hand section of the enclosure.

6 User Controls The engineer accesses panel configuration functions using the numerical designations. The menu structure on the LCD display guides the engineer through the different set-up facilities. System LED indications are provided in addition to the LCD display. The backlit LCD display gives information of loop, device and zone number, device type and event condition, together with a user-definable text description. The text descriptions give the user clear, single-operation functional controls.

7 Typical LCD Illustration The device types which may be indicated are as follows: SOU- Loop sounder/sounder circuit controller O/S - Input/Output device ION- Ionisation smoke sensor MON- Monitor (zone monitor, control monitor) OPT- Optical smoke sensor HEAT- Heat sensor BGU- Call point or call point monitor The device types which may be indicated are as follows: SOU- Loop sounder/sounder circuit controller O/S - Input/Output device ION- Ionisation smoke sensor MON- Monitor (zone monitor, control monitor) OPT- Optical smoke sensor HEAT- Heat sensor BGU- Call point or call point monitor

8 Display /Repeater PCB (A1575) Viewed from Inside Cabinet LCD display. Power supply fault input when used as a repeater with a local power supply unit. Comms link to the main panel motherboard. System Eprom. S13 Display number Address switch (Node Address Switch) 16 way ribbon connector to the printer interface. 16 way ribbon connector to the zone board. DC power in.

9 Zone Indications The Nexus 1-8 loop panel provides 64 fully programmable zone LEDs. The zone identification label may be inserted from inside the cabinet

10 Engineer Facilities The fault LEDs, fuses and DIL switch are easily accessible for the engineer when the user display board has been removed.

11 Power Supply The fault LEDs, fuses and DIL switch are easily accessible for the engineer when the user display board has been removed. These LED indications give the engineer more details of the fault when the Power Supply Fault message has appeared on the panel display. Test lamp switch. Decoupling link. 230V AC supply. Battery supply fuse Amps.

12 Printer Designed for easy replacement of the paper roll onto the carrier. This good quality printer uses a reliable Epson mechanism. This button advances the paper. Open access to feed paper through mechanism. Engineers printer test button. Hinged access to allow easy ribbon change.

13 A Way Relay Board RS485 comms from panel motherboard. 8 inputs may be normally open or normally closed and will register as fire or non-fire on the panel as configured. Inputs are fully programmable via the panel or PC cause/effect. 24V DC power. 8 x 1Amp changeover relay outputs may be fully programmed via the panel or PC cause/effect programme. Engineers DIL switches to set board address, enable O/C or S/C inputs and disable inputs/outputs. Engineers links to disable functions for set- up or maintenance purposes.

14 A Way Alarm Board Engineers buzzer disable link for set-up or maintenance purposes. 8 x 1Amp two- stage alarm outputs may be fully programmed via the panel or PC cause/effect. Engineers DIL switches to isolate alarm outputs individually. 8 normally open inputs which will register as fire or non-fire on the panel as configured. Inputs are fully programmable via panel or PC cause/effect. 24V DC power. Test alarms when switched to 0V. Alarm Fault LEDs. RS485 comms from panel motherboard. Engineers DIL switches to set board address, disable inputs and outputs, test LEDs and test alarms.

15 Windows-based PC Programming A Windows-based PC programming package is available for panel set up, zones, text, local and network cause/effect.

16 Typical Radio Pager Configuration The radio pager system, when connected to the control panel, can be used to transmit both text and numeric messages direct to pocket pagers. Pagers will display Fire / Fault conditions including Sensor location text. Up to 9,999 pagers can be connected to system. Connection to panel printer port. Interface board Opto isolator Transmitter

17 XP95 Test Tool The XP95 Test Tool is an engineers tool to assist with commissioning and fault finding on XP95 loop systems. Loop configurations and the status of each device may be interrogated, device LEDs may be turned on/off. The test tool may be connected to an entire loop without the panel connected or connected to individual devices around the circuit. Alpha-numeric LCD display. Engineers keypad. On/off switch and LED indication. Battery charger socket. Sockets for flying leads to connect to loop and/or individual XP95 devices.