NFPA 70E: Standard for Electrical Safety in the Workplace

Slides:



Advertisements
Similar presentations
Subcontractor Electrical Safety & NFPA 70E
Advertisements

NFPA 70E® 2012….. What's New and What do I Need to Know?
LIMITED APPROACH BOUNDARY
Murray State University
 ELECTRICAL SAFETY Gerald P. Robinson Jr., P.E. – Hatch Mott MacDonald.
ELECTRICAL SAFETY-RELATED WORK PRACTICES Qualified Persons Those people that have training in avoiding electrical hazards while working on or near exposed.
FHM TRAINING TOOLS This training presentation is part of FHM’s commitment to creating and keeping safe workplaces. Be sure to check out all the training.
San Bernard Electric Cooperative, Inc. Arc Flash Assessment.
Practice Statement The effective use of Isolate and Insulate equipment and procedures to provide the necessary level of safety when performing Live Line.
When working on or near electricity or electrical equipment you must be trained in & use Electrical Safety Related Work Practices NFPA.
Joe Cobb Crawford, P.E.,C.E.M. Crawford Engineering Services
ARC FLASH ANALYSIS.
Slide 1 UNCLASSIFIED Breaker Operation Arc Flash Breakout Group EFCOG Electrical Safety Workshop – July 18, 2014.
Arc Flash Energy & Protection Presented by EWB Engineering (Electrical Engineers)
Electrical Safety Training
Significant Changes to NFPA 70E
THE INTERNATIONAL SOCIETY OF FIRE SERVICE INSTRUCTORS Electronic INSTRUCT-O-GRAM Program Lockout / Tagout Policy.
Utilizing Only Qualified Persons for Electrical Work can Reduce Risk Presented by: Dennis K. Neitzel, CPE Director Emeritus AVO Training Institute, Inc.
INJURY PREVENTION ARC FLASH REGIONAL SAFETY MEETING.
Electric Arc-Flash Injury Reduction Program Herman O. Kemp Electrical Safety Consultant Safety Program Consultants, LLC.
“Standard for Electrical Safety in the Workplace”
 Recognize the scope and structure of the OSHA standards.  Identify the common electrical hazards in long term care settings.  Discuss electrical safety.
Qualified Persons Working On Or Near Energized Equipment
Controlling Hazardous Energy
Occupational Safety and Health Course for Healthcare Professionals.
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE.
W504 - Management of asbestos containing materials.
High Voltage Electrical Safety
Process Safety Management
NFPA Changes 2015.
© Evaluating Electrical Risk Factors Module 3.
NECA & Salisbury Assessment Solutions Partnership.
NFPA 70E - Awareness Training1 NFPA 70E Standard for Electrical Safety in the Workplace Article 130.7(C)(1-7) – Personal Protective Equipment.
NSC Utilities Div. Winter Meeting St. Petersburg Florida 2012 Presenter: Robert E. Lawless 1 NFPA 70E 2012 Update Brief.
NFPA 70E Electrical Safety in the Workplace. Objectives What NFPA 70E covers Understand Arc Flash, Incident Energy, & Flash Protection Boundary Standards,
Electrical Safety and Electrical Safe Work Practices EHS Course #525 Reference EHS Electrical Safety Procedure
MNM Fatal Electrical Accident Electrical Accident October 10, 2010 (Oklahoma) October 10, 2010 (Oklahoma) Granite Operation Granite Operation Contract.
First Draft Language (B) Service Equipment. In addition to the requirements in (A), service equipment shall contain the following information: (1)
Electrical Safety, Subpart K
NFPA 70E Standard for Electrical Safety Requirements for Employee Workplaces Article 130 A Operational Guide for Protection Against Shock and Arc Flash.
Electrical Safety in the Workplace FN000385/CR. FN000385/CR, Electrical Safety in the Workplace 2 Overview NFPA 70E Objectives Electrical Hazards Mitigation.
Working On or Near Energized Conductors and FR Clothing.
Training of Airport Visual Aids Maintenance Personnel “Airport Operator” - Are you Meeting the Requirements? IESALC Denver 2015 Presented by Seward Ford.
Global Marketing © Chevron 2009 Rev. 1 Electrical Safety Awareness Plus.
NFPA 70E Electrical Safety Presentation (updated for 2015)
ELECTRICAL SAFETY TASK GROUP
What is Arc Flash? Electrical arc flash and arc blasts release dangerous levels of heat energy, fire , molten materials, vaporized solids that can be inhaled,
SAF603S Switching of Electrical Equipment 6/23/2017 Revision 3.
Managing Safe Work Permits
OSHA Electric Power Training Rules Qualified vs. Unqualified Employees
The Control of Hazardous Energy (Lockout-Tagout)
Lock Out & Tag Out.
Energy Control (Lockout/Tagout)
Occupational Radiation Protection during High Exposure Operations
The Control of Hazardous Energy (Lockout-Tagout)
Personal Protective Equipment
Environmental Health & Safety Arc Flash Training
OSHA’s Final Rule: Electric Power Generation, Transmission, and Distribution Electrical Protective Equipment Presented to: RESAP Area Administrators Presented.
Electrical Receptacle Testing
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Murray State University
Developing a Comprehensive Electrical Program
Control of Hazardous Energy
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Changes to Part 4 – Work Rules
Arc Flash Fundamentals & Compliance
Parker domnick hunter. Safety of Electrical and
Presentation transcript:

NFPA 70E: Standard for Electrical Safety in the Workplace Overview of Major 2015 Changes

The 2015 Has Arrived! The NFPA 70E was first published in 1979 at the request of OSHA. The 2015 Edition is the tenth to be published. Each edition is made to bring clarification and a safer work environment. The 2015 edition brings in some major changes.

Global Changes 2012 Edition 2015 Edition Harm Injury or Damage to Health Probablility Likelihood Work Shoes Footwear Arc Flash Hazard Analysis Arc Flash Risk Assessment Shock Hazard Analysis Shock Risk Assessment

Global Changes These Global Changes provide accuracy and better harmonize with other standards addressing risk and hazards

Definitions Qualified Person. One who has demonstrated skills and knowledge related to the construc- tion and operation of electrical equipment and installations and has received safety training to identify and avoid the hazards involved. Risk. A combination of the likelihood of occurrence of injury or damage to health and the severity of injury or damage to health that results from a hazard.

Definitions Risk Assessment. An overall process that identifies hazards, estimates the potential severity of injury or damage to health, estimates the likelihood of occurrence of injury or damage to health, and determines if protective measures are required. InformationalNote: As used in this standard, arc flash risk assessment and shock risk assessment are types of risk assessments.

Article 110.1(A) Electrical Safety Program. General. The employer shall implement and document an overall electrical safety program that directs activity appropriate to the risk associated with electrical hazards. The electrical safety program shall be implemented as part of the employer’s overall occupational health and safety management system, when one exists. Informational Note No. 1: Safety-related work practices such as verification of proper maintenance and installation, alerting techniques, auditing requirements, and training requirements provided in this standard are administrative controls and part of an overall electrical safety program.

Article 110.1(B) Electrical Safety Program. Maintenance.The electrical safety program shall include elements that consider condition of maintenance of electrical equipment and systems.

Article 110.2(C)(1) Training Requirements Emergency Response Training Contact Release. Employees exposed to shock hazards shall be trained in methods of safe release of victims from contact with exposed energized electri- cal conductors or circuit parts. Refresher training shall occur annually.

Article 110.2(C)(2) First Aid, Emergency Response, and Resuscitation Training Requirements First Aid, Emergency Response, and Resuscitation (a)  Employees responsible for responding to medical emergencies shall be trained in first aid and emer- gency procedures. (b)  Employees responsible for responding to medical emergencies shall be trained in cardiopulmonary resuscitation (CPR). Refresher training shall occur annually. (c)  Employees responsible for responding to medical emergencies shall be trained in the use of an auto- mated external defibrilator (AED) if an employer’s emergency response plan includes the use of this device. Refresher training shall occur annually. Employers shall verify at least annually that employee training required by this section is current.

Article 130.2(A)(4) This was added in the 2015 Text: Normal Operation: Normal operation of electrical equipment shall be permitted where all of the following conditions are satisfied: The equipment is properly installed. The equipment is properly maintained. The equipment doors are closed and secured. All equipment covers are in place and secured. There is no evidence **This is in accordance with manufacturer and industry codes and standards. Physical damage, arcing, deterioration, and overheating are all signs of impending failure.

Article 130.2(B)(1) Energized Electrical Work Permits When Required: When energized work is permitted in accordance with 130.2(A), and energized electrical work permit shall be required under the following conditions: When work is performed within the restricted approach boundary When the employee interacts with the equipment when conductors or circuit parts are not exposed but an increased likelihood of injury from an exposure to an arc flash hazard exists.

Article 130.2(B)(3) Energized Electrical Work Permits Exemptions to Work Permit: An energized work permit shall not be required if a qualified person is provided with and uses appropriate safe work practices and PPE under any of the following conditions: Testing, troubleshooting,and voltage measuring Thermography and visual inspections if the restricted approach boundary is not crossed Access and egress from an area with energized electrical equipment if no electrical work is performed and the restricted approach boundary is not crossed General housekeeping and miscellaneous non-electrical tasks if the restricted approach boundary is not crossed.

Article 130.4(A) Shock Risk Assessment: A shock risk assessment shall determine the voltage to which personnel will be exposed, the boundary requirements, and the PPE necessary in order to minimize the possibility of electric shock to personnel.

Shock Protection Boundaries Restricted Approach Boundary Prohibited Approach Boundary Limited Approach Boundary

2015 Boundaries Exposed Energized Conductor or Circuit Part Arc Flash Boundary Exposed Energized Conductor or Circuit Part Limited Approach Boundary Limited Space Restricted Approach Boundary Restricted Space 2015 Boundaries

Table 130.4(D)(a) Approach Boundaries for Shock Protection for Alternating Current Systems Nominal System Voltage Range, Phase to Phase Limited Approach Boundary Movement Adder Conductor Part <50V Not specified 50 V – 150 V 3.0 m (10 ft 0 in) 1.0 m (3 ft 6 in) Avoid contact 151 V – 750 V 0.3 m (1 ft 0 in) 751 V – 15 kV 1.5 m (5 ft 0 in) 0.7 m (2 ft 2 in) 15.1 kV – 36 kV 1.8 m (6 ft 0 in) 0.8 m (2 ft 7 in) 36.1 kV – 46 kV 2.5 m (8 ft 0 in) 0.8 m (2 ft 9 in) 46.1 kV – 72.5 kV 1.0 m (3 ft 3 in) 72.6 kV – 121 kV 3.3 m (10 ft 8 in) 1.0 m (3 ft 4 in) 138 kV – 145 kV 3.4 m (11 ft 0 in) 1.2 m (3 ft 10 in) 161 kV – 169 kV 3.6 m (11 ft 8 in) 1.3 m (4 ft 3 in) 230 kV – 242 kV 4.0 m (13 ft 0 in) 1.7 m (5 ft 8 in) 345 kV – 362 kV 4.7 m (15 ft 4 in) 2.8 m (9 ft 2 in) 500 kV – 550 kV 5.8 m (19 ft 0 in) 3.6 m (11 ft 10 in) 765 kV – 800 kV 7.2 m (23 ft 9 in) 4.9 m (15 ft 11 in)

Article 130.5 Arc Flash Risk Assessment: An arc flash risk assessment shall be performed and shall: Determine if an arc flash hazard exists. If an arc flash hazard exists, the risk assessment shall determine: Appropriate safety-related work practices The arc flash boundary The PPE to be used within the arc flash boundary Updated with major modifications and reviewed periodically, at intervals not to exceed 5 yrs. Take into consideration the design of the overcorrect protective device and its opening time, including its condition of maintenance. Informational Note No. 1: Where equipment is not properly installed or maintained, PPE selection based upon incident energy analysis or the PPE category method may not provide adequate protection from arc flash hazards.

Article 130.5(C) Arc Flash PPE: One of the following methods shall be used for the selection of PPE. Either, but not both, methods shall be permitted to be used on the same piece of equipment. The results of an incident energy analysis to specify an arc flash PPE Category in Table 130.7(C)(16) shall not be permitted. Incident Energy Analysis Method. Arc Flash PPE Categories Method.

Hazard Risk Categories HRC #1 4 cal/cm2 Min. HRC #0 (100% Natural Fibers): HRC #2 8 cal/cm2 Min. HRC #3 25 cal/cm2 Min. HRC #4 40 cal/cm2 Min. Hazard Risk Categories PPE Categories PPEC #0 PPEC #1 1.2-4 Cal/cm2 PPEC #2 4.1-8 Cal/cm2 PPEC #3 8.1-25 Cal/cm2 PPEC #4 25.1-40 Cal/cm2

Arc-Rated vs. Flame-Resistant Protective equipment and clothing that is intended for protection from an arcing fault must be rated by the manufacturer for use in an environment influenced by an electrical arc. Although the term flame resistant (FR) has been used in previous editions of NFPA 70E, an FR marking on a garment does not necessarily mean it is arc rated. The term flame resistant is no longer used in NFPA 70E; this change has been made to clarify that only clothing or other PPE with an arc rating is acceptable for protecting persons against arc flash hazards. The term flame resistant could indicate exposure to other events such as flames from a fire. As an example, FR clothing for race car drivers or pilots is not suitable for arc flash protection. Arc-rated clothing is the only clothing marked with the cal/cm2 rating.

Article 130.5(D) Equipment Labeling: Electrical equipment such as switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centers that are in other than dwell- ing units and that are likely to require examination, adjustment, servicing, or maintenance while energized shall be field-marked with a label containing all the following information: Nominal System Voltage Arc Flash Boundary At least one of the following: Available incident energy and the corresponding working distance, or the arc flash PPE category for the equipment, but not both Minimum arc rating of clothing Site-specific level of PPE

Arc Flash and Shock Hazard Appropriate PPE Required Article 130.5(D) WARNING Equipment Bus: PAINT ROOM MCC-1 Lockout Device: MDP-1 3B Date: 1/1/14 Reference Document: IEEE Std 1584 through 1584b-2011 PPE: Reference NFPA 70E-2012 Table 130.7 (C)(16) #2 Nominal System Voltage 480V Arc Flash Boundary 38” Limited Approach Boundary 42” Restricted Approach Boundary 12” Prohibited Approach Boundary 1” Hazard Risk Category @ 18” Arc Flash and Shock Hazard Appropriate PPE Required

Arc Flash and Shock Hazard Appropriate PPE Required Article 130.5(D) WARNING Equipment Bus: PAINT ROOM MCC-1 Lockout Device: MDP-1 3B Date: 1/1/14 Reference Document: IEEE Std 1584 through 1584b-2011 PPE: Reference NFPA 70E-2012 Table 130.7 (C)(16) 6.5 Nominal System Voltage 480V Arc Flash Boundary 38” Limited Approach Boundary 42” Restricted Approach Boundary 12” Prohibited Approach Boundary 1” cal/cm2 @ 18” Arc Flash and Shock Hazard Appropriate PPE Required

Article 130.5(D) The owner of the electrical equipment shall be responsible for the documentation, installation, and maintenance of the field-marked label.

Article 130.7(15)(A)-(B) Alternating Current (ac) Equipment: When selected in lieu of the incident energy analysis of 130.5(B)(1), Table 130.7(C)(15)(A)(a) shall be used to identify when arc flash PPE is required. When arc flash PPE is required, Table 130.7(C)(15)(A)(b) shall be used to determine the arc flash PPE category. The estimated maximum available short-circuit current, maxi- mum fault-clearing times, and minimum working distances for various ac equipment types or classifications are listed in Table 130.7(C)(15)(A)(b). An incident energy analysis shall be required in accordance with 130.5 for the following: Tasks not listed in Table130.7(C)(15)(A)(a) Power systems with greater than the estimated maximum available short-circuit current Power systems with longer than the maximum fault clearing times Tasks with less than the minimum working distance

Table 130.7(C)(15)(A)(a) Arc Flash Hazard Identification for Alternating Current and Direct Current Systems Task Equipment Condition Arc Flash PPE Required Reading a panel meter while operating a meter switch Any No Normal operation of a circuit breaker (CB), switch, contactor, or starter There is no evidence of impending failure There is no evidence of impending failure Yes For dc system: Work on energized electrical conductors and circuit parts, including voltage testing For dc system: Work on energized electrical conductors and circuit parts of series-connected battery cells, including voltage testing

Arc Flash Hazard PPE Categories for Alternating Current Table 130.7(C)(15)(A)(b) Arc Flash Hazard PPE Categories for Alternating Current Equipment Arc Flash PPE Category Arc Flash Boundary Panelboards or other equipment rated 240 V and below
Parameters: Maximum of 25 kA short-circuit current available; maximum of 0.03 sec (2 cycles) fault clearing time; working distance 455 mm (18 in.) 1 19 in. Panelboards or other equipment rated >240 V and up to 600 V
Parameters: Maximum of 25 kA short-circuit current available; maximum of 0.03 sec (2 cycles) fault clearing time; working distance 455 mm (18 in.) 2 3 ft. 600-V class motor control centers (MCCs)
Parameters: Maximum of 65 kA short-circuit current available; maximum of 0.03 sec (2 cycles) fault clearing time; working distance 455 mm (18 in.) 5 ft. 600-V class motor control centers (MCCs)
Parameters: Maximum of 42 kA short-circuit current available; maximum of 0.33 sec (20 cycles) fault clearing time; working distance 455 mm (18 in.) 4 14 ft.

Arc Flash and Shock Hazard Appropriate PPE Required Article 130.5(D) WARNING Equipment Bus: PAINT ROOM MCC-1 Lockout Device: MDP-1 3B Date: 1/1/14 Reference Document: IEEE Std 1584 through 1584b-2011 PPE: Reference NFPA 70E-2012 Table 130.7 (C)(16) #2 Nominal System Voltage 480V Arc Flash Boundary 38” Limited Approach Boundary 42” Restricted Approach Boundary 12” Prohibited Approach Boundary 1” Hazard Risk Category @ 18” Arc Flash and Shock Hazard Appropriate PPE Required

Article 130.7(15)(D)(2) Barricades. Barricades shall be used in conjunction with safety signs where it is necessary to prevent or limit employee access to work areas containing energized conductors or circuit parts. Conductive barricades shall not be used where it might increase the likelihood of exposure to an electrical hazard. Barricades shall be placed no closer than the limited approach boundary given in Table 130.4(D)(a) and Table 130.4(D)(b). Where the arc flash boundary is greater than the limited approach boundary, barricades shall not be placed closer than the arc flash boundary.