1 Automation and DrivesIEC OEM Control Components Siemens Energy & Automation, Inc. iniature circuit breakers to UL 489 M

2 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Miniature Circuit Breakers to UL 489 What is UL 489? UL 489 is the UL Standard for Safety for Molded-case Circuit Breakers, Molded-case Switches and Circuit Breaker Enclosures. The requirements are specifically intended to provide Service Entrance, Feeder and Branch Circuit Protection in accordance with the National Electrical Code, NFPA 70. The 5SJ4 series of Miniature Circuit Breakers meet the requirements for Branch Circuit or Feeder Protection and are intended to protect electrical wires from catching fire in an application.

3 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 There are three variations of the Siemens 5SJ4 Miniature Circuit Breaker Series... 5SJ4...-.HG4 2 5SJ4…-.HG4 1 5SJ41..-.HG4 0 5SJ4...-.HG4. Mini Circuit Breakers (mCB)

4 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Catalog Number Nomenclature 1) 5SJ HG42 a b c 2) d e a Frame Style b Number of Poles c Rated Current Code 2) d Tripping Characteristic Curve e Version HG40: 240 VAC, Same Polarity HG41: 240 VAC HG42: 480Y / 277 VAC 1) For specific nomenclature designations refer to the 5SJ4…-.HG4. Product Profile 2) Exceptions are 05, 11, 14, 15, & 18 5SJ4...-.HG4. Mini Circuit Breakers (mCB)

5 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5SJ4...-.HG4. Mini Circuit Breakers (mCB) 1-Pole 1-, 2- & 3-Pole Thermal / magnetic overcurrent protection Intended for General Use (Branch Circuit Protection) UL Listed (UL 489) Certified to Canadian Standards (CSA 22.2 No. 5-02) cULus to UL File E Include a manual means for opening a circuit Not ambient compensated 5SJ4...-.HG4 0 5SJ4...-.HG4 1 5SJ4...-.HG4 2 5SJ41..-.HG42

6 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5SJ4...-.HG4. Mini Circuit Breakers (mCB) B, C & D C & D (Trip Characteristics per IEC/EN ) UL 489 Rated Voltage – HG VAC Max. 1-Pole 60 VDC Max. 1-Pole UL 489 Rated Voltage – HG VAC Max. 60 VDC Max. 1-Pole 125 VDC Max. 2- & 3-Pole UL 489 Rated Voltage – HG VAC Max. 1-Pole 480Y VAC Max. 2- & 3-Pole 60 VDC Max. 1-Pole 125 VDC Max. 2- & 3-Pole 5SJ4...-.HG4 0 5SJ4...-.HG4 1 5SJ4...-.HG4 2 5SJ41..-.HG42

7 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5SJ4...-.HG4. Mini Circuit Breakers (mCB) 5SJ41..-.HG42 NSJ HSJ NSJ HSJ Type 10 kA25 – 63 AD 14 kA0.3 – 20 AD 10 kA45 – 63 AC 14 kA0.3 – 40 AC 10 kA DC 60/125 VAC 240 V Interrupting RatingI n (A)Tripping Characteristic 5SJ4…-.HG41 NSJ Type 10 kA 0.3 – 32 A D 10 kA0.3 – 40 AC 10 kA DC 60/125 VAC 480Y V Interrupting RatingI n (A)Tripping Characteristic 5SJ4…-.HG42 NSJ HSJ NSJ HSJ Type 10 kA25 – 63 AD 14 kA0.3 – 20 AD 10 kA45 – 63 AC 14 kA0.3 – 40 AC 10 kA DC 60 VAC 240 V Interrupting RatingI n (A)Tripping Characteristic 5SJ4…-.HG40 B NSJ 14 kA 0.3 – 63 A

8 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5SJ4...-.HG4. Mini Circuit Breakers (mCB) 5SJ41..-.HG42 Technical Specifications

9 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5SJ4...-.HG4. Mini Circuit Breakers (mCB) Dimensions

10 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Miniature Circuit Breakers per UL All 5SJ4 Designs have the following features. Features to UL 489 – Suitable for Branch Circuit and Feeder Protection Applications UL Listed and Certified to Canadian Standards (cULus, File E243414, Volume 1, Section 1) HACR Rated 40° C Calibration Base (Industrial Applications) Can be used for “field wiring” applications; AWG 14 to AWG4, Copper (Cu) Only Suitable for “Reverse Feed” applications Visible Indicator for ON and OFF/Trip Finger Safe Design DIN Rail Mounting (Standard 35 mm) Identical Wire Screw Connections on Line and Load Sides Smaller Size than Traditional MCCBs

11 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Miniature Circuit Breakers per IEC 5SJ4 Miniature Circuit Breakers are also CE marked according to EN and EN making them suitable for use in International applications. Features include: 30° C Calibration Base Maximum Rated Voltage of 440 VAC / 60 VDC per pole (EN 60898) High Interrupting Rating (I cu ) of up to 15,000 Amps (EN ) Tripping Characteristics (B, C and D depending on the device selected) B: Designed for the protection of computers, electronic equipment, …, etc. C: Designed for general device protection in control circuits and all other miniature circuit breaker systems D: Designed for high inrush loads

12 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Accessories to UL 489 ProductDescriptionPlanned for… According to norm Auxiliary switches 1NO + 1NC 2NO 2NC Available Now!UL 489 Fault signal contacts Shunt trips 24 – 60 V AC/DC 110 – 480 V AC Available Now! UL 489 Busbars 1, 2 and 3 poles with 6,12 or 18 terminals Available Now! UL 489 Feeder terminals Terminals up to 115 A Available Now!UL 489 Busbar touch protection Accessories for 5SJ4…-.HG4. mCBs

13 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Accessories for 5SJ4…-.HG4. mCBs 5SJ4 mCB Auxiliary Contact (AS) 5ST301.-0HG Fault Signal Contact (FC) 5ST302.-0HG Shunt Trip (ST) 5ST303.-0HG 5ST36 Busbar 5ST36 Busbar Accessories

14 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5SJ4_HG MCB Accessories 5ST3030-0HG 5ST3031-0HG Shunt Trip (ST) 110 – 480 VAC 24 – 60 V AC/DC Used for the Remote Tripping of a mCB 5ST3020-0HG 5ST3021-0HG 5ST3022-0HG Fault Signal Contact (FC) 1NO + 1 NC 2 NO 2 NC Signals the automatic tripping of the mCB & the Trip Mechanism‘s Position 5ST3010-0HG 5ST3011-0HG 5ST3012-0HG Auxiliary Switch (AS) 1NO + 1 NC 2 NO 2 NC Signals the mCB’s Trip Mechanism Position Catalog No.Abbrev.Contact Arrangement Brief DescriptionPicture Auxiliary Devices to UL 489 UL File No. E321559

15 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Auxiliary Switch (AS) and Fault Signal Contact Advantages Siemens Miniature Circuit Breakers do not have to be derated Siemens Auxiliary Switch and Fault Signal Contacts are UL Listed and Certified to Canadian Standards to 480 VAC maximum. Many Competitive Auxiliary Switches and Fault Signal Contacts when used with a MCB require the MCB to be derated to 300 VAC Maximum. This means that many competitive MCBs DO NOT have Auxiliary Devices available at 480 VAC. Siemens 1NO + 1NC contacts are separate and can be used at the same time Many Competitive Auxiliary Switches have a Form C contact. A Form C contact can be used as a NO or a NC, but not both at the same time. 5SJ4_HG MCB Accessories

16 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5SJ4_HG MCB Accessories Selection and Assembly 5SJ4 MCB Select any 1-, 2- or 3- pole 5SJ4…-.HG4. Miniature Circuit Breaker and ensure that the trip mechanism is in the down position Select any 5ST30..-0HG Auxiliary Accessory and ensure that the trip mechanism is in the down position. Also ensure that the metal fastening strips are moved as far right as possible Metal Fastening Strips 5ST30.. Auxiliary Trip Mechanism

17 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5SJ4_HG MCB Accessories Selection and Assembly Find the locating pin on the accessory and place it into the locating pin hole in the miniature circuit breaker. Locating Pin Secure both metal fastening strips.

18 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Accessories for 5SJ4…-.HG4. mCBs Auxiliary Devices to UL 489

19 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Dimension (mm) Accessories for 5SJ4…-.HG4. mCBs Auxiliary switch, Fault signal contact Shunt trip

20 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Accessories for 5SJ4…-.HG4. mCBs

21 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Accessories for 5SJ4…-.HG4. mCBs Busbar to UL 489 1) Length (mm) Order No. Busbars to UL 489 1) For use with all 5SJ4…-.HG4. Fixed lengths, cannot be cut. 1-Pole Busbar For 6 MCB, 1-Pole For 12 MCB, 1-Pole For 18 MCB, 1-Pole 2-Pole Busbar For 3 MCB, 2-Pole For 6 MCB, 2-Pole For 9 MCB, 2-Pole 3-Pole Busbar For 2 MCB, 3-Pole For 4 MCB, 3-Pole For 6 MCB, 3-Pole ST3663-0HG 5ST3663-1HG 5ST3663-2HG 5ST3664-0HG 5ST3664-1HG 5ST3664-2HG 5ST3665-0HG 5ST3665-1HG 5ST3665-2HG UL File No. E  All unused busbar terminals must be covered with touch protection cover 5ST3666-1HG.

22 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Accessories for 5SJ4…-.HG4. mCBs Order No. Connection terminal to UL 489 For use only with 5SJ4…-.HG4. Infeed to MCBs 35mm 2 (14 – 2 AWG) Infeed to Busbars 50 mm 2 (14 – 1 AWG) Touch protection covers for Busbars to UL x 1 pin 5ST3666-0HG 5ST3666-2HG 5ST3666-1HG Busbar to UL 489 1) UL File No. E ST3666-0HG 5ST3666-2HG 5ST3666-1HG 1) 1) All unused busbar terminals must be covered with touch protection covers 5ST3666-1HG.

23 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Busbar & Connection Terminals to UL 489 Accessories for 5SJ4…-.HG4. mCBs

24 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Dimension (mm) Accessories for 5SJ4…-.HG4. mCBs

25 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5ST3665-1HG Application Example : Center Feed using Busbar Terminal Connection 3-Pole Busbar with 3-Pole MCB Insert 3-Pole / 3-Phase Busbar into the terminals of a 3-Pole MCB and tighten the screw terminals of the MCB. Always cover all exposed busbar terminals with touch protection covers 5ST3666-1HG Connect one end of terminal connector 5ST3666-2HG to a busbar terminal and the other end to a power conductor and tighten the terminal connector screws. Accessories for 5SJ4…-.HG4. mCBs

26 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 5ST3665-1HG Application Example : Center Feed using Busbar Terminal Connection 3-Pole Busbar with 3-Pole MCB The busbar and the terminal connectors are rated at 115 A maximum. Using the center feed method allows up to 115A maximum to flow. The sum of the current per pole in both directions must not be greater than 115 A. Connect the other end of the power conductors to the power source Accessories for 5SJ4…-.HG4. mCBs

27 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Application Example : End Feed using MCB Terminal Connection 3-Pole Busbar with 3-Pole MCB Connect one end of a power conductor to the MCB Terminal Connector and tighten the screw. Connect the other end of the conductor to the power source. Insert 3-Pole / 3-Phase Busbar and MCB Terminal Connector into the terminals of a 3-Pole MCB and tighten the screw terminals of the MCB. 5ST3665-0HG Remember to always cover all exposed busbar terminals with touch protection covers 5ST3666-1HG Accessories for 5SJ4…-.HG4. mCBs

28 IEC OEM Control Components 5SJ4 Miniature Circuit Breakers & Accessories September SJ4_UL 489_Overview_September09 Application Example : End Feed using MCB Terminal Connection 3-Pole Busbar with 3-Pole MCB The busbar and the MCB terminal connectors are rated at 115 A maximum per pole. 115A max. per pole Always cover all exposed busbar terminals with touch protection covers 5ST3666-1HG Accessories for 5SJ4…-.HG4. mCBs

29 Automation and DrivesIEC OEM Control Components Siemens Energy & Automation, Inc. iniature circuit breakers to UL 489 M


Download ppt "Automation and DrivesIEC OEM Control Components Siemens Energy & Automation, Inc. iniature circuit breakers to UL 489 M."

Similar presentations


Ads by Google