PD Detection on Metal Enclosed Switchgear Panels

Similar presentations


Presentation on theme: "PD Detection on Metal Enclosed Switchgear Panels"— Presentation transcript:

1 PD Detection on Metal Enclosed Switchgear Panels
PARTIAL DISCHARGE DETECTION ON METAL ENCLOSED SWITCHGEAR PANELS BY LENNY GOVENDER AND KAMENDREN GOVENDER 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

2 PRESENTATION OVERVIEW
Introduction Partial Discharge Acoustic Emission Tests Operation Basic Examples Case Studies Conclusion 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

3 PD Detection on Metal Enclosed Switchgear Panels
INTRODUCTION TE is responsible for maintenance of ± metal enclosed switchgear panels operating at 11 kV Reliability of aging switchgear panels is of paramount importance to the stability and performance of the network TE has embarked on a condition assessment program through the introduction of advanced diagnostic testing 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

4 PD Detection on Metal Enclosed Switchgear Panels
INTRODUCTION (cont.) Use of acoustic techniques seems to be an excellent starting point for the detection of partial discharges in 11 kV switchgear panels This method had proven itself invaluable in the detection of Partial Discharge within GIS This non-invasive method has the ability to detect, locate and evaluate defects within switchgear panels 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

5 PD Detection on Metal Enclosed Switchgear Panels
PARTIAL DISCHARGE Definition ..is an electrical discharge that only partially bridges the insulation between conductors and which may or may not occur adjacent to a conductor… Mediums ??? Solid, Liquid & Gas Why Test ??? Degradation of insulation material 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

6 ACOUSTIC EMISSION TESTS
Acoustic transducers detect and capture energy Data Interpretation Acoustic energy radiates from discharge source Figure 1: Sound Energy from a Discharge Source 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

7 ACOUSTIC EMISSION TESTS (cont.)
Practical Testing In practice it tends only to be used for the detection of discharges in gas equipment and surface tracking or corona Surface Tracking Tracking is the formation of a permanent conducting path across an insulator surface Usually the conduction path results from degradation of the insulation Corona Detection is usually performed at frequencies between 30kHz and 90kHz Absolute levels are likely to vary considerably with atmospheric conditions Concentration on variation in recorded levels between similar pieces of equipment should be done 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

8 PD Detection on Metal Enclosed Switchgear Panels
OPERATION Acoustic Emission Testing AE proved successful as diagnostic tool for GIS Experimented on metal enclosed switchgear The Instrument Ultrasonic sensor – monitors signals μC performs data operation Results displayed on LCD screen Record the background noise Screen the panel by moving the sensor 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

9 OPERATION(cont.) RMS Value during one power cycle
Periodic Peak during one power cycle Degree of modulation with the power cycle Degree of modulation with twice the power cycle Figure 2: Continuous Mode with Background noise 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

10 PD Detection on Metal Enclosed Switchgear Panels
BASIC EXAMPLES Figure 3 : Example1 Figure 4: Example 2 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

11 CASE STUDY 1 Continuous Mode
RMS bar and periodic peak value have increased PD is present Freq 1 and Freq 2 content PD on positive and negative cycles Figure 5: PD detection in Continuous Mode 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

12 CASE STUDY 1(cont.) Phase Measuring Mode:
Correlation between the acoustic signal and power frequency PD is present in both cycles Figure 6: The Phase Measuring Mode 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

13 CASE STUDY 1(cont.) FINDINGS ??? Surface Discharge on the
Current Transformer Figure 7: Surface Tracking on CT 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

14 CASE STUDY 2 Continuous Mode Phase Mode
RMS and Periodic Peak increased PD in correlation to 100 Hz Figure 8: Continuous measuring mode PD is present Phase Mode Correlation between acoustic signal and the power frequency Figure 9: The Phase Measuring Mode 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

15 CASE STUDY 2 FINDINGS??? PD ON THE CRUTCH
Figure 10: Inspection on Cable Terminations 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

16 PD Detection on Metal Enclosed Switchgear Panels
CONCLUSION Acoustic Method has proven to be a reliable tool for condition assessment in GIS Successful in detecting PD in metal enclosed switchgear However, the drawbacks of this testing technique are: Results can be influence by severe background noise; and Only surface discharge can be detected 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels

17 PD Detection on Metal Enclosed Switchgear Panels
THANK YOU !!! 19/09/2018 PD Detection on Metal Enclosed Switchgear Panels