Presentation is loading. Please wait.

Presentation is loading. Please wait.

Presentation Topic: Circuit Breakers Represented to: Dr. M. Riaz Khan Represented by: M. Mujahid.

Similar presentations


Presentation on theme: "Presentation Topic: Circuit Breakers Represented to: Dr. M. Riaz Khan Represented by: M. Mujahid."— Presentation transcript:

1 Presentation Topic: Circuit Breakers Represented to: Dr. M. Riaz Khan Represented by: M. Mujahid

2 Table of Contents  Introduction  Circuit Breaker  Operating Principle  Types of Circuit Breakers  Queries

3

4 Circuit Breaker Is an electrical switch that is designed to break or protect an Electrical circuit from damage, cause by several factors, such as:  Electricity Overload  Short Circuit

5

6 Operating Principle  Two contacts called electrode remains closed under normal operating conditions. When fault occurs on any part of the system, the trip coil of the circuit breaker get energized and contacts are separated.

7

8 Types of circuit Breakers  1.Low-voltage circuit breakers  2.Medium-voltage circuit breakers  6.High-voltage circuit breakers

9 Low Voltage Circuit Breakers (MCB)  Low-voltage (less than 1,000 V AC ) types are common in domestic, commercial and industrial application and include  Miniature circuit breaker (MCB)—rated current not more than 100 A. Trip characteristics normally not adjustable. Thermal or thermal- magnetic operation. Breakers illustrated above are in this category.

10 Magnetic Circuit Breakers  Magnetic circuit breakers use a solenoid (electromagnet) whose pulling force increases with the current.  The circuit breaker contacts are held closed by a latch. As the current in the solenoid increases beyond the rating of the circuit breaker, the solenoid's pull releases the latch, which lets the contacts open by spring action

11 Common Trip Breakers  When supplying a branch circuit with more than one live conductor, each live conductor must be protected by a breaker pole. To ensure that all live conductors are interrupted when any pole trips, a "common trip" breaker must be used. Common trip breakers must used when neutral wire switching is needed  These may either contain two or three tripping mechanisms within one case, or for small breakers, may externally tie the poles together via their operating handles.

12 Earth Leakage Circuit Breakers  CT are used to detect the fault current and cut off the supply in condition of Hazard.  This detects current in the earth wire directly rather than detecting Hazard.  They are no longer seen in new installations as they can not detect any dangerous condition where the current is returning to earth by another route - such as via a person on the ground or via plumbing.

13 Medium Voltage Circuit Breakers  Medium-voltage circuit breakers rated between 1 and 72 kV may be assembled into metal-enclosed switchgear line ups for indoor use, or may be individual components installed outdoors in a substation. 1.Air Break Circuit Breaker 2.Oil-filled Circuit Breaker 3.Vacuum Circuit Breaker  These are also operated by current sensing protective Relays operated through current transformers.

14

15  Air circuit breakers Rated current up to 6,300 A and higher for generator circuit breakers. Trip characteristics are often fully adjustable including configurable trip thresholds and delays. Usually electronically controlled, though some models are microprocessor controlled via an integral electronic trip unit.  Vacuum circuit breakers With rated current up to 6,300 A, and higher for generator circuit breakers. These are generally applied for voltages up to about 40,500 V. It tend to have longer life expectancies between overhaul than do air circuit breakers.

16 High Voltage Circuit Breakers  Electrical Power Transmission networks are protected and controlled by high-voltage breakers. The definition of high voltage varies but in power transmission work is usually thought to be 72.5 kV or higher  High-voltage breakers are nearly always solenoid-operated, with current sensing protective relays operated through current transformers  In substations the protective relay scheme can be complex, protecting equipment and buses from various types of overload or ground/earth fault. High-voltage breakers are broadly classified by: 1.Oil-filled2.Air blast Vacuum 3.SF 6 4.CO 2

17  Due to environmental and cost concerns over insulating oil spills, most new breakers use SF 6 gas to quench the arc.  High-voltage AC circuit breakers are routinely available with ratings up to 765 kV. 1,200 kV breakers were launched by Siemens.  High-voltage(HVAC) circuit breakers used on transmission systems may be arranged to allow a single pole of a three-phase line to trip, instead of tripping all three poles; for some classes of faults this improves the system stability and availability. SF 6 CB

18 Any Question??

19 Thank You


Download ppt "Presentation Topic: Circuit Breakers Represented to: Dr. M. Riaz Khan Represented by: M. Mujahid."

Similar presentations


Ads by Google