TESTING, MAINTENANCE & PROTECTION OF DISTRIBUTION TRANSFORMERS

Slides:



Advertisements
Similar presentations
Inspection & Preventive maintenance of breakers
Advertisements

Chapter 12 Transformers. Chapter 12 Transformers.
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
RMM Systems, LLC By Sam Rietta RMM Systems, LLC is a manufacturer's representative firm focused on providing value added sales solutions by providing.
GENERATOR PROTECTION.
Dry type transformers Zaragoza Traction application
Topic 1 : Magnetic Concept and Transformer
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Dry type transformers Zaragoza Accessories and options
Transformers.
Transformer.
Chapter 19 Charging Systems.
Transformers.
Electrical Machine-I EE 2107 Dr. Md. Sherajul Islam
Substations. Substations Chapter 4 Substations Major types of equipment found in most transmission and distribution substations with their purpose,
Quality Service Providing Quality Performance.
TESTING AND COMMISIONING
Chapter 2 Transformers.
Transformers Mechanical and Electrical Systems SKAA 2032
ABSTRACT: Electricity is a form a energy and is playing vital role in the world. Electricity has become a part of human life. Electricity is developed.
Transformer.
Protection & Switchgear
Transformer Protection Over-current protection in the form of fuses may be the only protection provided to a small 100 kVA, 11 kV/440 V distribution transformer.
Transformer condition assessment with an integrated test van
POWER HOUSE.
Submitted to: Submitted by:
A PRESENTATION OF PRACTICAL TRAINING ON “400KV GSS “ \
A Presentation On 132 KV GSS BEHROR
SEMINAR PRESENTATION ON 220 KV GSS UDAIPUR
ON 400 KV GSS RAISER JAIPUR ROAD ,BIKANER
A SEMINAR ON 400 KV GSS(RRVPNL) BIKANER.
Submitted To:- Submitted By:- Mr.
SMJE 2103 Overvoltage, Electrical Insulation and Protection Devices.
HIMACHAL PRADESH STATE ELECTRICITY BOARD LTD.
HASMUKH GOSWAMI COLLEGE OF ENGINEERING
Transformer vaishnav gaurav yadav shalu
Instrument Transformer Electrical Measuring Instruments & Instrumentation 3rd SEMESTER ELECTRICAL ENGG.
D.C. Machine & Transformer Topic: Instrument Transformer Electrical:-1 presented by: Jill Chauhan ( ) Chirag Agarawal ( )
1 :. Introduction These are special type of transformers used for the measurement of voltage, current, power and energy. As the name suggests, these transformers.
DC Machine & Transformer
Outage of Generator Transformer due to High DGA. BRIEF HISTORY 200 MVA 400 kV GT erected at site. After satisfactory pre-commissioning checks GT was successfully.
Md.Hamidul Haque ID: Prog:BSEEE SEC:E/3 International University of Business Agriculture and Technology (IUBAT )
Current Transformer Testing
ET 332b Ac Motors, Generators and Power Systems 1 Lesson 11_et332b.pptx.
Auto Transformer Current Flow. Principles of Auto Transformers H X H0/X0.
HNC/D Engineering Science
Transformer Professor Mohamed A. El-Sharkawi
TESTING AND MAINTENANCE OF POWER TRANSFORMER
Introduction High Voltage!!.
POWER DISTRIBUTION & POWER LOSS REDUCTION METHODS
TRANSFORMERS.
CHAPTER 4 SINGLE-PHASE TRANSFORMER
Lesson 10: Transformer Performance and Operation
Balaji engineering college Special transformer
CHAPTER 6 SPECIAL TRANSFORMERS Electrical Machines.
WELCOME.
Testing of Transformers
Welcome to the Presentation on Specifications Protective devices and Maintenance Operation & Maintenance of Distribution Transformers, Prevention of Failures.
GOVERNMENT ENNGINEERING COLLEGE , BHUJ
A presentation on Measurement of Winding Resistance and Insulation Resistance of 3 Phase 11 kV/ 433 V, 16KVA Oil cooled type Transformer PRESENTED BY:
Basics of electrical engineering
ELE 2103 Dept . of E & E, MIT Manipal
Electrical Machine-I EE 2107 Dr. Md. Sherajul Islam
المحولات Transformers
Lesson 11: Transformer Name Plate Data and Connections
TRANSFORMER.
Electrical components and systems
Biosco: MV/LV prefabricated substations IEC Presentation of the standard Safety is a choice.
Presentation transcript:

TESTING, MAINTENANCE & PROTECTION OF DISTRIBUTION TRANSFORMERS Presented by PRASHANT P. NANKAR TRANS-DELTA ELECTRICALS

WHAT IS A TRANSFORMER? TRANSFORMER IS A STATIC DEVICE WHICH TRANSFORMS A.C. ELECTRICAL POWER FROM ONE VOLTAGE TO ANOTHER VOLTAGE KEEPING THE FREQUENCY SAME BY ELECTROMAGNETIC INDUCTION.

TYPES OF TRANSFORMER BY APPLICATION 1. DISTRIBUTION TRANSFORMER 2.POWER TRANSFORMER 3.CURRENT TRANSFORMER 4.POTENTIAL TRANSFORMER 5.FURNACE TRANSFORMER 6.BOOSTER TRANSFORMER 7.RECTIFIER TRANSFORMER 8.LOCOMOTIVE TRANSFORMER 9.MINING TRANSFORMER 10.PHASE SHIFTING TRANSFORMER 11.WELDING TRANSFORMER 12.HIGH VOLTAGE TESTING/SC TESTING TRF. 13.GROUNDING TRANSFORMERS 14.CONVERTER TRANSFORMER

DISTRIBUTION TRANSFORMER TRANSFORMER WHICH IS USED FOR THE PURPOSE OF DISTRIBUTION OF POWER. 11KV/433V is the standard voltage rating. STANDARD KVA ratings are 25,63,100,160,200,250,315,400,500,630,750 , 1000 , 1250,1500,2000,2500 KVA. IS-2026 is the NATIONAL I S STANDARD.

MAIN FEATURES OUTDOOR,OIL COOLED, 3 PHASE,50HZ PRIMARY IS DELTA CONNECTED AND SECONDARY IS STAR CONNECTED. NATURALY COOLED (ONAN TYPE). AMONGST ALL THE TYPES OF TRANSFORMERS THIS IS THE MOST REQUIRED AND MOST USED TYPE.

PARTS OF TRANSFORMER MAIN TANK RADIATORS CONSERVATOR EXPLOSION VENT LIFTING LUGS AIR RELEASE PLUG OIL LEVEL INDICATOR TAP CHANGER WHEELS HV/LV BUSHINGS FILTER VALVES OIL FILLING PLUG DRAIN PLUG CABLE BOX

TESTING OF TRANSFORMER TESTING IS CARRIED OUT AS PER IS-2026. ROUTINE , TYPE TESTS & SPECIAL TESTS ROUTINE TESTS ( TO BE CARRIED OUT ON EACH JOB) 1.Measurement of winding resistance 2.Measurement of insulation resistance 3.Seperate source voltage withstand test (High Voltage tests on HV & LV) 4.Induced Over voltage Withstand test (DVDF test) 5.Measurement of voltage ratio 6.Measurement of NO LOAD LOSS & current. 7.Measurement of LOAD LOSS & IMPEDENCE.(EFFICIENCY & REGULATION) 8.Vector Group Verification 9.Oil BDV test. 10.Tests on OLTC (if Attached)

TYPE TESTS THESE TESTS ARE CARRIED OUT ONLY ON ONE TRANSFORMER OF THE LOT. All routine tests Additionally following tests are included in type tests Lightening Impulse test. Temperature rise test

SPECIAL TESTS Additional Impulse test Short circuit test Measurement of zero Phase sequence Impedance test. Measurement of acoustic noise level. Measurement of harmonics of the no load current. Magnetic balance test.

ROUTINE TESTS 1.Measurement of winding resistance This test measures the resistance of the HV & LV winding. The values of resistance should be balance for all three phases and should match the designed values. Equipment used : Digital resistance meter.

ROUTINE TESTS 2.Measurement of insulation resistance Measures the insulation resistance of HV & LV windings with respect to earth (body) and between LV & HV winding. INSULATION TESTER OR MEGGER IS USED. Recommended Values are 2000Mohms for HV & 500 Mohms for LV.

ROUTINE TESTS 3.Seperate source voltage withstand test (High Voltage tests on HV & LV)- This test checks the insulation property between Primary to earth, Secondary to earth and between Primary & Secondary. HV high voltage test : LV winding connected together and earthed. HV winding connected together and given 28 KV ( for 11KV transformer) for 1 minute. LV high Voltage test : HV winding connected together and earthed. LV winding connected together and given 3 KV for 1 minute. Equipment used : High Voltage tester ( 100KV & 3KV)

ROUTINE TESTS 4.Induced Over voltage Withstand test (DVDF test)- This test checks the inter turn insulation. For a 11KV/433V transformer,866 Volts are applied at the 433V winding with the help of a Generator for 1 minute. This induces 22KV on 11KV side. The frequency of the 866V supply is also increased to 100HZ. Equipment used : MOTOR GENERATOR SET

ROUTINE TESTS 5.Measurement of voltage ratio This test measures the voltage ratio as per the customer’s requirement. V1/V2 = N1/N2 The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is measured with the help of a turns ratio meter. If it is correct , then the voltage ratio is assumed to be correct. Equipment used : Turns Ratiometer

ROUTINE TESTS 6.Measurement of NO LOAD LOSS & current. The iron losses and no load current are measured in this test. The 433V winding is charged at 433V supply & the 11KV winding is left open .The power consumed by the transformer at no load is the no load loss in the transformer. Effect of actual frequency must be taken into account. Equipment used : Wattmeters or power analyser.

ROUTINE TESTS 7.Measurement of LOAD LOSS & IMPEDENCE.(EFFICIENCY & REGULATION) This test measures the power consumed by the transformer when the 433V winding is short circuited and The rated current is passed through the 11KV winding. Equipment used : Wattmeters or power analyser.

ROUTINE TESTS 8.Vector Group Verification test This test verifies the Dyn-11 vector group of a distribution transformer. Equipment used : voltmeter.

ROUTINE TESTS Oil BDV TEST. Oil breakdown voltage is checked as per IS-335. 100 mm L X 70 mm B X 80 mm Ht. glass pot. 500ml Oil sample. Spherical electrodes with gap of 2.5 mm Recommended value : 60KV Equipment used : OIL BDV TEST SET.

TYPE TESTS LIGHTENING IMPULSE TEST All the dielectric tests check the insulation level of the job. Impulse generator is used to produce the specified voltage impulse wave of 1.2/50 micro seconds wave One impulse of a reduced voltage between 50 to 75% of the full test voltage and subsequent three impulses at full voltage. For a three phase transformer, impulse is carried out on all three phases in succession. The voltage is applied on each of the line terminal in succession, keeping the other terminals earthed. The current and voltage wave shapes are recorded on the oscilloscope and any distortion in the wave shape is the criteria for failure.

SPECIAL TEST Short circuit withstand ability test. This tests measures the ability of the transformer to withstand the mechanical and thermal stresses caused by the external short circuit. HV terminals are connected to the supply bus of the testing plant. The LV is short circuited. The testing plant parameters are such adjusted to give the rated short circuit current. Supply is made on and closed after specified duration of short circuit. The record of current wave form is noted. There should not be any mechanical distortion, fire to the transformer during this test. Similarly no wave form distortion. The transformer should also withstand the routine tests after the short circuit test. The reactance of the winding measured before and after the S.C. test should not vary beyond the limits stated in the IS2026.

MAINTENANCE OF TRANSFORMER Transformer is the heart of any power system. Hence preventive maintenance is always cost effective and time saving. Any failure to the transformer can extremely affect the whole functioning of the organization.

MAINTENANCE PROCEDURE OIL : Oil level checking. Leakages to be attended. Oil BDV & acidity checking at regular intervals. If acidity is between 0.5 to 1mg KOH, oil should be kept under observation. BDV, Color and smell of oil are indicative.

MAINTENANCE PROCEDURE Sludge, dust, dirt ,moisture can be removed by filtration. Oil when topped up shall be of the same make. It may lead to sludge formation and acidic contents. Insulation resistance of the transformer should be checked once in 6 months. Megger values along with oil values indicate the condition of transformer. Periodic Dissolved Gas Analysis can be carried out.

MAINTENANCE BUSHINGS Bushings should be cleaned and inspected for any cracks. Dust & dirt deposition, Salt or chemical deposition, cement or acid fumes depositions should be carefully noted and rectified.

MAINTENANCE Periodic checking of any loose connections of the terminations of HV & LV side. Breather examination. Dehydration of Silica gel if necessary. Explosion vent diaphragm examination. Conservator to be cleaned from inside after every three years. Regular inspection of OIL & WINDING TEMPERATURE METER readings. Cleanliness in the Substation yard with all nets, vines, shrubs removed.

PROTECTION OF TRANSFORMERS The best way of protecting a transformer is to have good preventive maintenance schedule. Oil Temperature Indicators. Winding Temperature indicators. Buchholz Relay. Magnetic Oil level Gauge. Explosion Vent.

PROTECTION OF TRANSFORMERS HT fuse & D.O. fuse. LT circuit breaker. HT Circuit breaker with Over load, Earth Fault relay tripping. Oil Surge Relay for OLTC. PRV for OLTC. HORN GAPS & Lightening Arrestor. Breather.

FAILURES & CAUSES Insufficient Oil level. Seepage of water in oil. Prolonged Over loading. Single Phase loading. Unbalanced loading. Faulty Termination (Improper sized lugs etc) Power Theft. Prolonged Short Circuit. Faulty operation of tap changer switch. Lack of installation checks.

FAILURES & CAUSES Faulty design Poor Workmanship Improper formation of core. Improper core bolt insulation. Burr to the lamination blades Improper brazing of joints. Burr /sharp edges to the winding conductor. Incomplete drying. Bad insulation covering. Insufficient cooling ducts in the winding.

FAILURES & CAUSES Bad Quality of raw material. Transit damaged transformers. After failure , transformer is removed and replaced with new/repaired one without removing the cause of failure which results in immediate or short time failure.