FIREFIGHTER I LESSON 15. SPRINKLER SYSTEM DESIGN AND OPERATION Series of sprinklers arranged to automatically distribute enough water to extinguish or.

Slides:



Advertisements
Similar presentations
Sprinkler Systems and Standpipe Operations
Advertisements

Fire Protection Systems
Chapter 16 Lesson Goal After completing this lesson, the student shall be able to operate various fire detection, alarm, and suppression systems and operate.
Slide 5-1 UNIT 5: WATER SUPPLY, FIXED FIRE PROTECTION SYSTEMS, AND SALVAGE.
Buildings and Structures 2 Fixed Installations Aim To provide students with information to allow them to recognise the types of fixed fire protection.
Unit 3 Fire Suppression Section 1 Detection and Alarm Systems.
Wet Sprinkler Systems Identifying components of, and inspection and testing procedures.
Water Based Sprinkler Systems 2 major different types of water sprinkler systems Wet pipe system Dry pipe system.
UL/FM Fire Pump Systems Lunch & Learn 04/18/05
State of Georgia BASIC FIRE FIGHTER TRAINING COURSE
Augmenting Fire Standpipe Systems
BS9990 : 2015 Updates and/or Changes
Chapter 12 Systems and Equipment for Fire Protection.
4/15/2017 7:34 AM Fire Sprinkler Systems Prepared by Thomas Bartsch Chief Fire Inspector (ret) Former Chief of Department, Valley Stream, NY © 2007.
CVFD Training – Water Supply SFFMA Training Objectives: –
HH H OUSTON H OUSTON F IRE F IRE D EPARTMENT P UMP P UMP O PERATOR O PERATOR P ROGRAM VAL JAHNKE TRAINING FACILITY.
Fire Streams SFFMA Training Objectives: –
Automatic Sprinkler System. Importance of Sprinklers First line of protection – small fires Enhanced protection Business protection – less interruption.
AUTOMATIC SPRINKLERS.
3-1 NFIRS 3 Structure Fire Module. 3-2 ObjectivesObjectives The participants will be able to: –describe when the Structure Fire Module is to be used.
WATER SUPPLY Copyright© Delmar is a division of Thomson Learning.
Purpose of Standpipe and Hose Systems
Chapter 9 Water Supply.
1402 Hybrid Firefighter I 6 th Edition Chapter 14 Water Supply.
Chapter 9. Please read chapter 9.  Please review, know and understand the terms related to fire protection page 284.  Know the Classifications of.
C L A S #4 Driver Operator Refresher Training.
Pumping Apparatus Driver/Operator
Automatic Sprinkler Systems
CVFD Training – Fire Protection Systems
Intermediate SFFMA Objectives: – Hrs received.
Augmenting Sprinkler Systems
Fuel Oil Systems Fuel Oil Systems consist of: Storage Tanks Pumps
Hydronic Mechanical Controls
Module C Sprinkler systems (4-20)
Learning Objective 1 Explain the ways water supply system components are used by firefighters.
Fresno County Fire Protection District. Fire Sprinklers Systems Residential – 13D October 30, 2007.
Technical Review Needed Fire Flow Analysis Developer Services Summit November 16, 2010 Engineering - Asset Planning Joe Dugandzic, PE.
State of Georgia BASIC FIRE FIGHTER TRAINING COURSE
If you hear the fire alarm sound, evacuate immediately! Check door for signs of fire Close doors behind you to prevent fire & smoke spread Keep storage.
Fire Pump Functions The main function of a fire pump is to increase the pressure of the water that flows through it. Inadequate or nonexistent municipal.
Fire Department Hydraulics
FIREFIGHTER II LESSON 12. TYPES OF VALVES Ball — Ball — Controls nozzle flow and pump discharge rates Gate — Gate — Controls hydrant flow Butterfly.
1402 Hybrid Firefighter II 6th Edition Chapter 15 — Fire Hose South Carolina Fire Academy.
CHAPTER 9 Copyright © 2007 Thomson Delmar Learning 9.1 Water Supply.
Pre Incident Planning and Related Loss Reduction Strategies
MODULE:3 FIRE CONFINMENT AND EXTINGUISHMENT. OBJECTIVES Module 3 Select and deploy the appropriate hose lines to accomplish fire confinement and extinguishment.
Water Supply Skill Drills.
Fire Stream and Line Selection Firefighter II. Copyright © Texas Education Agency All rights reserved. Images and other multimedia content used.
MODULE:3 FIRE CONFINMENT AND EXTINGUISHMENT. OBJECTIVES Module 3 Overview Select and deploy the appropriate hose lines to accomplish fire confinement.
CHAPTER 12 Copyright © 2007 Thomson Delmar Learning 12.1 Protective Systems.
MODULE 4: WATER SUPPLY AND EXPOSURE PROTECTION. OBJECTIVES Module 4 Overview Identify the principles of water supply and tactics for establishing water.
Firefighter III Module B Water Supply (4-19) (4-19)
Fire Protection Systems Chapter 6. Fire Protection Systems Most of the time you will work with an electrical engineer or fire-protection designer to coordinate.
MODULE 2 Operate the Propane Liquid Supply System.
MODULE 4: WATER SUPPLY AND EXPOSURE PROTECTION. OBJECTIVES Module 4 Identify the principles of water supply and tactics for establishing water supplies.
3.1.8 Student Book © 2004 Propane Education & Research CouncilPage Identifying Procedures for Conducting Container Vapor Flaring Operations Before.
15 Water Supply. 15 Objectives (1 of 2) Discuss rural water supplies. Describe how portable tanks are used to supply water for firefighting. Describe.
Video: Fire Hydrant Time: 1:01 Chap 14-1
The purpose of installing fire fighting equipments is to protect the public, property, and assets in fire emergency. Manufacturers of fire protection.
Water Shuttle Operations
IFSTA Chapter 16 Fire Streams
Operating Fire Pumps Sugar Land Fire Department Driver/Operator—Pumper Academy Spring 2003.
Fire Protection Systems for Facility Managers Michael Salazar NICET Level 2.
Welcome To High Rise Operations ! Like The Jefferson's...
Dual Pumping Definition: An operation where a strong hydrant is used to supply two Engines by connecting the Engines intake-to-intake. The second Engine.
AUTOMATIC SPRINKLERS.
NFIRS 3 Structure Fire Module
Firefighting equipment
Sprinkler Systems: Review and Response Considerations
Bella Vista Fire Department Procedures on Sprinkled Buildings
Presentation transcript:

FIREFIGHTER I LESSON 15

SPRINKLER SYSTEM DESIGN AND OPERATION Series of sprinklers arranged to automatically distribute enough water to extinguish or check fire Series of sprinklers arranged to automatically distribute enough water to extinguish or check fire Water is supplied to sprinklers through a piping system Water is supplied to sprinklers through a piping system System’s sprinkler heads discharge water after a cap or plug is released by a heat-responsive element System’s sprinkler heads discharge water after a cap or plug is released by a heat-responsive element TS 15–1

SPRINKLER SYSTEM ADVANTAGES Most reliable Most reliable Most effective (control 96% of fires in sprinkler- protected buildings) Most effective (control 96% of fires in sprinkler- protected buildings) Less business interruption Less business interruption Less water damage Less water damage Enhance life safety Enhance life safety Reduce insurance costs Reduce insurance costs TS 15–2

SPRINKLER SYSTEM MAIN CONTROL VALVE Purpose Purpose — Cutting off the water supply to the system so that sprinklers can be replaced, maintenance performed, or operations interrupted Location Location — Immediately under the sprinkler alarm valve, the dry-pipe or deluge valve, or outside the building near the system connections Position after maintenance Position after maintenance — Open Type Type — Manual indicating valve TS 15–3

CAUSES OF SPRINKLER FAILURE Partially or completely closed main water control valve Partially or completely closed main water control valve Interruption to municipal water supply Interruption to municipal water supply Damaged or painted-over sprinklers Damaged or painted-over sprinklers Frozen or broken pipes Frozen or broken pipes Excess debris or sediment in pipes Excess debris or sediment in pipes Failure of a secondary water supply Failure of a secondary water supply Tampering and vandalism Tampering and vandalism TS 15–4

SITUATIONS IN WHICH SPRINKLERS ARE EFFECTIVE Preventing fire spread upwards in multiple- story buildings Preventing fire spread upwards in multiple- story buildings Protecting the lives of occupants in other parts of the building Protecting the lives of occupants in other parts of the building TS 15–5

SITUATIONS IN WHICH SPRINKLERS MAY NOT BE EFFECTIVE Fires too small to activate sprinkler system Fires too small to activate sprinkler system Smoke reaches occupants before sprinkler system activates Smoke reaches occupants before sprinkler system activates Sleeping, intoxicated, or handicapped persons occupy fire building Sleeping, intoxicated, or handicapped persons occupy fire building TS 15–6

WATER SUPPLY SOURCES Public Water System Fire Pumps from Private Storage Fire Department Connection (FDC) TS 15–7

PURPOSES OF A FIRE DEPARTMENT CONNECTION (FDC) Providing additional water and pressure to boost the existing system in the event of a large fire Providing additional water and pressure to boost the existing system in the event of a large fire Providing backup water and pressure should a pipe break Providing backup water and pressure should a pipe break TS 15–8

FDC COMPONENTS & DIMENSIONS Siamese with at least two 2½-inch (65 mm) female connections with a clapper valve, or Siamese with at least two 2½-inch (65 mm) female connections with a clapper valve, or One large-diameter connection connected to a clappered inlet One large-diameter connection connected to a clappered inlet TS 15–9

FDC CHECK VALVE Purpose Purpose — Preventing water flow back into FDC while allowing water from FDC to flow into system Water flow Water flow — Direction indicated by arrows on valve or appearance of valve casing Ball drip valve within Ball drip valve within — Keeping check valve and connection dry and operational in freezing weather TS 15–10

FDC HOSE SIZES & MINIMUM PUMP CAPACITY Hose sizes Hose sizes  Minimum of two 2½-inch (65 mm), or  One large-diameter Minimum pump capacity for a pumper supplying a sprinkler system Minimum pump capacity for a pumper supplying a sprinkler system — At least 1,000 gpm (4 000 L/min) TS 15–11

GUIDELINES FOR OPERATIONS AT PROTECTED PROPERTIES Connect to FDC (earliest arriving pumper) per pre-incident plan. Connect to FDC (earliest arriving pumper) per pre-incident plan. Check to ensure that sprinkler system control valves are open. Check to ensure that sprinkler system control valves are open. Do not close sprinkler control valves until ordered to do so by fire officer. Do not close sprinkler control valves until ordered to do so by fire officer. Station a firefighter with a portable radio at closed sprinkler control valve in case it needs to be reopened. Station a firefighter with a portable radio at closed sprinkler control valve in case it needs to be reopened. TS 15–12a

GUIDELINES FOR OPERATIONS AT PROTECTED PROPERTIES (cont.) Do not disconnect pumpers until after extinguish- ment has been determined by a thorough overhaul. Do not disconnect pumpers until after extinguish- ment has been determined by a thorough overhaul. Do not leave the premises until the sprinkler system has been restored to service by a qualified representative of the occupant. Do not leave the premises until the sprinkler system has been restored to service by a qualified representative of the occupant. TS 15–12b

HOW TO SUPPLY ADEQUATE WATER TO THE SYSTEM Limit use of direct hoselines from sprinkler system water supply system. Limit use of direct hoselines from sprinkler system water supply system. Establish a second water supply for hoselines if necessary. Establish a second water supply for hoselines if necessary. Observe sprinkler discharge in the area of fire, and maintain adequate pressure at pumper. Observe sprinkler discharge in the area of fire, and maintain adequate pressure at pumper. Improve discharge from the sprinklers as necessary by increasing pressure on system. Improve discharge from the sprinklers as necessary by increasing pressure on system. TS 15–13