MarsⅡ On-Line UPS Series

Similar presentations


Presentation on theme: "MarsⅡ On-Line UPS Series"— Presentation transcript:

1 MarsⅡ On-Line UPS Series

2 Content Introduction of MSII Series System Block Diagram
Product Features Functions Explanations Product Specifications Q&A

3 Introduction of MSII Series
Model MSII K (RT) 6K (X) (RT) (C) 8K (X) (P) (PX) (RT) (RTP) 10K (X) (P) (PX) (RT) (RTP) MSII K、20K Rack / Tower Convertible Design 4.5K 6K 8K 10K 15K、20K (Tower Unit)

4 System Block Diagram Standard Unit (Mono/Mono)

5 Unit (Mono/Mono) w/Dual Input

6 Standard Unit (Tri/Mono)

7 Unit (Tri/Mono) w/Dual Input

8 Product Features True On Line Double Conversion Topology
Advanced Digital Control Technology N+1 Power Scalable Parallel Redundancy (up to 80KVA/60KVA) Support Normal/ECO/CF50/CF60 Modes Galvanic Isolation ( up tp 20kVA, optional ) External Battery Cabinet & Charger Hot-Swappable Battery Versatile Interfaces Personalization & Intelligent Self-diagnostics

9 Functions Explanations
Consists of 5 x LEDs 1 x Large-scale LCD 6 x Control Keypads Functions Status Display Parameters Reading Operation Control Personalization Self-diagnostics

10 For Tower UPS LED Indicators Mains_1 LED Mains_2 LED Redundancy LED ECO Mode LED Common Alarm LED Control Keypads On ( & Alarm Silence) Key Off Key Function Key Scroll Keys Enter Key

11 For RT UPS LED Indicators Mains_1 LED Mains_2 LED Redundancy LED ECO Mode LED Common Alarm LED Control Keypads On ( & Alarm Silence) Key Off Key Function Key Scroll Keys Enter Key

12 LCD Display Explanations
Status Line Mode, Backup Mode, ECO Mode, Bypass Supply, Battery Low Voltage, Battery Bad/Disconnect, Overload, Transferring with Interruption, & UPS Fault. Parameters AC Voltage, Frequency, Load Percentage, Battery Voltage, & Temperature.

13 A RS232 Port B Terminal Resistor for Parallel function C CAN Bus Connection Port for Parallel System D Customer Options Slot 1 E Customer Options Slot 2 F Cooling Fan G External Battery Connector H External Charger Connector I Utility Input Breaker CB1 J Bypass Input Breaker CB2 (for Dual Input Model Only) K CAM Switch(Maintenance Bypass Switch)* L Input/Output Terminal Block M Fixing Holes for External Charger Cabinet N EPO(Emergency Power Off): Short to enable the function O Thermal breaker for the protection of Load in abnormal condition: CB3 (for 8-10kVA with Transformer Model Only) P Air Ventilation Hole . DIM:Dual Input Model, SIM:Single Input Model * : 15K/20K option

14

15 External Communication Interface
Standard Unit : Adapted with RS232 and EPO Optional in 2 Slots : 1. WEB/SNMP Card 2. True Relay Contact Card 3. RS485 Card 4. USB Card 5. 2nd RS232 Card

16 Communication Software
Emily UPSilon 2000

17 External Battery Charger
Capacity 1000Watt Continuously Isolated Conversion Topology Parallel Units up to 4 PFC Control Mounted on the Rear of UPS or on the Wall

18 External Battery Bank Same Dimension as UPS Unit
Battery Configurations (Tower) 7AH/12V x 40/60 PCS 9AH/12V x 40/60 PCS 12AH/12V x 40 PCS Battery Configurations (RT) 7AH/12V x 20 PCS (3U) 9AH/12V x 20 PCS (3U) 15K、20K Battery Configurations 9AH/12V x 40 PCS (Standard) 9AH/12V x 60 PCS 12AH/12V x 40 PCS

19 MSII 8K 10K 15K 20K (3P/1P) Simply install one additional Rectified Board

20 Optional Galvanic Transformer
Module for Tower Unit Secondary Voltage a. same as Primary or 240/120V connections by user b. 240/208/120V Net Weight: 34kgs for 4.5k/6kVA 53kgs for 8k/10kVA

21 Optional Galvanic Transformer
Module for RT Unit 6kVA 440x660x88(2U)mm, 42kgs 8k/10kVA 440x660x132(3U)mm, 49kgs

22 Parallel System Installation

23

24 Maintenance Box For Easy Maintenance Or Service
Parallel Option Maintenance Box For Easy Maintenance Or Service TowPDU2120 For Max. Two 15KVA/20KVA UPS in Parallel(2 unit) TowPDU2200 For Max. Two 15KVA/20KVA UPS in Parallel(2 unit) TowPDU2XXX For Max. Four 15KVA/20KVA UPS in Parallel(4 unit)

25 N+1 Redundancy & MTBS Application
LOAD

26 N+1 Redundancy & MTBS Application
LOAD

27 N+1 Redundancy & MTBS Application
LOAD

28 Operating Ambient Temperature Storage Ambient Temperature
Model TowPDU260 TowPDU2120 TowPDU2200 Input Voltage 200Vac ~ 240Vac Input Current 60Arms 120Arms 200Arms Operating Ambient Temperature 0℃ to 40℃ ( 32℉ to 104℉) Storage Ambient Temperature -20 to 60℃ ( -4℉ to 140℉) Humidity 0% to 95% non-condensing Dimensions ( W x H x D mm ) 440x176x124

29 Product Specifications
Model 4.5K 6K 8K 10K Input Voltage Window 160~280Vac* 160~280Vac(1Φ)/277~485Vac(3Φ) Frequency 45 ~ 65 Hz Phase/Wire Single, Line + Neutral + Ground Input Current THD (minimum) 6% at 100% Linear Load Power Factor Up to 0.99 at 100% Linear Load *160~175V for <75% load

30 Nominal; +/-1%; +/-2%; +/-3% Voltage Regulation +/-2% Capacity (VA/W)
Model 4.5K 6K 8K 10K Output Rated Voltage 200/208/220/230/240Vac Selectable Voltage Adjustment Nominal; +/-1%; +/-2%; +/-3% Voltage Regulation +/-2% Capacity (VA/W) 4500/3150 6000/4200 8000/5600 10000/7000 Rated Power Factor 0.7 Lagging Wave Form Sine Wave, THD<3% (no load to full load) Frequency Stability +/-0.2% (Free Running) Frequency Regulation +/-1%; +/-3% Transfer Time 0ms Crest Factor 3:1 Efficiency (AC to AC, Normal) Up to 90% Up to 93.5% Efficiency (AC to AC, ECO) >95% DC Start Yes

31 Backup Time & Fast Recharge Time
LOAD MSII6000 + 1 x BBT40J007 + 2 x BBT40J007 + 3 x BBT40J007 + 4 x BBT40J007 1050w (25%) 42mn 2hr16mn 3hr47mn 5hr18mn 6hr48mn 2100w (50%) 15mn 1hr16mn 2hr14mn 3hr08mn 4hr02mn 3150w (75%) 11mn 54mn 1hr35mn 2hr52mn 4200w (100%) 08mn 36mn 1hr10mn 1hr44mn Inside Charger 3hrs 8hrs 14hrs 18hrs 24hrs + 1000W Charger x 5hrs 7hrs 9hrs

32 Backup Time & Fast Recharge Time
LOAD MSII10000 + 1 x BBT40N009 + 2 x + 3 x + 4 x BBT40JN009 1750w (25%) 40mn 2hr16mn 2hr48mn 5hr18mn 6hr50mn 3500w (50%) 14mn 1hr08mn 2hr 2hr49mn 3hr37mn 5250w (75%) 08mn 47mn 1hr18mn 1hr56mn 2hr30mn 7000w (100%) 05mn 29mn 59mn 1hr23mn 1hr53mn Inside Charger 5hrs 14hrs 26hrs 38hrs 45hrs + 1000W Charger x 8hrs 11hrs 15hrs

33 200/220/230/240Vac Selectable(208/120Vac Optional) Voltage Adjustment
Model MSII15000 MSII20000 INPUT Voltage Window 304~485Vac(3Φ R, S, T, N )* Frequency 45~65Hz Power Factor >0.95 at 100% Linear Load Input Current THD <30% at 100% Linear Load OUTPUT Rated Voltage 200/220/230/240Vac Selectable(208/120Vac Optional) Voltage Adjustment Nominal; +/-1%; +/-2%; +/-3% Voltage Regulation +/-2% Capacity 15000VA/13500W 20000VA/18000W Rated Power Factor 0.9 Lagging Wave Form Sine Wave, THD< 3% (no load to full linear-load) THD< 4%(20KVA/18KW, 15KVA/13.5KW) Frequency Stability +/-0.2% (Free Running) Frequency Regulation +/-1Hz; +/-3Hz Crest Factor 3:1 acceptable Efficiency (AC to AC, Normal) >91% DC Start Yes Battery Voltage 240Vdc

34 Backup Time & Fast Recharge Time
15KVA/13.5KW 20KVA/18KW LOAD 9Ah 40PCS 60PCS 12Ah 6750w (50%) 15min. 30min. 28min. 10800w (80%) 8min. 13min. 13500w (100%) 6min. 11min. 10min. LOAD 9Ah 40PCS 60PCS 12Ah 9000w (50%) 11min 18min. 16min. 14400w (80%) 5min. 10min. 9min. 18000w (100%) 4min. 7min. 6min. 9Ah 40PCS 60PCS 12Ah RECHARGE TIME(90%)* 4 hours 6 hours 5 hours * inner charger(1000W)

35 Q & A