Presentation is loading. Please wait.

Presentation is loading. Please wait.

UL/ANSI/NEMA Low Voltage Circuit Breakers.

Similar presentations


Presentation on theme: "UL/ANSI/NEMA Low Voltage Circuit Breakers."— Presentation transcript:

1 UL/ANSI/NEMA Low Voltage Circuit Breakers

2 “System” Consideration
Product Standards and Certification Installation Codes Safe Products and Safe Installations Inspection and Enforcement (verification)

3 UL Standards for LV components
UL 489: Molded Case Circuit Breakers UL 1066: LV Power Circuit Breakers UL 98: Enclosed and Deadfront Switches UL 508: Industrial Control Equipment

4 UL Standards for LV Assemblies
UL 67: Panelboards UL 891: Switchboards UL 1558: LV Switchgear UL 845: Motor Control Centers UL 857: Busway UL 508A: Industrial Control Panels

5 IEC Standards for LV Components
IEC 60947: LV Switchgear and Controlgear Part 1: General rules Part 2: Circuit breakers Part 3: Switches, disconnectors… Part 4 series: Contactors and motor- starters Part 5 series: Control circuit devices and switching elements Part …

6 IEC Standards for LV Assemblies
IEC 61439: LV Switchgear and Controlgear Assemblies Part 1: General rules Part 2: Power Switchgear Part 3: Distribution boards operated by ordinary persons Part 4: Construction sites Part 5: Distribution in public networks Part 6: Busbar Trunking Systems (Busways) Part 7: Marinas, camping sites, market squares, EV charging

7 National Electrical Code, NEC
NFPA 70, contains “installation” rules Cable connections = AWG sizes Wire bending spaces Enclosure type designations Grounding Working spaces Creepage/Clearance distances Temperature rises Mentions “Listed” products References “product” Standards (Annex A) The NEC is the basis for your large installed Petro industry

8 UL conformity assessment
UL Listing provides Independent confirmation of original design On-going factory inspections Periodic follow-up testing Market surveillance

9 Support the installed “system”
UL Components UL Assemblies IEC Components IEC Assemblies SAFE

10 UNSAFE Do not “intermix” UL Components IEC Components UL Assemblies
IEC Assemblies

11 System Considerations - Summary
Support your installed electrical infrastructure Concerns extend beyond individual components Need alignment with Installation requirements Certification confirms initial & continued compliance Do not intermix IEC and UL products, it will compromise safety!

12 Background/Evolution: LV Power Breakers
UL 1066, Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures Robust Large commercial & industrial applications

13 Low Voltage Circuit Breaker Standards IEC & UL
Low Voltage Switchgear and Controlgear-Part 2 Circuit Breakers UL 1066 UL Standard for Low Voltage AC and DC Power Circuit Breakers used in Enclosures Air (Power) Circuit Breakers Moulded Case Circuit Breakers UL 489 UL Standard for Molded-Case Circuit Breakers IEC 60898 Circuit-breakers for overcurrent protection for household and similar installations

14 Key differences Power Circuit Breakers have compared to Molded Case Circuit Breakers
Electronic Trip Only Used Primarily in Draw-out Switchboards Serviceable and Maintainable Typically used upstream from Molded Case Circuit Breakers Provide a Higher Level of Selective Coordination Stored Energy Mechanism

15 Many Standards differences between IEC 60947-2 and UL 1066, including
Testing Approach For example, Short Circuit Interrupting Capability Performance Requirements For example: Temperature Rise Overload Follow Up Test Requirements For example, periodic UL 1066 Follow Up Testing

16 Power Circuit Breakers: Short Circuit Capability
IEC UL 1066 Significant clause is 4.4: Utilization Categories Category B “Determine rated short time withstand current” Annex H Single Pole Interrupting – Optional Ics: Rated Breaking Capacity (Seq. II) Icu: Rated Ultimate Capability (Seq. III) References ANSI/NEMA C37.50 for: Short-Time Current Duty Cycle Carry fault current for two 0.5 second periods Short-Circuit Current Duty Cycle Single Pole Test at 87% of Interrupting Capacity (ANSI C37.50 Table 4) Short Circuit Current Tests required in each Test Sequence (C Table 1) ANSI/NEMA C37.50 contains the testing specifics and is the “test standard” UL 1066 is the Certification standard which simply refers to ANSI C37.50 for tests UL requires defined/vigorous short circuit verifications and single pole interruption.

17 Philosophy different for temperature tests
Power Circuit Breakers: Temperature IEC UL Maximum Allowable Temperature Rise 80°C Enclosure not required, sample previously tested in Seq. I and Seq. II 55˚C Tested in the Enclosure, tested on a new sample (C37.50 Table 1 Sequence V) Maximum allowable Temperature Rise At the Circuit Breaker Contacts No value specified but no damage to adjacent parts (Table 7 Note a) 85°C These are the MAXIMUM temperatures permitted under completely stabilized conditions UL has lower allowable temperature rises Philosophy different for temperature tests

18 Power Circuit Breakers: Overload Capability
IEC UL Overload test requirements Required for 630A and less, optional above 630A ( and Test Sequence I) Required for ALL circuit breakers (ANSI C37.50 Table 1, Seq. 1) Tests after Overload Short Circuit Test not required and not part of test sequence Short Circuit Test required UL always requires overload, also Requires short circuit test after overload

19 Power Circuit Breakers: Conformance Testing/Conformity Assessment
IEC UL UL Third-Party Witness of Conformance Testing UL Factory Surveillance UL “procedures” document the construction/components for on-going compliance UL periodic Follow-up Testing based on production volume or number of years (ANSI C37.50 Table 7) Conformance to IEC Standard (CE Mark) typically justified solely by manufacturer’s self declaration Third-party certification assures independent verification & ongoing conformance

20 Emerging technology: Addressing Arc Flash Hazards
Data is available to apply UL low voltage circuit breakers to limit arc flash energy

21 Traditional Circuit Protection
Circuit breakers were originally intended to protect the installed conductors: Protect & prevent possible damage for operating beyond their capability. Cut-off current below the cable damage curves.

22 Arc Flash Hazards

23 IEEE 1584, Guide for Performing Arc-Flash Hazard Calculations
Calculate Incident energy Use fault current level and interruption time of the overcurrent device. Circuit breaker calculation methods do not account for their current limiting aspects! Published Papers referencing circuit breaker arc flash applications are: “Molded-Case Circuit Breakers reduce Arc-Flash Hazard Impact” NEMA (available for free download from the NEMA Website) “Understanding IEEE 1584 Arc-Flash Calculations”, K. J. Lippert, D. M. Colaberardino, and C. W. Kimblin, IEEE IAS Magazine, May/June 2005. Applying Low Voltage Circuit Breakers to Limit Arc-Flash Energy”, G. Gregory and K. J. Lippert, IEEE PCIC, September 2006

24 Comparison of MCCB arc test results
Incident Energy at Bolted Fault Current (kA) Min Mid Max 250 A MCCB with Thermal - Magnetic Trip Unit Bolted fault current Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm 2 ) 1584 & Trip Curve Measured Incident Energy ( Cal/cm 3.7 kA N/A 1 27.6 0.11 35 kA 1.7 0.9 0.15 100 kA 4.7 1.8 0.13 400 A MCCB with Thermal Incide nt Energy (Cal/cm 6 kA 72 0.12 0.7 0.2 1.4 0.20 600 A MCCB with Thermal Incident Energy (Cal/cm 9 kA 46 1.22 2.3 1.1 0.78 5.7 0.36 800 A MCCB with Thermal Me asured 12 kA 61.4 0.86 1.14 65 kA 3.9 2.8 1.05 1200 A MCCB with Electronic Trip Unit 20 kA 218 1.86 3.5 1.20 9.4 5.8 1.64 2500 A MCCB with Electronic Trip Unit (Cal /cm 110 3.96 7.7 5.4 3.48 11.5 6.5 2.12 1. N/A represents “Not Applicable” because the parameters are outside the range of the IEEE 1584 Table E.1 generic equation. Test data from IEEE paper by 2 major US MCCB manufacturers tests

25 Conclusions from Molded Case Circuit Breaker arc flash testing
In the instantaneous region, tested incident energies are significantly lower than calculated values due to: Actual arcing time Current reduction by the circuit breaker (particularly for current limiting circuit breakers)

26 Zone Selective Interlocking (ZSI)
Many modern circuit breakers have electronic trip units which make them more “intelligent” Electronic trips with ZSI allows breakers in the same zone to communicate with each other ZSI bypasses the preset short delay time (and ground fault delay time when available) on the upstream circuit breaker closest to the fault, which then trips with no intentional delay ZSI is one method of getting breakers to operate instantaneously. It’s applicable to many breakers which have electronic trip. Upstream & downstream breakers in the same “zone” communicate with each other During a fault condition, with ZSI it bypasses the Short Delay Time of the upstream breaker. Trips with NO intentional delay. Faster tripping = less arc flash energy and STILL MAINTAINS SELECTIVE COORDINATION so that only the device closest to the fault opens!

27 Zone Selective Interlocking (ZSI)
When a fault occurs at point X... X Feeder 1 Circuit Breaker Feeder 2 Feeder 3 Main 1 I sense trouble! All is OK here, so I’m quiet. All is OK here, so I’m quiet. All is OK here, so I’m quiet. Zone A The following are a series of graphics illustrations to help explain the concept of ZSI. First Fly-in: In this example the fault occurs at point X. Second-5th Fly-ins: The communications between the downstream & upstream breakers NOTE: The words are not the actual communication (as our electronics guys have corrected me). I suggested them to more easily understand the concept. Circuit Breaker Circuit Breaker

28 Zone Selective Interlocking (ZSI)
But with ZSI… since none of my downstream buddies are telling me that they sense trouble, I know not to wait at all, and open as quickly as I can! Feeder 1 Circuit Breaker Feeder 2 Feeder 3 Main 1 Without ZSI, I’d normally wait for my Short Delay time, and then open! X Zone A Without ZSI: This is the standard situation when Short Delay settings are used. With ZSI: The Short Delay setting is bypassed. No INTENTIONAL delay! Circuit Breaker Circuit Breaker

29 Zone Selective Interlocking (ZSI)
However, when a fault occurs at point XX... XX Feeder 1 Circuit Breaker Feeder 2 Feeder 3 Main 1 I sense trouble! I sense trouble too! Hey upstream buddy, hang in there, I’ve got it! All is OK here, so I’m quiet. All is OK here, so I’m quiet. Zone A Further example to understand the REAL advantage: When the fault occurs at point XX (on the load side of downstream device). Fly-ins (only 1 click required) Again there is communication between the devices. Next Fly-in: MAJOR ADVANTAGE is Coordination is Maintained, while assuring Quick tripping! Coordination Is Maintained! Circuit Breaker Circuit Breaker

30 ZSI Arc Flash Example X Without ZSI = 0.5 S: With ZSI = 0.08 S:
Main 1 Circuit Breaker Short Delay= 0.5S X 35kA fault current * Using IEEE 1584: 480V-35kA, MCC, 18” from Arc Circuit Breaker Circuit Breaker Circuit Breaker Short Delay= 0.3S Short Delay= 0.3S Short Delay= 0.3S Feeder 1 Feeder 2 Feeder 3 Here is an example of how ZSI of breakers reduces Arc Flash Energy. Repeat the delay settings: Upstream = 0.5S, Downstream = 0.3 S. Fly-In 1: Explain where the fault occurs. This example is based upon using IEEE 1584 calculation of 480V, 35Ka, MCC, 18” from Arc Fly-In 2: WITHOUT ZSI - .5S = 43.7Cal = No PPE, so find other alternatives Fly-In 3: WITH ZSI – 0.08S = 7 Cal = 2 PPE, which is a simple FR Shirt, Pants & Cotton underwear. TAKE AWAY: ZSI reduces arc flash energy associated with circuit breakers, while maintaining coordination. Without ZSI = 0.5 S: 43.7* Cal/cm2 Greater than Cat. 4 PPE! FIND ALTERNATIVES! With ZSI = 0.08 S: 7.0* Cal/cm2 FR Shirt & Pants + Cotton underwear Cat. 2 PPE

31 Arc-reducing maintenance switching
Manually or Automatically enables an instantaneous pickup Trip Times May Vary Between Manufacturers Some may be same as Instantaneous Some my be faster than Instantaneous Reduces arc energy to downstream equipment/personnel Limits energy available during maintenance EXAMPLE: Normal settings calculates to 10.7 cal (Cat. 3) With Arcflash Reduction Maintenance Switch 2.2 cal (Cat. 1)

32 Arc flash mitigation system
When activated, this technology continuously monitors current and voltage to identify an arc flash. When an arc flash occurs, the arc is automatically dealt with, without changes to the circuit breaker. Sometimes referred to as “crowbar systems”

33 Summary of UL circuit breaker applications to reduce arc flash energy
Use Arc flash energy values published by the circuit breaker manufacturer Zone Selective Interlocking Arc Reduction Maintenance Switch Arc Flash Mitigation Systems Summary of CB applications to reduce arc flash. USA developed technologies. Adjust settings (want instantaneous operation) Use ZSI to reduce time (& corresponding energy) while maintaining selective coordination Use CL breakers: specifically marked, drastically reduces let-through energy

34 Emerging technology: PV Circuit Breakers
UL 489B, Outline of Investigation for Molded-Case Circuit Breakers …for Use with Photovoltaic (PV) Systems

35 UL 489B and IEC UL 489B: First published July, 2010
Several manufacturers have UL Listed products IEC No published requirements yet for PV breakers CD circulated

36 UL 489B PV Circuit Breaker Requirements
1500 V dc capability Rated/marked for 50 C Vigorous dc current tests Evaluated for reverse direction current

37


Download ppt "UL/ANSI/NEMA Low Voltage Circuit Breakers."

Similar presentations


Ads by Google