Presentation is loading. Please wait.

Presentation is loading. Please wait.

DET 310 UNDERGROUND CABLES

Similar presentations


Presentation on theme: "DET 310 UNDERGROUND CABLES"— Presentation transcript:

1 DET 310 UNDERGROUND CABLES
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE DET 310 CHAPTER 7 UNDERGROUND CABLES

2 7.0 INTRODUCTION A considerable amount of transmission and distribution of electrical energy, especially in densely populated urban areas is carried out by means of underground cable. The underground cable are rugged in construction and provide greater service reliability, increased safety, better appearance and trouble free service under a variety of environmental conditions.

3 7.1 Applications Of Underground Cables
Underground cables are necessary for supply connection in the electrical plants, in generating stations, transmission system and distribution systems, utilization plants and so on. List of example of underground cable application for connecting one apparatus with the others for the following: - Supply power to the individual machine apparatus in electrical plants - Connection between switchgear and individual load, group load - Connection between auxiliary transformer and switchgear - Subtransmission line between receiving substation and distribution substation

4 7.2 Underground Distribution System Vs Overhead Line
Safety Reliability of supply Interference / Disturbance Maintenance Environment impact Economics

5 mechanical damage, chemical reaction, moisture an so on.
7.3 Cable Constructions A cable consists of three main components:- Conductor Insulation Sheath External protection is provided by the sheath against mechanical damage, chemical reaction, moisture an so on.

6 7.3 Cable Constructions Conductor
6 Conductor An element design to transmit electricity A single core has one conductor while a three-core has 3 conductors. A cable may be has single core, 3 core or multiple conductor ETE503 Underground Cable 4/19/2017

7 7.3 Cable Constructions Insulation
Is a material that reduces or prevents the transmission of electricity Each conductor is covered by insulation Insulation is phase to ground and phase to phase XLPE PAPER ETE503 Underground Cable 4/19/2017

8 7.4 Cable Constructions Sheath Cable protective covering
8 Sheath Cable protective covering Metallic or nonmetallic protective covering over the conductor / insulation / shield External protection is provided by the sheath against mechanical damage, chemical reaction, moisture an so on. ETE503 Underground Cable 4/19/2017

9 7.5 Types of Underground Cables
9 The identification of the cable are based on the several items : Insulation Voltage System Cable Sizing And Core Technical Specification Characteristics Of The Cable ETE503 Underground Cable 4/19/2017 ETE503 Underground Cable 9

10 7.5 Types of Underground Cables
10 Usually the operating voltage decides the types of insulation and cable placed in various categories depending upon the voltage for which they are designed. Low Voltage Cable (LV)  11kV High Voltage Cable (HV)  11 kV ETE503 Underground Cable 4/19/2017 ETE503 Underground Cable 10

11 7.6 High Voltage Cable Categories
11 Paper Insulation 3 core belted 11kV PILC cable Single core screened 11 kV PILC cable Polymer Insulation 3 core XLPE 11 kV cable Single core XLPE 11 kV cable ETE503 Underground Cable 4/19/2017 ETE503 Underground Cable 11

12 7.7 High Voltage Cable Categories
12 A = Conductor (Aluminum) B = Strand Screen (carbon black paper ) C = Insulation (Paper) D = Insulation Screen (carbon black paper) E = Sheath (copper lead) F = Jacket Example of Single core screened 11 kV PILC cable ETE503 Underground Cable 4/19/2017

13 7.7 High Voltage Cable Categories
13 A = Conductor (Aluminum) B = Strand Screen (extruded semiconducting) C = Insulation (XLPE) D = Insulation Screen E = Shield (copper tape) F = Jacket Example of Single core XLPE 11 kV cable ETE503 Underground Cable 4/19/2017

14 7.8 Why XLPE Cable ? Excellent Electrical & Physical Properties
14 Excellent Electrical & Physical Properties Capable Of Carrying Large Current At High Temperature Normal ~ 90oc Emergency ~ 130oc Short Circuit Conditions ~250oc Easy To Install – XLPE Easier To Joint No Need For Metallic Sheath ETE503 Underground Cable 4/19/2017 ETE503 Underground Cable 14

15 7.9 Cable Accessories 15 A cable network must be capable of supplying electric power without interruption. If a failure does occur, it is usually the junction points on the network that are at fault, rarely the cable. So it pays to choose cable accessories with care. ETE503 Underground Cable 4/19/2017

16 7.9 Cable Accessories 16 Cable accessories can be divided into 3 major categories:- Joint/Splice Termination Connector Joint/Splice Termination Connector ETE503 Underground Cable 4/19/2017

17 7.10 Examples of Cable Joint/Splice
17 Examples Of LV/MV/HV Cable Joint:- 1.LV Heat Shrink Joint 2.LV Heat Shrink (Branch Joint) 3.MV Heat Shrink Joint 4.MV Heat Shrink Joint (Transition Joint Paper To Polymeric) 5. HV Heat Shrink Joint Up To 72KV 6.HV Heat Shrink Joint Up To 170kv 1 2 3 4 5 6 ETE503 Underground Cable 4/19/2017 ETE503 Underground Cable 17

18 7.10 Cable Accessories –Termination
18 Cable termination is one of the important components in the electrical power system. A failure of it can cause a long interruption, costly repair and loss of revenue. A cable termination is a way of preparing the end of a cable to provide adequate electrical and mechanical properties. ETE503 Underground Cable 4/19/2017

19 7.11 Examples of Cable Connector
19 Examples Of LV/MV/HV Cable Connector:- 1. MV Heat Shrink Straight Bushing Boot 2.MV Heat Shrink Right Angle Bushing Boot 3.MV Push On connector with surge arrestor 4.MV Push On Connector separable 3 Core 5. MV Push On Connector 1 Core 6.MV Push On Straight Bushing Boot 1 2 3 4 5 6 ETE503 Underground Cable 4/19/2017 ETE503 Underground Cable 19

20 7.12.0 (CABLE FAULT) INTRODUCTION

21 7.12.1 CAUSES OF CABLE FAULT (CONTINUE)
􀂃 Cable faults are undesirable causes because:- Power supply is interrupted 2. Locating fault in a long underground cable is difficult and time consuming 3. Repairing faulty cable is difficult and time consuming, aging is a natural process 􀂃 Cable insulation gets deterioration with time. 􀂃 Preventive Maintenance, periodic monitoring is necessary to prevent failure.

22 MECHANICAL

23 7.12.2 CAUSES OF UNDERGROUND CABLE FAILURE
Major factors that cause failure of a cable are:- Damaged accidentally by external mechanical means Damage caused as a results of mishandling the cable during layout. Poor workmanship in cable jointing. Natural causes due to aging of cable. Damaged caused by movement of soil and erosion

24 MISHANDLING Mishandling of cable may be occurred during installation Some of the examples are: Excessive pull Sharp bend. Accident crush.

25 7.12.2.3 Poor workmanship During Cable Jointing
The cable are jointed together with poor workmanship can lead to cable fault after a period of time.

26 7.12.2.4 NATURAL CAUSES DUE TO AGING OF CABLE

27 CONTINUE-

28 CONTINUE-

29 CONTINUE-

30 CONTINUE-

31 CONTINUE-

32 7.13 TYPES OF CABLE FAULT GENERAL: Series (open circuit) Fault - Failure of continuity (conductor (s) or cable) Shunt (short circuit) fault - failure of insulation

33 7.13 TYPES OF FAULT (CONTINUE)-

34 7.13 TYPES OF FAULT (CONTINUE)-

35 SERIES AND SHUNT FAULT Are subsided into the following categories: Low Resistance Fault Where Zo= cable surge impedance =10 – 100 ohm Usually happens in series fault. High Resistance Fault Where

36 7.13.2 INTERMITTENT OR FLASH FAULT
Usually not apparent to insulation resistance measuring instrument. Does not manifest itself at lower voltages or a surge Breakdown will appear under application of high voltage dc or DC pressure test.

37 7.14 FAULT LOCATION PROCEDURE
The proper sequence of cable fault location are as follows: Analysis of fault Pre-location Pin Pointing Confirmation and re-test

38 7.14 FAULT LOCATION PROCEDURE (cont-)

39 7.14 FAULT LOCATION PROCEDURE (cont-)

40 7.14 FAULT LOCATION PROCEDURE (cont-)

41 7.14 FAULT LOCATION PROCEDURE (cont-)

42 7.14 FAULT LOCATION PROCEDURE (cont-)

43 7.14 FAULT LOCATION PROCEDURE (cont-)

44 7.14 FAULT LOCATION PROCEDURE (cont-)
Continuity Test - With the cable conductor shorted or looped at the remote end, perform continuity test on the cable. - Measure and record the results in ohm. - Three measurements are to be carried out between R-Y, Y-B, B-R. - The test will determine whether any of cable is open circuited. - The resistance per-conductor per km is provided in Table VI, VII, VIII and IX (refer appendix A)

45 7.14 FAULT LOCATION PROCEDURE (cont-)
if the continuity of the cable is sound, insulation resistance from one end are sufficient. If continuity is broken, IR test should be carried out at both ends of the cable BURNING A FAULT The continuity and IR test may indicate that burning of fault by means of HT pressure test set is required. -

46 7.14.1 BURNING A FAULT (continue-)
Burning a fault is achieve by passing current from a DC HT test set through the fault. Other conductors not under test should be earthed. HT is applied for about 5 to 10 minutes to burn the fault. HT test is used to determine which fault location equipment is suitable to be used. HT is the last resort often used because it sometimes produce ambiguous and unpredictable results. Therefore, fault location equipment should be attempted first.


Download ppt "DET 310 UNDERGROUND CABLES"

Similar presentations


Ads by Google