FAULT ANALYSIS - BALANCED FAULT

Slides:



Advertisements
Similar presentations
1 POWER QUALITY -- Bhanu Bhushan -- June, How close is the supply voltage waveform to sinusoidal, and how close are the supply voltage and frequency.
Advertisements

Chapter 12 Transformers. Chapter 12 Transformers.
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
SYMMETRICAL COMPONENETS OF POWER SYSTEM
During fault behavior of circuit breaker
GENERATOR PROTECTION.
EE 369 POWER SYSTEM ANALYSIS
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Disconnect Switches There are many purposes for disconnect switches in substations and power lines. They are used to isolate or deenergize equipment for.
DET 310 UNDERGROUND CABLES
Symmetrical Faults Instructor: MOHAMMAD ABDUL BASEER
Electrical Power Systems
7.1.3 Student Book © 2005 Propane Education & Research CouncilPage Applying a Systems Approach to Gas Appliance Troubleshooting Troubleshooting.
POWER SYSTEM PROTECTION
What makes substation work?
Lecture 18 Markets, Fault Analysis Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
1 POWER QUALITY -- Bhanu Bhushan -- April, Simple examples around us : Ceiling fan regulators Tube lights Lap-tops & peripherals Domestic inverters.
Lecture 18 Fault Analysis Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
1 Power Quality EKT 451 CHAPTER 8. 2 Introduction Utilities transmit electricity over power lines into home as an alternating current (AC) wave. This.
Protection & Switchgear
What is POWERGRID??? The Power Grid Corporation of India Limited (POWERGRID), is an Indian state-owned electric utilities company headquartered in Gurgaon,
Introduction to switchgears
Introduction  Utilities transmit electricity over power lines into home as an alternating current (AC) wave.  This is how power travels through wiring.
POWER SYSTEM PROTECTION AND SWITCHGEARS
Submitted to: Submitted by:
A SEMINAR ON 400 KV GSS(RRVPNL) BIKANER.
What makes substation work?
Presentation Topic: Circuit Breakers Represented to: Dr. M. Riaz Khan Represented by: M. Mujahid.
EE 2353 HIGH VOLTAGE ENGINEERING
SYNERGY INSTITUTE OF ENGINEERING AND TECHNOLOGY
  The traditional molded-case circuit breaker uses electromechanical (thermal magnetic) trip units that may be fixed or interchangeable.  An MCCB provides.
STUDY OF ELEMENTS OF A 220/132/33KV SUBSTATION
III ALTERNATING CURRENT Electricity is generated, transmitted, and used in the form of three-phase alternating current (AC). The current strength of AC.
BY: VISHU KUMAR 1HK08EE055 Internal Guide: WASEEM KHANUM.
Chapter 3 Basic Electrical Circuits Chapter 3 Basic Electrical Circuits.
Unit 3 Lesson 3 Electric Circuits
Protection and Relay Schemes
High Voltage Engineering
Sub Station.
ECE 476 Power System Analysis
Chapter # 25 Sub-Stations risemark.pbworks.com.
Grounding And Safety Techniques Ms. Tahoora Qureshi, Asst. Professor
WELCOME TO ALL.
Principles & Applications Residential Wiring Concepts
Basics of electrical engineering
ELECTRICAL POWER SYSTEM – II. ACTIVE LEARNING ASSIGNMENT: SYMMETRICAL THREE PHASE FAULTS. PREPARED BY : JOBIN ABRAHAM.
Synchronous Condensers Transient & First Swing Periods
Circuit Breakers & Reclosers
Passive Shunt Compensation
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
POWER SYSTEM ANALYSIS INTRODUCTION.
Chapter 7 System Protection
OBJECTIVES After studying Chapter 4, the reader should be able to:
High Voltage Power Circuit Breakers
Protective Relaying Conference
Components of Substation
Unit 3 Lesson 3 Electric Circuits
UNIT II APPARATUS PROTECTION.
ELECTRICAL POWER-II Electrical engineering sixth semester
POWER SYSTEM ANALYSIS EET308/3 EET308 POWER SYSTEM ANALYSIS.
Overcurrent Protection— Fuses and Circuit Breakers
Agenda Introduction of Protective Relays
EET 323 – Electrical System Design Lecture 9: Grounding
Protection against over voltages
A. Touching both terminals with the hands can cause electrical shock
0 Air Blast Circuit Breaker under the guidance of:- Presented By:- Mr. B.R.Reddy Anuj Kumar Pandey EN-3 rd year Roll No Unrestricted.
Prepared by: Ismael K. Saeed
Substation Equipment's
Exercise 6 Power systems.
Presentation transcript:

FAULT ANALYSIS - BALANCED FAULT UNIT - 3 FAULT ANALYSIS - BALANCED FAULT

BALANCED FAULT Importance of Short circuit Analysis Assumptions in fault analysis Analysing fault using Thevenin’s theorem Z-bus building algorithm Fault analysis using Z-bus Computations of short circuit capacity, post fault voltage and currents.

Introduction for Symmetrical Fault analysis A fault current that occurs in any normal circuit will tends to change the circuit to abnormal state. For example, a short circuit is a fault in which high current bypasses the normal load. An open-circuit fault occurs if a circuit is interrupted by some failure.

Fault usually occurs in a power system due to Insulation failure of equipment. Flashover of lines initiated by a lighting stoke. Permanent damage of conductors and tower or accidental faulty operation. Wires blowing together in the wind. Animals or plants coming in contact with the wires Salt spray or pollution on insulators.

Causes of short-circuit “Whenever a fault occurs on a network such that a large current flows in one or more phases, a short circuit is said to have occurred”. Causes of short-circuit (i) Internal effects are caused by breakdown of equipment or transmission lines, from weakening of insulation in a generator, transformer etc. Such troubles may be due to ageing of insulation, inadequate design or improper installation. (ii) External effects causing short circuit include insulation failure due to lightning surges, overloading of equipment causing excessive heating; mechanical damage by public etc.

Effects of short-circuit When a short-circuit occurs, the current in the system increases to an abnormally high value while the system voltage decreases to a low value. Short-circuit causes excessive heating which may result in fire or explosion. Sometimes short-circuit takes the form of an arc and causes considerable damage to the system. Low voltage created by the fault has a very harmful effect on the service rendered by the power system. If the voltage remains low for even a few seconds, the consumers’ motors may be shut down and generators on the power system may become unstable.

Types of fault Series fault (or) open circuit i. One open conductor fault ii. Two open conductor fault Shunt fault (or) short-circuit fault Symmetrical fault (or) balanced fault ----Three-Phase fault Unsymmetrical fault (or) Unbalanced fault i. Line-to-ground (L-G) fault ii. Line-to-line (L-L) fault iii. Double line-to-ground (L-L-G) fault.

Symmetrical fault

Application of Thevenin’s Theorem: Fault current evaluation. Bus Voltage & Line current during the fault can be determined. Post fault voltage & current can be obtained using pre-fault voltages & current.

Circuit Breaker CB is protective device which is used to isolate the faulty part of the system from healthy part. It also act as switch under normal conditions.

CB ratings required for computation of SC current : Rated momentary current & Rated symmetrical interrupting current. Symmetrical SC current is obtained by using Sub-transient reactance of (Xd”) for synchronous machines. Momentary current (rms) is then calculated by multiplying the symmetrical momentary current by a factor of 1.6 to account for the presence of dc offset current.

CB for Particular application is selected on the basis of: Normal working power level specified as rated interrupting current or rated interrupted KVA. The fault level specified as either the rated SC interrupting current or rated SC interrupting MVA. Momentary current rating. Normal working voltage. Speed of the CB.

The symmetrical current to be interrupted is calculated by using Xd” for Syn. Generator & Xd’ for Syn. Motor. Dc offset value is added to obtain the current which is interrupted is accounted by multiplying the Symme SC current by a suitable factors given below. Speed of CB Multiplying factor 8 Cycle or more 1.0 5 cycles 1.1 3 cycles 1.2 2 cycles 1.4 1 cycles 1.5