SWEEP FREQUENCY RESPONSE ANALYSIS AS A DIANOSTIC TOOL TO DETECT TRANSFORMER MECHANICAL INTEGRITY by:Luwendran Moodley Brian de Klerk ETHEKWINI ELECTRICITY.

Slides:



Advertisements
Similar presentations
RL-RC Circuits & Applications SVES Circuits Theory
Advertisements

1 Series Resonant Converter with Series-Parallel Transformers for High Input Voltage Applications C-H Chien 1,B-R Lin 2,and Y-H Wang 1 1 Institute of Microelectronics,
ENERGY CONVERSION ONE (Course 25741)
1 New high permeability materials for EMI suppression February 2011 February 2011.
Announcements Be reading Chapter 6. HW 3 is due now.
SYNCHRONOUS MACHINES SUBMITTED BY: Ms. APOORVA KANTHWAL
EXPERIMENTAL STUDY AND COMPARATIVE ANALYSIS OF TRANSFORMER HARMONIC BEHAVIOUR UNDER LINEAR AND NONLINEAR LOAD CONDITIONS.
Sweep Frequency Response Analysis (SFRA) and Transformer Diagnostics M5100 Product Series Doble Engineering Knowledge Is Power SM Apparatus Maintenance.
Announcements Be reading Chapter 3
SUBJECT : DC Machine & Transformer
EQUIVALENT CIRCUIT OF TRANSFORMER Lecture No. 5 By: Sajid Hussain Qazi.
1 ECE 3336 Introduction to Circuits & Electronics Set #16 Transformers Fall 2012, TUE&TH 4:00-5:30 pm Dr. Wanda Wosik.
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Problem Solving Part 2 Resonance.
MONITORING AND FAULT DIAGNOSIS OF INDUCTION MOTORS
Transformers Test Friday 3/30/12. Electromagnetic Induction Induction is the process of producing (inducing) a voltage by passing a wire through a magnetic.
Oscillators with LC Feedback Circuits. LC Feedback elements are used for the generation of higher frequencies of oscillation. Because of lower unity gain.
Passive components and circuits
Copyright ©2011 by Pearson Education, Inc. publishing as Pearson [imprint] Introductory Circuit Analysis, 12/e Boylestad Chapter 20 Resonance.
Copyright ©2011 by Pearson Education, Inc. publishing as Pearson [imprint] Introductory Circuit Analysis, 12/e Boylestad Chapter 20 Resonance.
1.6 Real Single-Phase Transformer.
Motor Testing (Motor Only)
POWER SYSTEM PROTECTION
POWER QUALITY.
Connections of a CT and a PT to supply, load and relay.
A PRACTICAL TRAINING SEMINAR ON PLCC
Announcements Please read Chapter 3; start on Chapter 6
Announcements For lectures 9 and 10 please be reading Chapter 3
Transformer Protection Over-current protection in the form of fuses may be the only protection provided to a small 100 kVA, 11 kV/440 V distribution transformer.
Transformer condition assessment with an integrated test van
1 ELECTRICAL TECHNOLOGY EET 103/4 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
1 ELECTRICAL TECHNOLOGY EET 103/4 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
BASIC INSTRUMENTS - oscilloscopes
EFFECTS OF VOLTAGE IMBALANCE ON 3-PHASE INDUCTION MOTORS DESIGN TEAM 3.
PRESENTED BY Gupta.Deepakkumar.R ( ) Condition Monitoring of Transformer (The heart of Power System)
Protection of Power Systems
Parul Institute Of Technology Name Of Subject:-Electrical Machines Name Of Faculty:-(1) Suresh Sahoo (2) Yogendra Tiwari E&C 3 rd Sem. Prepaid By :- Sr.No.NameEnrolment.
Md.Hamidul Haque ID: Prog:BSEEE SEC:E/3 International University of Business Agriculture and Technology (IUBAT )
1 ELECTRICAL TECHNOLOGY ERT 105/3 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
Transformers. Single Phase Transformers Principles of Operation – Single Phase.
Protection and Relay Schemes
TRANSFORMER A transformer is a static device.
CHAPTER 4 SINGLE-PHASE TRANSFORMER
CHAPTER 6 SPECIAL TRANSFORMERS Electrical Machines.
ECE 476 POWER SYSTEM ANALYSIS
WELCOME.
Testing of Transformers
Electric Machine Induction Motor
GUJARAT POWER OF ENGINEERING AND RESEARCH INSTITUTE (104)
Oscillators with LC Feedback Circuits
ELECTRONICS & COMMUNICATION 3-SEM SHANTILAL DHOLIYA ( )
K. J. I. T institute of engineering 3-PHASE TRANSFORMER. PREPARD BY:-
Electrical Machine-I EE 2107 Dr. Md. Sherajul Islam
Alexander Dierks – Alectrix (Pty) Ltd, South Africa
PD Detection on Metal Enclosed Switchgear Panels
Transformers. Transformer An A.C. device used to change high voltage low current A.C. into low voltage high current A.C. and vice-versa without changing.
المحولات Transformers
electronics fundamentals
3-Phase Transformer Construction, Principal, Working, Operation Advantages Over 1-Phase Transformer Introduction Advatages Construction Principal Working.
Energy Conversion and Transport George G. Karady & Keith Holbert
Amateur Extra Q & A Study Pool
OIL DISTRIBUTION TRANSFORMERS OIL DISTRIBUTION TRANSFORMERS Presented By 1 Dr. Eng. Adel Abdel-Twab Farag.
Agenda Introduction of Protective Relays
TRANSFORMER.
Chapter 14.
Chapter-23 Alternating Current (AC) Circuits
Three Phase Transformers
Difference between Earthing & Grounding
Biosco: MV/LV prefabricated substations IEC Presentation of the standard Safety is a choice.
Instruments & Electrical Measurements Lecture 10
Presentation transcript:

SWEEP FREQUENCY RESPONSE ANALYSIS AS A DIANOSTIC TOOL TO DETECT TRANSFORMER MECHANICAL INTEGRITY by:Luwendran Moodley Brian de Klerk ETHEKWINI ELECTRICITY

INTRODUCTION Why assess the mechanical condition of a transformer? To detect core displacement and winding deformation due to: –Large electromagnetic forces from fault current –Winding shrinkage –Transformer transportation and relocation If these faults are not detected they will manifest into a dielectric or thermal faults Which normally results in the loss of the transformer Hence periodic testing is essential ETHEKWINI ELECTRICITY

DETECTION OF WINDING MOVEMENT Prior to SFRA the mechanical integrity of the transformer was assessed with the following methods: winding capacitance; excitation current; and leakage reactance measurements Each of these methods have drawbacks Winding Capacitance: successfully only if reference data is available Ideally measurements must be made on each phase ETHEKWINI ELECTRICITY

DETECTION OF WINDING MOVEMENT Excitation Current: Excitation current is an excellent means of detecting turn-to-turn failure as a result of winding movement if a turn-to-turn failure is absent, winding movements can remain undetected. Leakage Reactance: Per phase leakage reactance measurements generally shows no or little correlation between the phases and nameplate discrepancies from nameplate value of 0,5 % to 3 % can be a reason for concern The range of defect detection is to large for an accurate assessments Hence the move to SFRA ETHEKWINI ELECTRICITY

FUNDAMENTALS OF SFRA Transformers are made up of complex RLC networks Any physical damage results in changes to these RLC networks These changes in the RLC networks is what we are looking for. ETHEKWINI ELECTRICITY

FUNDAMENTALS OF SFRA How does it work? A low voltage signal with varying frequencies are applied to the transformer. The input and output signal is measured. The ratio of the two signal gives the frequency response of the transformer. This ratio is called the transfer function from which the magnitude and phase can be obtained. ETHEKWINI ELECTRICITY

FUNDAMENTALS OF SFRA The RLC network offers different impedance path at different frequencies. The transfer function of each frequency is the measure of the effective impedance of the RLC network. Any geometrical deformation, changes the RLC network, which in turn changes the transfer function at different frequencies. These changes gives an indication of damage within a transformer. ETHEKWINI ELECTRICITY

ANALYSIS OF SWEEP FREQUENCY RESPONSES Measured responses are analyzed for any one of the following key indicators : Starting dB values The expected shape of a star and delta configuration Comparison of responses to fingerprint Comparison of responses to the different phase of the same transformer Comparison of responses to sister transformer Creation of new resonant frequencies and the elimination of existing resonant frequencies ETHEKWINI ELECTRICITY

ANALYSIS OF SWEEP FREQUENCY RESPONSES A guideline for the analysis of SRFA has been in existence for many years 2 kHz scan is sensitive to core deformation, open circuit, shorted turns and residual magnetism. 20 kHz scan is sensitive to mainly bulk winding movement and clamping structure 200 kHz scan is sensitive to deformation within the main and tap winding 2 MHz scan is sensitive to movement of main and tap winding leads Different frequency bands have different sensitivities to different mechanical failure modes ETHEKWINI ELECTRICITY

ANALYSIS OF SWEEP FREQUENCY RESPONSES At low frequencies – inductive – magnetic circuit Significant difference in the responses between the outer two phases and the center phase ETHEKWINI ELECTRICITY

ANALYSIS OF SWEEP FREQUENCY RESPONSES At high frequencies – complex with a large number of resonant points - dominated by the winding inductance At highest frequencies - capacitive ETHEKWINI ELECTRICITY

TYPICAL RESPONSES Typical response of a healthy transformer –Starting dB value is what we would expect –The shape is consistent with a star configuration –All phase lineup with each other ETHEKWINI ELECTRICITY

TYPICAL RESPONSES Typical response of a transformer with huge problems –Starting dB value of the white phase is unexpected –The shape is not consistent with a star configuration –Phase do not lineup with each other –Clear frequency shift with the formation of new resonant point ETHEKWINI ELECTRICITY

ETHEKWINI’S CONDITION ASSESSMENT Our approach to condition assessment on transformers: –Monthly visual inspection –Oil analysis Oil screen DGA Furan analysis Tan δ of oil at 90ºC –Electrical tests Tan δ and capacitance measurements on windings and bushings 10 kV ratio measurements Excitation current measurements Leakage reactance measurements Sweep Frequency Response Analysis (SFRA) Insulation resistance measurements –Infrared scanning ETHEKWINI ELECTRICITY

SWEEP FREQUENCY RESPONSE ANALYSIS (SFRA) SFRA was introduced three years ago in eThekwini Since its introduction SFRA has proven to be a reliable and sensitive means of detecting winding movement SFRA measurements are performed under the following conditions: On all new transformers for fingerprinting purposes After relocation After long duration short circuits After any type of maintenance ETHEKWINI ELECTRICITY

SWEEP FREQUENCY RESPONSE ANALYSIS (SFRA) SFRA measurements are performed on the highest, lowest and nominal tap position An additional measurement is made on the faulted tap position Short circuit tests on HV and LV windings These short circuit tests acts as an indication and does not identify the area of concern ETHEKWINI ELECTRICITY

CASE STUDIES Four case studies will be presented on real defects Case studies will focus on problems in the low frequency range. ETHEKWINI ELECTRICITY

CASE STUDY 1 : Shorted Turn Failure These are the responses of the HV and LV winding of the same transformer Significant difference in the White phase Imbalance in the reluctance on one of the core limbs (white phase) as a result of shorted turns will produces this characteristic response in the low frequencies ETHEKWINI ELECTRICITY

CASE STUDY 2 : Multiple grounded neutral Figure A shows the LV winding response of a multiple grounded neutral and Figure B shows the response after the transformer was repaired. Significant difference in the starting dB values This difference in the dB or vertical shift in response A is attributed to the change in the resistance of the transformer ETHEKWINI ELECTRICITY

CASE STUDY 3 : Core Magnetization Figure A shows the fingerprint response of the transformer and Figure B shows the response as a result of a magnetized core This transformer was diagnosed with a tapchanger problem – DC test performed on contacts - inadvertently magnetized the core Figure B shows a shift and the elimination of existing resonance frequencies ETHEKWINI ELECTRICITY

CASE STUDY 4 : Extra Core Earth These are responses of the middle phase with (White trace) and without (Red trace) an extra core earth. Differences were noted on all three phases but the greatest difference was on the middle phase There is a difference in the capacitance response from about 1,5 kHz to 14 kHz The White trace has a resonant frequency at 1,6 kHz which is absent in the Red trace ETHEKWINI ELECTRICITY

CONCLUSION Sweep Frequency Response Analysis has proven itself within eThekwini Electricity to be a valuable diagnostic tool for the detection of winding movement and other faults that affect the transformers impedance An advantage is that reference responses are not required The results obtained are reliable, repeatable and unaffected by test lead position, weather and electromagnetic interference. The test is easy to perform, however measurements must be made confidently and conscientiously to ensure reliable and meaningful diagnosis SFRA when used in conjunction with other diagnostic tools can provide a complete condition assessment of the transformer and in so doing ensure that informed decisions are made by asset managers. ETHEKWINI ELECTRICITY