Master Examination Practice Drill # O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded.
Advertisements

Master Examination Practice Drill # Ted “Smitty” Smith.
DAY 4 CHAPTER 3 CONDUCTOR SIZES,TYPES, ETC.. Continuous Load. A load where the maximum current is expected to continue for 3 hours or more. Continuous.
Master Examination Practice Drill # (16) O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles.
2014 CHANGES TWO MINUTE DRILL COPYRIGHT TED “SMITTY” SMITH ©2014.
©Ted “Smitty” Smith This speed drill focuses on calculations that will be required for the journeyman and masters examination. The question slide.
Copyright 2005 Ted "Smitty" Smith Two Minute Drill Number Three Improving your skill in code Look Up Increasing Speed Drill.
Two Minute Drill Number 32- Journeyman Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 25- Residential Improving your skill in code Look Up Increasing Speed Drill.
©Ted “Smitty” Smith  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead.
Two Minute Drill Number 26- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.
Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage.
Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith.
Two Minute Drill Number 27- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Calculation Speed Drill # NEC
Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1.
Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6.
Copyright 2008 Ted "Smitty" Smith.  Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. 
©Ted “Smitty” Smith This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.
Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 31- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 22- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 24- Residential.
Speed Drill 51 Wireways and Raceways.
2008 Code Drills (C) Copyright 2008 Ted "Smitty" Smith 1 Smitty’s Speed Drills.
Ag. Mechanics for Beginning Teachers
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 21- Residential Improving your skill in code Look Up Increasing Speed Drill.
Suggestion on How to Use
P RACTICE C ODE L OOK U P Two Minute Drill #7 Copyright 2005 Ted "Smitty" Smith.
Smitty’s Two Minute Drill Grounding
Smitty’s Two Minute Drill Grounding
Advanced Calculations Drill 1 for the 2011 NEC
License Examination Practice Drill
Special-Purpose Outlets— Electric Heating, Air Conditioning
2011 Changes Two Minute Drill
Smitty’s Two Minute Drills
Smitty’s Two Minute Drill Overcurrent Protection
Smitty’s Two Minute Drill Mixed Content -05
Theory and Calculations
Smitty’s Two Minute Drill #9: Special Occupancies
Practice Code Look Up Two Minute Drill #7
Conductors and Cables 2017 NEC
Ampacity Calculations and Overcurrent Protection 1
Calculation Speed Drill #1
Calculations: Transformers and Service Conductor Calculations
Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
Two Minute Drill: Raceways and Boxes 2017
Smitty’s Two Minute Drill Photovoltaic Systems
Overcurrent Protection— Fuses and Circuit Breakers
2014 Changes Two Minute Drill
EET 323 – Electrical System Design Lecture 9: Grounding
Two Minute Drill Number 29- Conductors and Raceways
Smitty’s Two Minute Drill Grounding and Bonding
Wiring Circuits Lesson Plan PSTS: C6-7.
Transformer Calculations: Word Problems
2008 Code Drills Health Care Facilities
Smitty’s Two Minute Drill Services, Feeders, and Branch Circuits 1
Load Calculation Speed Drill
Two Minute Drill – Residential 3
Smitty’s Two Minute Drill Varied Number 7
Smitty’s Two Minute Drill General Knowledge
Smitty’s Two Minute Drill The BIG 5 Drill 1
Two Minute Drill – Residential 2
Calculations Review Drill
Cooking , Electric Dryer and Appliance Calculations 3
Calculation Speed Drill Varied-1
Varied Calculations Drill 2
Presentation transcript:

Two Minute Drill #8 Copyright 2005 Ted "Smitty" Smith Practice Code Look Up

Directions Copyright 2005 Ted "Smitty" Smith Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:00 minutes or less. The correct answer will transition in 10 seconds. Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill exercise. Good luck

Further More Copyright 2005 Ted "Smitty" Smith  Remember do not worry about writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then.  Concentrate on finding the answers using the targeting method and then worry about the correct answers after you reach the slide that says the end.  All of the questions now will be multiple choice.  Click on the slide to proceed.

Conductors Copyright 2005 Ted "Smitty" Smith  Conductors larger than ___________ AWG may be marked as grounded and equipment grounding conductors by using the correctly colored electrical tape and wrapping it around the conductors insulation.  A. 2  B. 4  C. 6  D. 8

Conductors Copyright 2005 Ted "Smitty" Smith C. 6 AWG (A) and 200.6(B)

Equipment Copyright 2005 Ted "Smitty" Smith A ballast in a fluorescent luminaire that is used for egress lighting and energized only during the a failure of the normal supply shall not have thermal protection. A. True B. False

Equipment Copyright 2005 Ted "Smitty" Smith A. True (E)(4)

Grounding Copyright 2005 Ted "Smitty" Smith Contact devices or yokes designed and listed as __________________ shall be permitted in conjunction with the supporting screws to establish the grounding circuit between the device yoke and flush-type boxes. A. self tapping B. secured in place C. self grounding D. automatically grounded

Grounding Copyright 2005 Ted "Smitty" Smith C. self grounding (B)

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection. What is the minimum sized THHN conductor that can be used to feed this circuit? A. 1/0 AWG B. 200 Kcmil C. 250 Kcmil D. 300 Kcmil

Calculations Copyright 2005 Ted "Smitty" Smith D. 300 Kcmil Don’t forget to consider (C) when determining the conductor size.

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A, with a marked service factor of 1.15 and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection. What is the minimum sized overload protection that could be used for motor C? A. 36 A B A C. 49 A D. None of the above

Calculations Copyright 2005 Ted "Smitty" Smith C. 49 Amps (A) Do not round off answers or use standard size fuses when determining over load sizes.

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A, with a marked service factor of 1.15 and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection.  What is the maximum sized short circuit branch circuit protection that can be used for motor A if a duel element, time delayed fuse where to be used? A A B. 180 A C. 200 A D. 175 A

Calculations Copyright 2005 Ted "Smitty" Smith C. 200 A Remember that you round up to the next standard size for branch circuit protection and also that you use the table value for the full load current, not the name plate value. The nameplate value is used only for determining the overload protection.

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A, with a marked service factor of 1.15 and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection. What is the maximum size or setting of overload protection that can be used to protect motor C if an overload relay is used? A B C D

Services Copyright 2005 Ted "Smitty" Smith A (C) Remember to use the nameplate full load current

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A, with a marked service factor of 1.15 and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection. What is the maximum sized duel element fuse that can be used to protect the feeder conductors for this motor circuit if motor A has 125A duel element fuses for branch circuit protection and motor B has 50 ampere duel element fuses for branch circuit protection and motor C has 50 ampere duel element fuses for branch circuit protection. A. 190a B. 200a C. 215a D. 250a

Calculations Copyright 2005 Ted "Smitty" Smith B. 200 a Remember to round down to the next standard size for feeder protection. Also remember to look at to ensure you are using the correct standard sizes.

Motors Copyright 2005 Ted "Smitty" Smith Controllers, other than ______________ and molded case switches, shall have horsepower ratings at the application voltage not lower than the horsepower rating of the motor. A. dual element fuses B. Instantaneous trip circuit breakers C. Inverse time circuit breakers D. None of the above

Motor Copyright 2005 Ted "Smitty" Smith C. Inverse time circuit breakers (A)

Raceways Copyright 2005 Ted "Smitty" Smith ENT must be secured in place every ______. A. 12 inches B. 18 inches C. 24 inches D. 36 inches

Raceways Copyright 2005 Ted "Smitty" Smith D. 36 inches (A)

Raceways Copyright 2005 Ted "Smitty" Smith The minimum burial depth for a nonmetallic raceway under a 4 inch thick concrete exterior slab in a wide driveway for a commercial building shall be __________________ inches. A. 4 inches B. 12 inches C. 18 inches D. 24 inches

Raceways Copyright 2005 Ted "Smitty" Smith 24" Table Col. 3

Calculations Copyright 2005 Ted "Smitty" Smith What is the demand on the main service entrance cable for a 15.6kw rated range at 240V? A watts B watts C watts D watts

Calculations Copyright 2005 Ted "Smitty" Smith 9600 watts Tble note 1

Equipment Copyright 2005 Ted "Smitty" Smith In areas used for patient care, the grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electric equipment ______________ shall be grounded by an insulated copper equipment grounding conductor. Operating at over 100 V Likely to become energized Subject to personal contact All of these

Equipment Copyright 2005 Ted "Smitty" Smith All of these (B)

Equipment Copyright 2005 Ted "Smitty" Smith At what ambient temperature must conductors be coordinated for determining ampacity if they are installed above a radiant heating ceiling panel? 20 degrees C 40 degrees C 50 degrees C None of above

Equipment Copyright 2005 Ted "Smitty" Smith 50 degrees C

Equipment Use Copyright 2005 Ted "Smitty" Smith Receptacles mounted in boxes that are set back of the wall surface shall be installed so that the mounting ____________________ of the receptacle is held rigidly at the surface of the wall Screws or nails yoke or strap face plate none of these

Equipment Use Copyright 2005 Ted "Smitty" Smith yoke or strap 406.4(A)

Equipment Copyright 2005 Ted "Smitty" Smith Receptacle faceplate covers made of insulating material shall be noncombustible and not less than _____________ in thickness..10 in.04 in.01 in.22 in

Equipment Copyright 2005 Ted "Smitty" Smith.10 in 406.5(C)

Equipment Copyright 2005 Ted "Smitty" Smith Receptacles installed outdoors in a location protected from the weather or other damp locations shall be in an enclosure that is _____________________ when the receptacle is covered. rain tight weatherproof rainproof weather tight

Equipment Copyright 2005 Ted "Smitty" Smith weatherproof 406.8(A)

Equipment Copyright 2005 Ted "Smitty" Smith Electric heaters of the cord and plug connected immersion type shall be constructed and installed so that current carrying parts are effectively ____________ from electrical contact with the substance in which they are immersed. isolated protected insulated all of these

Equipment Copyright 2005 Ted "Smitty" Smith insulated

Equipment Copyright 2005 Ted "Smitty" Smith The minimum clearance between an electric space-heating cable and an outlet box used for surface luminaries shall not be less than _________________. 8 in 14 in 18 in 6 in

Equipment Use Copyright 2005 Ted "Smitty" Smith 8 in

Calculations Copyright 2005 Ted "Smitty" Smith What is the minimum sized conductor that can be used for a 20 ampere load if the conductors will be installed in a conduit with a total of 9 current carrying conductors. The conductors will be TW conductors. A. 12 AWG B. 10 AWG C. 8 AWG D. 6 AWG

Feeders and Branch Circuits Copyright 2005 Ted "Smitty" Smith 10 AWG Tble and Tble (B)(2)(a)

The End Copyright 2005 Ted "Smitty" Smith Each of the slides will now be repeated. They are not timed in this segment. To change a slide, click on the side with your left mouse button. Be sure to physically look up the answers in your code book to improve your look up speed and skill.

Conductors Copyright 2005 Ted "Smitty" Smith  Conductors larger than ___________ AWG may be marked as grounded and equipment grounding conductors by using the correctly colored electrical tape and wrapping it around the conductors insulation.  A. 2  B. 4  C. 6  D. 8

Conductors Copyright 2005 Ted "Smitty" Smith C. 6 AWG (A) and 200.6(B)

Equipment Copyright 2005 Ted "Smitty" Smith A ballast in a fluorescent luminaire that is used for egress lighting and energized only during the a failure of the normal supply shall not have thermal protection. A. True B. False

Equipment Copyright 2005 Ted "Smitty" Smith A. True (E)(4)

Grounding Copyright 2005 Ted "Smitty" Smith Contact devices or yokes designed and listed as __________________ shall be permitted in conjunction with the supporting screws to establish the grounding circuit between the device yoke and flush-type boxes. A. self tapping B. secured in place C. self grounding D. automatically grounded

Grounding Copyright 2005 Ted "Smitty" Smith C. self grounding (B)

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection. What is the minimum sized THHN conductor that can be used to feed this circuit? A. 1/0 AWG B. 200 Kcmil C. 250 Kcmil D. 300 Kcmil

Calculations Copyright 2005 Ted "Smitty" Smith D. 300 Kcmil Don’t forget to consider (C) when determining the conductor size.

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A, with a marked service factor of 1.15 and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection. What is the minimum sized overload protection that could be used for motor C? A. 36 A B A C. 49 A D. None of the above

Calculations Copyright 2005 Ted "Smitty" Smith C. 49 Amps (A) Do not round off answers or use standard size fuses when determining over load sizes.

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A, with a marked service factor of 1.15 and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection.  What is the maximum sized short circuit branch circuit protection that can be used for motor A if a duel element, time delayed fuse where to be used? A A B. 180 A C. 200 A D. 175 A

Calculations Copyright 2005 Ted "Smitty" Smith C. 200 A Remember that you round up to the next standard size for branch circuit protection and also that you use the table value for the full load current, not the name plate value. The nameplate value is used only for determining the overload protection.

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A, with a marked service factor of 1.15 and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection. What is the maximum size or setting of overload protection that can be used to protect motor C if an overload relay is used? A B C D

Services Copyright 2005 Ted "Smitty" Smith A (C) Remember to use the nameplate full load current

Calculations Copyright 2005 Ted "Smitty" Smith A motor circuit feeds three squirrel cage motors. The circuit is a three-phase, 208V circuit. Motor A is a three phase, 40hp, with a nameplate FLC of A, a Marked Service Factor of 1.2, and is a design B motor. Motor B is a three phase, 15hp, with a nameplate FLC of 39.2 A, with a marked service factor of 1.15 and is a Design C motor, and Motor C is a single phase, 7.5hp, with a nameplate FLC of 33.8 A, a marked service factor of 1.6 and is a design K motor. All of the motors are protected with duel element fuses for short circuit branch circuit protection. What is the maximum sized duel element fuse that can be used to protect the feeder conductors for this motor circuit if motor A has 125A duel element fuses for branch circuit protection and motor B has 50 ampere duel element fuses for branch circuit protection and motor C has 50 ampere duel element fuses for branch circuit protection. A. 190a B. 200a C. 215a D. 250a

Calculations Copyright 2005 Ted "Smitty" Smith B. 200 a Remember to round down to the next standard size for feeder protection. Also remember to look at to ensure you are using the correct standard sizes.

Motors Copyright 2005 Ted "Smitty" Smith Controllers, other than ______________ and molded case switches, shall have horsepower ratings at the application voltage not lower than the horsepower rating of the motor. A. dual element fuses B. Instantaneous trip circuit breakers C. Inverse time circuit breakers D. None of the above

Motor Copyright 2005 Ted "Smitty" Smith C. Inverse time circuit breakers (A)

Raceways Copyright 2005 Ted "Smitty" Smith ENT must be secured in place every ______. A. 12 inches B. 18 inches C. 24 inches D. 36 inches

Raceways Copyright 2005 Ted "Smitty" Smith D. 36 inches (A)

Raceways Copyright 2005 Ted "Smitty" Smith The minimum burial depth for a nonmetallic raceway under a 4 inch thick concrete exterior slab in a wide driveway for a commercial building shall be __________________ inches. A. 4 inches B. 12 inches C. 18 inches D. 24 inches

Raceways Copyright 2005 Ted "Smitty" Smith 24" Table Col. 3

Calculations Copyright 2005 Ted "Smitty" Smith What is the demand on the main service entrance cable for a 15.6kw rated range at 240V? A watts B watts C watts D watts

Calculations Copyright 2005 Ted "Smitty" Smith 9600 watts Tble note 1

Equipment Copyright 2005 Ted "Smitty" Smith In areas used for patient care, the grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electric equipment ______________ shall be grounded by an insulated copper equipment grounding conductor. Operating at over 100 V Likely to become energized Subject to personal contact All of these

Equipment Copyright 2005 Ted "Smitty" Smith All of these (B)

Equipment Copyright 2005 Ted "Smitty" Smith At what ambient temperature must conductors be coordinated for determining ampacity if they are installed above a radiant heating ceiling panel? 20 degrees C 40 degrees C 50 degrees C None of above

Equipment Copyright 2005 Ted "Smitty" Smith 50 degrees C

Equipment Use Copyright 2005 Ted "Smitty" Smith Receptacles mounted in boxes that are set back of the wall surface shall be installed so that the mounting ____________________ of the receptacle is held rigidly at the surface of the wall Screws or nails yoke or strap face plate none of these

Equipment Use Copyright 2005 Ted "Smitty" Smith yoke or strap 406.4(A)

Equipment Copyright 2005 Ted "Smitty" Smith Receptacle faceplate covers made of insulating material shall be noncombustible and not less than _____________ in thickness..10 in.04 in.01 in.22 in

Equipment Copyright 2005 Ted "Smitty" Smith.10 in 406.5(C)

Equipment Copyright 2005 Ted "Smitty" Smith Receptacles installed outdoors in a location protected from the weather or other damp locations shall be in an enclosure that is _____________________ when the receptacle is covered. rain tight weatherproof rainproof weather tight

Equipment Copyright 2005 Ted "Smitty" Smith weatherproof 406.8(A)

Equipment Copyright 2005 Ted "Smitty" Smith Electric heaters of the cord and plug connected immersion type shall be constructed and installed so that current carrying parts are effectively ____________ from electrical contact with the substance in which they are immersed. isolated protected insulated all of these

Equipment Copyright 2005 Ted "Smitty" Smith insulated

Equipment Copyright 2005 Ted "Smitty" Smith The minimum clearance between an electric space-heating cable and an outlet box used for surface luminaries shall not be less than _________________. 8 in 14 in 18 in 6 in

Equipment Use Copyright 2005 Ted "Smitty" Smith 8 in

Calculations Copyright 2005 Ted "Smitty" Smith What is the minimum sized conductor that can be used for a 20 ampere load if the conductors will be installed in a conduit with a total of 9 current carrying conductors. The conductors will be TW conductors. A. 12 AWG B. 10 AWG C. 8 AWG D. 6 AWG

Feeders and Branch Circuits Copyright 2005 Ted "Smitty" Smith 10 AWG Tble and Tble (B)(2)(a)