1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click the APC logo link to jump back to the previous showed slide. Click the left margin area to jump to the index (“Contents of the presentation”) From the index -links, you may jump to any other subjects. - use the APC-return logo to return to the index slide again . DP300E rev 8.3

2 APC presentation Silcon DP300E On-line power protection Duration:
DP300E rev 8.3

3 It’s a world of risky business
DP300E rev 8.3

4 ... 5 minutes power down time in your company !
Imagine... ... 5 minutes power down time in your company ! DP300E rev 8.3

5 Sort

6 5 minutes power down time
Is your business depending on IT infrastructure? What is the cost of IT downtime? Do you have a strategy for securing up-time? Do you have a strategy for power availability? 5 minutes power down time

7 Enterprise IT Infrastructure
Is this the situation…? Application Servers NT, UNIX, Novell etc. File server DP300E Mainframe Print Web Mail DP100E Gateway Mini Computers DP10E Windows 95 Windows NT OS/ and others Policy... Protection of the critical infrastructure to ensure: Up-time Data safety Availability Efficiency Productivity DP300E rev 8.3

8 Contents of the presentation
Silcon DP300E Series Headlines: Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Contents of the presentation DP300E rev 8.3

9 Cost of down time Cost of down time Performance and benefits
UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Cost of down time DP300E rev 8.3

10 Cost of IT Power Down time
Cost of down time Fortune 1000 companies average outage across industries that lasts four hours costs…. USD 330,000. Source: Find/SVP. Outages includes other than power failures DP300E rev 8.3

11 Cost of IT Power Down time
Cost of down time A typical company experiences 9 outages per year, resulting in annual losses of almost (excluding the cost of lost employee productivity). USD 3 million Source: Find/SVP. Outages includes other than power failures DP300E rev 8.3

12 Average industry cost of down time
Financial Brokerage operations Financial Credit card operations Media Pay-per-view Retail Home shopping (TV) Retail Home catalog sales Transportation Airline reservations Media Tele ticket sales Transportation Package shipping Finance ATM fees $ 6,45 million $ 2,6 million $ $ $ $ $ $ $ Source: Dataquest, Perspective, Sept. 30, 1996 DP300E rev 8.3

13 ...97% of power supply problems are coursed by
IT Power problems... Cost of down time ...97% of power supply problems are coursed by power disturbances and low supply voltage. the invissible events Source: National Power Laboratories USA DP300E rev 8.3

14 Power problems are preventable...
Did You Know? Cost of down time Causes of data loss... Power problems are the largest single cause of data loss, 5 times more frequent than viruses. Power problems are the second largest (to theft) cause of hardware loss. Power problems are preventable... Source: Contingency Planning DP300E rev 8.3

15 Industry Trends Drive Demand for...
Cost of down time Constant- Clean- Increased IT usage: Internet extranets EDI E-commerce Databases 7 x 24 hours up-time network availability Utility deregulation Power DP300E rev 8.3

16 99.9% uptime per year... 99.99% uptime per year...
Did you realize that.... Cost of down time 99.9% uptime per year... means 525 minutes down time (8½ hours) 99.99% uptime per year... means 52 minutes down time 99.999% uptime per year... means 5 minutes down time Investment “nines” DP300E rev 8.3

17 Users Require 7 x 24 hours Availability...
Cost of down time “As businesses becomes more internationalized, 7 x 24 hours access to computer systems is a requirement. , group-ware, and similar types of services are becoming business critical, - and as a result, highly available systems are now needed by many more organizations.” IDC, Highly Available Systems Study DP300E rev 8.3

18 Information availability... throughout the enterprise network
Cost of down time Corporate Datacenter Regional Datacenter Regional Datacenter Regional Datacenter Local servers Local servers Local servers Local servers Local servers Local servers Local servers Local servers Local servers DP300E rev 8.3

19 Enterprise Customer Needs
Cost of down time No shut-down = Availability Mainframe class functionality, reliability, availability, and fault tolerance Flexible growth Round-the-clock, easy manageability Low cost of ownership 7 x 24 hours system support Operate in poor power conditions DP300E rev 8.3

20 On-line 3 phase UPS systems for…
Cost of down time Data Centers Corporate network - and industrial applications ...to protect any company or organization against losing money in case of power failure at... Lowest operation cost Lowest installation cost Highest performances DP300E rev 8.3

21 Performance and benefits
Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Performance and benefits DP300E rev 8.3

22 Silcon DP300E Series The product family offers...
Performance and benefits … from 10 to 480 kVA/ kW in one unit Cubicles for: UPS + Battery packs + isolation and combinations Highest efficiency Lowest operation cost “Close to perfect” DP300E rev 8.3

23 Performance and benefits “Close to perfect” means...
Silcon DP300E Performance and benefits “Close to perfect” means... Up to 97% efficiency Input power factor corrected to 1 No mains repercussions Full rated output power available in kW 200% overload capacity Compact and small footprint Expandable for more Power/ Redundancy DP300E rev 8.3

24 Performance and benefits
Silcon DP300E Performance and benefits What more to say about Delta-Conversion… ? Unique patented APC/Silcon technology True on-line system No phase compensation required Saves you the most money in operation Lowest installation cost “Close to perfect” DP300E rev 8.3

25 Performance and benefits
Silcon DP300E - power flow Performance and benefits Delta-Conversion Mains input Regulating the delta, ± diff. in/out Delta Inverter 1. Normal operation 2. Regulated operation Main Inverter Load 3. Battery operation Battery 4 Recharge battery DP300E rev 8.3

26 Performance and benefits
Mains repercussions... Performance and benefits Delta-Conversion Legacy double conversion Distortion free no repercussions Repercussions caused by UPS DP300E rev 8.3

27 Silcon DP300E - Input/ output efficiency
Performance and benefits 97% % Efficiency The high efficiency comes from the unique Delta-Conversion Technology Silcon DP300E Legacy UPS Systems % Load DP300E rev 8.3

28 Performance and benefits
High efficiency Performance and benefits Energy loss Legacy UPS systems Silcon DP300E Delta-Conversion Saves energy UPS DP300E rev 8.3

29 Would you accept 0.7 of a pint?
Performance and benefits “Would you accept 0.7 Power factor?” UPS UPS DP300E rev 8.3

30 Delta-Conversion On-Line and high efficiency…?
Performance and benefits what´s the trick…? DP300E rev 8.3

31 The Energy Saving Trick...
Performance and benefits Double conversion 4. Floor 5. Floor Delta Conversion DP300E rev 8.3

32 Performance and benefits
Who makes the trick... Performance and benefits The APC-Delta Conversion Technology is today protected by patents. APC is the exclusive supplier of this technology - DP300E The technology is not likely to be available from many other UPS-suppliers for some time DP300E rev 8.3

33 Silcon DP300E Series - technology
Performance and benefits The Delta-Conversion Technology “close to perfect” DP300E rev 8.3

34 UPS power factor Cost of down time Headlines: Headlines:
Performances and benefits Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Headlines: Cost of down time Efficiency Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Fans Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review UPS power factor DP300E rev 8.3

35 UPS - power factor Input - output and load
The power factor… Power factor Considerations: Input power-factor Output power-factor Load power-factor UPS UPS Load power factor INPUT OUTPUT LOAD DP300E rev 8.3

36 Silcon DP300E - power factor Input power factor
Input power-factor is always 1 regardless of load... This means: High efficiency Smaller cables Smaller fuses No separate phase compensation required Lower installation cost Load (kW) UPS Supply INPUT DP300E rev 8.3

37 Silcon DP300E Input Power Factor… and the installation
Legacy UPS system Power factor 1 - means lower input current therefore... smaller cables and fuses DP300E rev 8.3

38 Silcon DP300E - Output power factor kVA and kW - ratings...
Unity output power-factor - means: Full load capacity specified in kWatts or kVA at unity PF Load PF-working range: inductive to 0.9 capacitive Normally smaller UPS size (compared to competitors) when pure resistive load System rated for... kVA = kW UPS Load OUTPUT DP300E rev 8.3

39 The power-factor on UPS loads will increase…
Load power-factor Type of load UPS load power-factor… Depending on type of load Computer load: 0.6 to1.0 typ. 0.8 (Trend: load power factor 1) The UPS must always be power-sized to supply the sum of loads in UPS Load power factor kVA LOAD DP300E rev 8.3

40 kVA-load ? ? ? Power sizing the UPS... ? Power factor on mixed loads
56 kW PF = 0.8 Legacy UPS system ? 70kVA kVA-load 60 kVA/ kW PF =1 60 kVA/ 48 kW PF = 0.8 Power factor on mixed loads DP300E ? Legacy UPS system ? Load 1: (8 kW / 0.8) = …..…… kVA Load 2: (18 kW / 0.9) = ……… kVA Load 3: (30 kW / 1) = ……..… kVA Sum of loads… kW…….……..……. 60 kVA 60 kVA 60 kVA UPS size = kVA/ kW load UPS size = kVA load DP300E rev 8.3

41 kW-load ? ? Power sizing the UPS... Power factor on loads = 1 75kVA
PF = 0.8 kW-load 60 kVA/ kW PF =1 Legacy UPS system ? Power factor on loads = 1 DP300E ? Load 1: = …………..…..… kW Load 2: = …………..……… kW Load 3: = ………..……..… kW Sum of loads………………………… kW 75kVA 60 kW UPS load = Loads/ 0.8 UPS load = Loads/ 1 DP300E rev 8.3

42 Silcon DP300E - Power sizing the UPS
Power factor Power sizing the DP300E UPS Calculate the sum of the UPS-load in kVA Define highest phase load Choose the DP300E having its full load output power equal to - or bigger than the load Additional considerations.. Overload capacity Redundancy ……. - see the Power Binder for further details DP300E rev 8.3

43 Economy with Silcon DP300E
Headlines: Cost of down time Efficiency Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Fans Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Economy with Silcon DP300E DP300E rev 8.3

44 The total Economy... : Purchase Price Installation Costs
- for a UPS system includes: Purchase Price Installation Costs Operating Costs Maintenance & Repair DP300E rev 8.3

45 Purchase Price Before comparing UPS prices it must be ensured they
Economy Before comparing UPS prices it must be ensured they are equal with respect to mains repercussion: Mains repercussion consists of a mains current out of phase with the mains voltage and a distorted mains current. Utilities demand a min. PF or require payment for the kVAh instead of the kWh. Utilities demand distortion filters installed if other power consumers are disturbed. DP300E rev 8.3

46 Above might increase the purchase price for the UPS with up to 30%
Economy “To clean” the mains input current in a legacy UPS system with 6-pulse thyristor rectifier normally involves: Legacy UPS A 12-pulse rectifier. A harmonic filter. A phase compensating unit. OPTION OPTION OPTION Above might increase the purchase price for the UPS with up to 30% UPS DP300E rev 8.3

47 Installation Costs Economy High efficiency and unity power factor generally means lower installation costs on the mains input side of the UPS: The installation costs on the UPS mains input side are determined by the prescribed input fuse for the actual UPS. As a rule a DP300E requires an input fuse one step smaller than a legacy UPS system without phase compensation. The installation costs are correspondingly lower. DP300E rev 8.3

48 Annual cost savings with Silcon DP300E
Economy USD 10000 20000 30000 40000 50000 60000 10 20 40 60 80 120 160 240 320 480 Savings USD USD 1472 Silcon DP300E compared to legacy UPS system… With harmonic filter Incl. cost of air conditioning Energy price: USD 0.18/kWh Savings - pay back your UPS investment within 5 years kVA Rating DP300E rev 8.3

49 Operating Costs The operating costs come from: Load power
Economy The operating costs come from: Load power UPS power losses Air conditioning Maintenance & repair - Let´s focus the power loss and the savings... DP300E rev 8.3

50 Power loss costs at 10 kVA... Silcon DP310E Economy UPS power losses and air conditioning have to be paid via the electricity bill ! UPS type: DP310E, 10kVA Period: 8760 timer, 1 year Efficiency: 95% Load: 100% Air con. power 33% Power price: USD 0.18/ kWh Power losses = input - output power = (10/0.95)-10 = 0.53 kW Cost of power loss: 0.53 x 8760 x 0,18 = USD 835 Cost of air con.: 835 x 0.33 = USD 275 Total to pay: = USD 1110 DP300E rev 8.3

51 A yearly saving of 2328 - 1110 = USD 1218
Power loss costs at 10 kVA... Legacy UPS Economy The same calculation for a legacy UPS system having an efficiency of 90% results in a bill of UPS type: A legacy UPS, 10kVA Period: 8760 timer, 1 year Efficiency: 90% Load: 100% Air con. power 33% Power price: USD 0.18/ kWh Power losses = input - output power = (10/0.9)-10 = 1.11 kW Cost of power loss: 1.11 x 8760 x 0,18 = USD 1750 Cost of air con.: 1750 x = USD 578 Total to pay: = USD 2328 A yearly saving of = USD 1218 What about 3, 5 & 10 Years ???? DP300E rev 8.3

52 Power loss costs at 30 kVA Economy UPS type: DP300E, 30 kVA A legacy UPS, 30 kVA Period: 8760 timer, 1 year 8760 timer, 1 year Efficiency: 96% 88% Load: 100% 100% Air con. power 33% Power price: USD 0.18/ kWh USD 0.18/ kWh Legacy UPS power losses per year (30/ ) kW x hour x 0.18 USD x 1.33 air con = USD 8579 Silcon DP300E power losses per year (30/ ) kW x hour x 0.18 USD x 1.33 air con = USD 2621 33% Saving with DP300E = = 5958 USD first year DP300E rev 8.3

53 Power loss costs at 160 kVA Economy UPS type: DP300E, 160 kVA A legacy UPS, 160 kVA Period: 8760 timer, 1 year 8760 timer, 1 year Efficiency: 97% 91% Load: 100% 100% Air con. power 33% 33% Power price: USD 0.18/ kWh USD 0.18/ kWh Legacy UPS power losses per year (160/ ) kW x hour x 0.18 USD x 1.33 air con = USD 33186 Silcon DP300E power losses per year (160/ ) kW x hour x 0.18 USD x 1.33 air con = USD 10378 Saving with DP300E = = USD first year DP300E rev 8.3

54 Saving money with DP300E Calculating actual costs
Data: Economy DP300E rev 8.3

55 Saving money with DP300E Calculate savings for a period of 10 years...
Economy DP300E rev 8.3

56 DP300E in parallel Cost of down time Performance and benefits
UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review DP300E in parallel DP300E rev 8.3

57 Parallel operation DP300E series in parallel operation…
1 2 3 4 5 6 7 8 9 - for expansion and redundancy or both. DP300E rev 8.3

58 Expansion and Redundancy
Parallel operation Expansion: - up to 9 units can be connected whenever you need more power. Redundancy: - to comply with strict requirements for uninterruptible operation - oversized capacity DP300E rev 8.3

59 Advanced Power Management
Parallel operation Optimized redundancy operation by control system. - only systems needed to supply the load are “active”. - the load can be switched between the systems in a preprogrammed sequence. Day 1 Day 3 Day 2 DP300E rev 8.3

60 Advanced battery management
Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Advanced battery management DP300E rev 8.3

61 Silcon DP300E battery life time
Battery management Extended battery life time…! - by “floating voltage compensation” - by charge voltage / battery temperature compensation - by advanced battery monitoring, control and alarms Typical: 2 years more life time ! DP300E rev 8.3

62 Silcon DP300E battery life time
Battery management Years Charge voltage compensated Typical compensation level from 2.20 to 2.36 Volts/ cell No compensation Temperature °C DP300E rev 8.3

63 Power Control Cost of down time Performance and benefits
UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Power Control DP300E rev 8.3

64 Silcon DP300E - Diesel back-up
Power Control Diesel / DP300E installation: Normal back-up time UPS: 5 to 10 minutes After 5 minutes - Diesel connects to DP300E Legacy UPS: 3-5 times over sizing Using DP300E series: no over sizing because: the sinusoidal input cause no distortion feed-back no distortion of supply from tyristors programmable soft start - step load from battery to diesel DP300E rev 8.3

65 Diesel / DP300E installation
Diesels Best Friend... Power Control Diesel / DP300E installation Mains Supply Diesel Generator Input Panel DP310E - DP340E SBP Distr. Panel DP300E rev 8.3

66 Diesels Best Friend... 100 kVA 100 kW 300 - 500 kVA 100 kVA
Power Control Same size as UPS No harmonics Silcon DP300E DIESEL 100 kVA 100 kW 3-5 times oversized Harmonics Traditional UPS DIESEL kVA 100 kVA DP300E rev 8.3

67 Communications and operations
Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Communications and operations DP300E rev 8.3

68 Communications and operations
User interface 15 languages Alarms Audible alarms for 38 different monitored functions Key measurements Utility power Battery status Output power Percent of capacity UPS-events logger Time stamped events Log is accessible from key-pad DP300E rev 8.3

69 Communications and operations
PC-software, DP-Soft CDX Shut-down Manager Makes unattended safe, automatic shut-down of your network if battery back-up time runs out. Notify connected users to make safe shut-down. DP300E rev 8.3

70 Communications and operations
DP view - SNMP Adapter The SNMP Adapter Tools for monitoring networked UPS systems Links your DP300E to network (RS232) Monitoring your UPS from any network location Central control of internetworking equipment like: Routers, servers, gateways, UPS DP300E rev 8.3

71 Determine the right solution
Communication... Questions Do you require monitoring Do you require shutdown Number of Servers / Workstations Network topology Operating Systems DP300E rev 8.3

72 With the right solution...
Communication... DP300E rev 8.3

73 Datasave Acrobat Reader UPS DP-SOFT CDX / DP-SOFT
Communication... DP300E rev 8.3

74 Stand alone architecture
Communication... Orderly shutdown of one computer... UPS PC Power RS232 DP300E rev 8.3

75 Stand alone architecture
Communication... Orderly shutdown of one computer… Broadcast to clients on the network... Server Client UPS DP300E rev 8.3

76 DP-SOFT CDX - Master/Slave
Communication... Orderly shutdown of more computers... Network Master RS232 Slaves Clients UPS Power DP300E rev 8.3

77 Multi-Link Unit Shutdown of more computers…
Communication... Shutdown of more computers… For all OS supported by Soft+ Daisy chainable UPS Server 1 Server 2 Server 3 Server 4 Server 5 Server 6 DP300E rev 8.3

78 NMS Sub Agent for Novell, NT & OS/2
Communication... Monitoring your UPS through the network... Console User interface NT Monitoring/Shutdown Core Driver INI Files UPS Proxy Sub Agent TCP/IP Network Driver NMS Application (Snap-in) NMS SNMP TCP/IP Network Driver DP300E rev 8.3 14

79 DP-View SNMP adapter Monitoring your UPS through the network Net work
Communication... Net work Monitoring your UPS through the network DP300E rev 8.3

80 DP-View Navigator Communication... Graphical user interface (GUI) for HP Open View (NMS system) Windows 95 Windows NT HP UNIX 22 DP300E rev 8.3

81 DP - Dial UPS Monitoring your UPS
Communication... Monitoring your UPS - through the Public Telephone Network... Control Centre Mobile Phone Pager DP-Dial UPS RS232 Public Telephone Network Service Technician Local DP300E rev 8.3

82 Power Administrator Communication... DP-SOFT+ DP-SOFT+ DP-SOFT+
Relay RS232 Network Power Administrator 800 UPS Power Local Monitoring DP-SOFT CDX NMS DP300E rev 8.3

83 Environment Administrator
Communication... Smoke Power Temp Lightning Air Conditioning Intruder Water UPS Modem Environment Administrator Pager Network Management Station DP300E rev 8.3

84 Green Power with Silcon DP300E
The green aspects... Minimizing the environmental impact... Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review DP300E rev 8.3

85 Green Power with Silcon DP300E
The green aspects... Green Power means saving resources in… Power consumption - by highest efficiency - less CO2-pollution from your power plant Low heat dissipation - by highest possible power factor “1” saves fan energy Smaller installation cost - due to the high efficiency -smaller cables and fuses No mains repercussions - saves costly EMC filters and energy losses Longer battery lifetime - charge-voltage relative to battery temperature Small space requirement - compact cabinet including many features as standard Recyclable materials - No PVC´s DP300E rev 8.3

86 Silcon DP300E - Efficiency
The green aspects... 97% % Efficiency Highest efficiency …saves energy resources …lower CO2 emission Silcon DP300E Legacy UPS Systems % Load DP300E rev 8.3

87 Green Power with Silcon DP300E
The green aspects... Extended battery lifetime… Years Charge voltage compensated ...less battery resources No compensation Temperature °C DP300E rev 8.3

88 Green Power with Silcon DP300E
The green aspects... Power factor - “1” Input power factor Power factor 1 ...less installation resources …less power dissipation Load (kW) DP300E rev 8.3

89 Green Power with Silcon DP300E
The green aspects... DET NORSKE VERITAS ENVIRONMENTAL SYSTEM CERTIFICATE APC Silcon Division is the first UPS vendor with ISO Certification DP300E rev 8.3

90 Service Cost of down time Performance and benefits UPS power factor
Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Service DP300E rev 8.3

91 AGS - 7. Division in APC Service APC GLOBAL SERVICE DP300E rev 8.3

92 Consistent high quality
AGS policy Service Consistent high quality “on site” service” - world wide DP300E rev 8.3

93 FAT AGS - program... Custom designed service solutions
Service program from buying process to lifecycle of your UPS Factory Acceptance Test FAT Service response time: within 24 hours Every service call is completed with a service report DP300E rev 8.3

94 Service products Premium Power Reliability package
Essential Power Reliability package Annual Maintenance Program Start-Up Service DP300E rev 8.3

95 Maintenance & Repair The maintenance is normally consisting of:
Service The maintenance is normally consisting of: Check of the system times a year Exchange of the battery at specified intervals Exchange of the fans at specified intervals The maintenance and repair costs are very different - some gambles and do nothing - if lucky they have no costs. - Others take out a complete maintenance and repair insurance with a yearly fee of % of the UPS price. DP300E rev 8.3

96 Accessories Headlines: Cost of down time Efficiency Cost of down time
Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Fans Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Accessories DP300E rev 8.3

97 Battery cubicles BDP Modularized cubicles for housing batteries
Accessories Modularized cubicles for housing batteries Matching cubicles from DP310E to DP380E Battery storage Easy battery accessibility Easy to install Small foot print Clean cabinet design DP300E rev 8.3

98 Galvanic isolated transformers
Accessories Modularized cubicles for housing transformers Matching cubicles for all DP300E units Transformer storage for galvanic isolation transformers DP300E rev 8.3

99 Remote display A convenient tool for the Facility Manager
Accessories A convenient tool for the Facility Manager Matching the whole DP300E family Remote surveillance of UPS Information identical to UPS Display Alarm features Surveillance tool only Operation distance - 25m DP300E rev 8.3

100 Service bypass panel -SBP300E
Accessories Safe bypass operation Switch panel for off-line operation Intelligent communication to DP300E eliminates fault operation Signal lamps indicate proper operation of the panel Bypass panel for efficient installation and safe maintenance DP300E rev 8.3

101 Service bypass panel - SBP300E
Accessories Configurations... Single System Parallel/ Redundant System System input System output System input System output DP300E rev 8.3

102 Fuse box - MCCB Guarding the Silcon DP300E external battery bank
Accessories Guarding the Silcon DP300E external battery bank Safe battery installation Protects against electric shocks Enhances safety with coiling and tripping facilities DP300E rev 8.3

103 Technical Data Cost of down time Performance and benefits
UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Technical Data DP300E rev 8.3

104 Silcon DP300E: 10 - 480 KVA 3-phase
Technical data 10 kVA 20 kVA 40 kVA 60 kVA 80 kVA 120 kVA 160 kVA 240 kVA 320 kVA 480 kVA 400V 400V 400V Built-in Batteries External Batteries External Batteries - click for 208/ 480V data DP300E rev 8.3

105 Silcon DP300E - Performances version 3x380/ 400/ 415V
Technical data Type - (version 3x380/ 400/ 415V) DP310E DP320E DP340E DP360E DP380E Output power, kW/ kVA 10 20 40 60 80 Full load output current, Amp. 14.5 29.0 57.7 87 115 Max input current, Amp. 18.9 37.6 74.7 112 147 Efficiency AC to AC, 100% load, % 94.8 95.5 96.5 96.1 96.5 Typical losses, nominal load, kW 0.5 0.9 1.5 2.4 2.9 Type - (version 3x380/ 400/ 415V) DP3120E DP3160E DP3240E DP3320E DP3480E Output power, kW/ kVA 120 160 240 320 480 Full load output current, Amp. 173 231 346 462 693 Max input current, Amp. 219 293 450 582 874 Efficiency AC to AC, 100% load, % 95.8 96.3 96.3 96.8 96.8 Typical losses, nominal load, kW 5.3 6.2 9.2 10.6 15.9 - click for 208/ 480V data DP300E rev 8.3

106 Silcon DP300E - General Specifications version 3x380/ 400/ 415V
Technical data General Specifications - (version 3x380/ 400/ 415V) Static bypass switch Built-in Communication Interface Built-in Ambient temperature 0-40 °C (above 25 °C the battery life time is reduced) Humidity Max 95% (non condensing) Protection Class IP 30 Safety,CE EN CE, Emission and Immunity EN UL 1778 Advanced bat. Monitoring Programmable Auto restart Programmable - click for 208/ 480V data DP300E rev 8.3

107 Silcon DP300E - Technical input data version 3x380/ 400/ 415V
Technical data Input voltage 3x380/ 400/ 415 Input tolerance, mains opr. ± 15% Input specifications - (version 3x380/ 400/ 415V) Input tolerance, bypass opr. ± 10% (standard) 4, 6, 8, % prog. Input frequency 50 Hz ± 6% (standard), 0.5-8% prog. Input power factor > 0.97 (load 25%), >0.99 (load 100%) - click for 208/ 480V data DP300E rev 8.3

108 Silcon DP300E - Technical output data version 3x380/ 400/ 415V
Technical data Output voltage 3x380/ 400/ 415 Output tolerance ± 1% static, sym. load Output specifications - (version 3x380/ 400/ 415V) tolerance ± 3% static, asym. load Voltage distortion Max 3% linear load ± 5% 0-100% load step Max 5% non-linear load distortion Load power factor 0.9 lead to 0.8 lag Output frequency 50 Hz (mains synchronized) ± 0.1% free funning Overload capacity, mains opr. 200% - 60 secs., 125% - 10 min. batt. opr. 150% - 30 secs., DP310E - DP 3320E bypass opr. 1000% msec. DP3480E bypass opr. 660% msec. - click for 208/ 480V data DP300E rev 8.3

109 Benchmarking 10kVA systems
Technical data Product Output power 10 kW / 10 kVA 8 kW / 12 kVA Input voltage 208 Run Time (Full Load) min. min. 8 min. min. AC to AC efficiency 94.8% 89% N/A Power Factor 0.99 0.96 Acoustic noise 57dBA Dimensions (in) High 55.12 28.10 36.00 62.00 Width 23.62 34.00 20.50 41.00 Depth 31.50 28.60 23.00 27.00 Weight 803 lbs. 920 lbs. 590 lbs. 702 lbs. APC DP300E Exide Powerware Plus 18 MGE EPS 3000 Liebert UPStation S3 - click for 208/ 480V data DP300E rev 8.3

110 Silcon DP300E: 10 - 500 KVA 3-phase
Technical data 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA (160 kVA) (320 kVA) (500 kVA) 200V, 208V & 480V 200V, 208V & 480V 480V Built-in Batteries External Batteries External Batteries - bypass 208/480V technical data DP300E rev 8.3

111 Silcon DP300E - Performances version 208V/ 480V
Technical data Type - (version 208V) DP310E DP315E DP320E DP330E DP340E Output power, kW/ kVA 10 15 20 30 40 Full load output current, Amp. 27.8 41.6 55.5 83.3 110 Max input current, Amp. 37.5 56.3 75.0 113 150 Efficiency AC to AC, 100% load, % 93.6 93.6 94.5 94.7 95.0 Efficiency AC to AC, 50% load, % 91.9 90.0 92.0 92.1 93.8 Typical losses, nominal load, kW 0.7 1.0 1.2 1.7 2.1 Type - (version 480V) DP310E DP315E DP320E DP330E DP340E Output power, kW/ kVA 10 15 20 30 40 Full load output current, Amp. 12 18 24.1 36.1 48.1 Max input current, Amp. 15.6 23.5 31.3 47.0 62.5 Efficiency AC to AC, 100% load, % 94.3 94.3 94.9 94.3 95.0 Efficiency AC to AC, 50% load, % 91.3 91.5 93.3 90.8 92.9 Typical losses, nominal load, kW 0.6 0.9 1.1 1.8 2.1 - bypass 208/480V technical data DP300E rev 8.3

112 Silcon DP300E - General Specifications version 208V/ 480V
Technical data Static bypass switch Built-in Communication Interface General Specifications (version 208V/ 480V) Ambient temperature °F (above 77 °F the battery life time is reduced) Humidity Max 95% (non condensing) Protection Class IP 30 Safety,CE EN Safety, UL 1778 EN Advanced bat. Monitoring Programmable Auto restart CE, Emission and Immunity Backfeed protection - bypass 208/480V technical data DP300E rev 8.3

113 Silcon DP300E - Technical input data version 208V/ 480V
Technical data Input specifications (version 208V/ 480V) Input voltage 3x208V/ 3x480V Voltage tolerance, mains opr. ± 15% Voltage tolerance, bypass opr. ± 10% (standard) 4, 6, 8, % prog. Input frequency 60 Hz ± 6% (standard), ± 0.5-8% prog. Input power factor > 0.97 (load 25%), >0.99 (load 100%) - bypass 208/480V technical data DP300E rev 8.3

114 Silcon DP300E - Technical output data version 208V/ 480V
Technical data Output specifications (version 208V/ 480V) Output voltage 3x208V/ 480V Output tolerance ± 1% static, sym. load tolerance ± 3% static, asym. load tolerance ± 5% 1-100% load step Voltage distortion Max 3% linear load distortion Max 5% non-linear load Load power factor 0.9 lead to 0.8 lag Output frequency 60 Hz (mains synchronized) ± 0.1% free funning Overload capacity, mains opr. 200% - 60 secs., 125% - 10 min. batt. opr. 150% - 30 secs., bypass opr. 125% - cont. bypass opr. 1000% msec. - bypass 208/480V technical data DP300E rev 8.3

115 Benchmarking 10kVA systems
Technical data Product Output power 10 kW / 10 kVA 8 kW / 12 kVA Input voltage 208 Run Time (Full Load) min. min. 8 min. min. AC to AC efficiency 94.8% 89% N/A Power Factor 0.99 0.96 Acoustic noise 57dBA Dimensions (in) High 55.12 28.10 36.00 62.00 Width 23.62 34.00 20.50 41.00 Depth 31.50 28.60 23.00 27.00 Weight 803 lbs. 920 lbs. 590 lbs. 702 lbs. APC DP300E Exide Powerware Plus 18 MGE EPS 3000 Liebert UPStation S3 - bypass 208/480V technical data DP300E rev 8.3

116 Customer references Cost of down time Performance and benefits
UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Customer references DP300E rev 8.3

117 Codan Network - Mr. Lars M. Anker Section Leader, Denmark
Insurance's - Codan Customer references Statement… "As an Insurance company, we always rate security highly and therefore the security of the data in our computers must also be at the highest level” Phrases from the statement: We protect all our business data with UPS equipment from Silcon. Before choosing Silcon we analysed 2 different suppliers. Several power-down situations has been handled by the Silcon equipment in battery back-up mode or by controlled shut-down. In the end - it is a matter of finance Codan Network - Mr. Lars M. Anker Section Leader, Denmark Codan is one of Denmark’s biggest and best consolidated insurance companies. Codan has branches throughout the country and the concern has about 2000 employees. The Codan concern comprises banking as well as the insurance business. DP300E rev 8.3

118 Banking Lloyds Bank - London
Customer Reference Bankdata - Denmark Lloyds Bank - London “Our original calculations showed that we would save USD 70,000 in electricity bills every year. That wasn’t right Bankdata, Denmark Ove vestergaard, Managing Director, Bankdata Mr. Julian Baarwell, Lloyds Bank Engineering Manager Annual savings USD 140, 000.- Installation: 2.7 megawatt of Silcon UPS supplies DP300E rev 8.3

119 Semiconductors - HITACHI
Customer references Peter Nikonowitch says… “Quality and safety comes first” “10 milliseconds of power down is fatal for a whole production batch. Beside the power security we have achieved essential savings in power consumption. The technology and the environmental aspects we have achieved with the Silcon DP300E product has also been decisive”. Peter Nikonowitch Hitachi, Tyskland One of the biggest supplier of electronic components in the world. employees 6 billion USD in turn over Hitachi Semiconductor GmbH DP300E rev 8.3

120 IT Services IBM Megacentre in Portsmouth UK
Customer references IBM chose Silcon DP300E systems IBM´s European and Middle East/ African organization have put their trust in the safety of their business data in the hands of APC/Silcon-UPS. “If you have 6 Mega watt to back-up the efficiency of the UPS system is essential.” “We can’t afford any drops at all” Chris Hayes, UPS Consultant IT Infrastructure Services Installation: 6 x DP3440 in parallel Capacity: 2 x 2.64 MW Additional: 540 kW on vital systems 12 minutes back-up at a load of 6 MW 2.5 MW generator back-up DP300E rev 8.3

121 SHELL refinery in Fredericia
Chemicals Shell Customer references Shell in Frederica has the most advanced control system in the world ! “We power ensure the whole control center with the Silcon UPS systems. Most essential for us was the low heat emission - meaning lower installation and operation costs”. SHELL refinery in Fredericia SHELL, Danmark

122 Air transportation RDM Lufthansa
Customer references Statement… “For RDM Lufthansa security and reliability are very important. With round-the-clock working and on-line access to RDM Lufthansa's host system in Germany, a power failure would have very serious financial consequences for the airline company”. RDM Lufthansa, India “We simply can't afford to go down because of a power cut. APC´s Silcon UPS systems gives us reliability and we get the service we need through El-Pan, APC's partner in India”. DP300E rev 8.3

123 Hospitals Länssjukhuset Ryhov Hospital
Customer references “It is of vital importance for hospitals to have high quality and constant power supply. Without power - it is impossible for doctors to help many of there patients - babies in incubators, patients undergoing surgery or dialysis etc. It is obvious that we put extreme demands on our UPS supplier” “I feel secure in having chosen Silcon and I know that each UPS system is produced with care and absolute precision Moreover the Silcon equipment is environmentally friendly with extreme high efficiency” Mr. Bengt Jönsson Technical Engineer Länssjukhuset Ryhov is a Swedish hospital. The 200,000 m2 hospital was opened in 1988 and today employs 3700 people. DP300E rev 8.3

124 Banking Bankdata - Denmark
Silcon Technology Customer references Statement… “We have always maintained the policy that one power cut per year is acceptable only. But since we have recently suffered three successive power cuts, we took the decision to install our own emergency power supply”. The project: 396 batteries - 11 tons - 10 minutes back-up time 4 Silcon DP300E UPS systems 1 Diesel generator - takes over after 30 seconds Ove Vestergaard, Bankdata, Managing Director, … ”We have estimated that in 1996 alone, the Silcon installation has saved us some USD 4 million worth of losses by protecting critical infrastructure against power failures” Erik Nielsen, Bankdata’s Installation Manager says... With the Silcon equipment we have installed some of the best electrical energy transformer systems with full back-up service. Bankdata can now be added to an already impressive client list. Bankdata is a data centre for 18 banks - employing 225 people - supporting banks with modern EDP systems. Bankdata, Denmark DP300E rev 8.3

125 Banking Customer references American Express National Bank of Slovakia
Lloyds Bank, UK BGZ Poland Qingdao City Bank, China Czech National Bank Pekao, Poland Orel Bank, Russia Crediplus, Portugal UBS, Switzerland Inter-Europa Bank, Hungary Slovak Stock Exchange Raiffeisenbank, Germany Generali, Ireland Citibank, Denmark Chase Manhattan Bank, USA Den Danske Bank, Denmark Bank of New Zealand Bloomberg, Japan BCA, Indonesia Dresdner Bank, Germany National Bank of Slovakia Bank OTP, Hungary Xiosbank, Greece Pacific Finance,Thailand Ulster Bank, Ireland MBNA Bank, UK SBG, Switzerland Alliance & Leicester, UK FINIbanco, Portugal Jordan Gulf Bank Allied Irish Bank, Ireland Paribas Sydbank, Denmark Deutsche Bank, Germany DP300E rev 8.3

126 Tele communication Telia - UK
Customer references "The main reason for choosing Silcon UPS systems over the competitors considered, was the electronics. The electronics gives advantages and behaves in a much more structured way. This meets the needs of the Telecoms. Mr. Paul Mulvenne Facilities Manager “The Silcon UPS is like having a gentle giant hidden in your cupboard that you can pull out when ever you fancy. So we are very happy with the Silcon product". ”APC´s Silcon products are probably going to the front in UPS support for telecommunications” DP300E rev 8.3

127 Tele communications Customer references Portugal PTT Nokia Finland PTT
Ericsson LM Telecom Eireann Motorola MCI USA TeleDanmark Sonofon France Telecom Telecom New Zealand T.T. Mobiles India AT&T Polish Telecom Swiss PTT Global One Alcatel Swissphone TeleDanmark Mobil VEW Telnet D Fujitsu British Telecom Polish Mobile Phone Teletas Turkey Telex-Exchange Indonesia City Telephone China Taiyan PTT China PTT China GEC Alsthom Bosch Telecom Telesystem Mobilfunk TMI Telecom Italia Telia Dutch PTT Orange Telecom VODAphone Deutsche Telecom Post Ungarn Tele Nordia Telecom Malaysia DP300E rev 8.3

128 Installation Headlines: Cost of down time Efficiency Economy
Parallel operation Advanced battery management Power Control - “Diesels best friend” Fans Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Headlines: Cost of down time Efficiency Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Fans Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Installation DP300E rev 8.3

129 Installation of DP300E Consider: Where to find information: Size
Is there enough space on the installation site? Will it go through the door? Is there free space for servicing and operation? Weight Will the floor carry the load? Can the lift carry the load? How can it be lifted off the pallet? Fuses Which fuses to use in installation? Cables What cable size to use in the installation? And where to connect to the DP300E (cable entry)? Where to find information: Spec Sheet Installation Guide Quick Reference Data Sheet DP300E rev 8.3

130 Where to find information:
Installation of DP300E Installation Consider: Heat dissipation: • Ensure correct dimensioning of the air conditioning system Diesel generators: • Due to the sinusoidal input current a diesel generator of only 1.3 times the size of the DP300E can be used. (A diesel for a traditional UPS must be 3-5 times the size of the UPS) • For very sensitive diesels the DP300E series can be programmed for soft start (diesel modification). Where to find information: Installation Guide Quick Reference Please note on ordering sheet DP300E rev 8.3

131 Installation of DP300E Consider: Parallel operation: Batteries:
Parallel to increase output power. Redundancy to increase safety. Up to four standard systems can be paralleled (only parallel boards needed). With external static switch up to nine systems can be paralleled (parallel boards and external static switch needed. Parallel systems can have common or separate batteries. Batteries: Configuration sheet for Johnson control batteries are available. Battery dimensioning for special applications has to be handled from case to case. Where to find information: Installation Guide APC Tech Support DP300E rev 8.3

132 Review Headlines: Cost of down time Headlines: Efficiency
Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Fans Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Headlines: Cost of down time Performances and benefits Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Cost of down time Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Review DP300E rev 8.3

133 ? What does it mean ? ....On-line UPS ? ....High efficiency ?
Review ? ....On-line UPS ? ....High efficiency ? ....Full kW Rating ? ....No mains repercussions ? ....Input power factor correction ? DP300E rev 8.3

134 Delta-conversion UPS systems...
Silcon DP300E benefits... Review Delta-conversion UPS systems... Highest up-time on IT equipment Low operation costs Low installation costs More protection capacity Environmentally friendly UPS system DP300E rev 8.3

135 “Close to perfect” Silcon DP300E benefits... Silcon DP300E
Review Silcon DP300E Delta Technology “Close to perfect” DP300E rev 8.3

136 Questions End of presentation Cost of down time
Performance and benefits UPS power factor Economy Parallel operation Advanced battery management Power Control - “Diesels best friend” Communication and operations Green Power aspects Service Accessories Technical data Customer references Installation considerations Review Questions DP300E rev 8.3