PREINCIDNET PREPARATION. OBJECTIVES Properly calculate required fire flow for structures using the National Fire Academy Fire Flow Formula. FIRE FLOW.

Similar presentations


Presentation on theme: "PREINCIDNET PREPARATION. OBJECTIVES Properly calculate required fire flow for structures using the National Fire Academy Fire Flow Formula. FIRE FLOW."— Presentation transcript:

1 PREINCIDNET PREPARATION

2 OBJECTIVES Properly calculate required fire flow for structures using the National Fire Academy Fire Flow Formula. FIRE FLOW REQUIREMENTS FIRE FLOW FORMULA Module 5 Overview

3 OBJECTIVES Given the required fire flow for a structure, estimate the personnel required for offensive operations. RESOURCE CAPABILITY AND DISTRIBUTION DATA Module 5 Overview

4 OBJECTIVES Given a scenario, properly complete a National Fire Academy Quick Access Prefire Plan QUICK ACCESS PREFIRE PLANNING Module 5 Overview

5 FIRE FLOW REQUIREMENTS Fires extinguished by absorbing the heat with water Application of water will: –Absorb heat –Reduce temperature –Extinguish fire

6 FIRE FLOW REQUIREMENTS To extinguish a fire, the quantity of water (gpm) must exceed the heat (Btu’s) being produced.

7 FIRE FLOW FORMULA QUICK CALCULATION Basic Formula: Length x Width = GPM 3

8 CALAULATES THEORETICAL FIRE FLOW Large amounts of heat absorbed Reduces temperature below ignition temperature Fire is “blacked-out” ready for overhaul

9 WITH HIGH PERCENTAGES OF INVOLVEMENT INTERIOR OPERATIONS ARE NOT POSSIBLE 100% involvement answer is theoretical Starting point for realistic flow rate Starting point for defensive operations Tactical operations must be evaluated

10 ORIGIN OF FORMULA Empirical formula developed by NFA development team. Study of fire flow at fire situations

11 BASIC FORMULA Basic Formula: L x W = GPM 3 Flow for one floor fully involved. Estimate Length/Width to nearest 10 feet. Multiply L x W then divide by 3. Theoretical fire flow for 100% involvement.

12 Insert 1 story 40’x 30’ structure- no fire 30 X 40

13 BASIC FORMULA Quick calculations at the scene Calculates water required for: –Confinement, Extinguishment, Back-up lines

14 Insert 50’ x 30’ building with dimensions on slide 50x30

15 MULTIPLE STORIES Multiply base fire floor by number of floors

16 Insert 2 story house (50 ft X 30 ft /3) x 2 = FULLY INVOLVED = 1000 GPM 50% INVOLVED = 500 GPM 25 % INVOLVED = 250 GPM

17 EXPOSURES GPM = LENGTH X WIDTH + EXPOSURES 3

18 WATER FOR EXPOSURE PROTECTION Interior exposures - floors above the fire on “fire-resistive” construction Exterior exposures - buildings or other objects

19 EXPOSURE PROTECTION Up to 4 floors above the fire Buildings or other objects 0 to 30’ -- usually an exposure 30’ to 100’ -- could be an exposure 100’ or more -- usually not an exposure

20 You must make the final determination of exposure based on observed conditions

21 EXPOSURE PROTECTION Fire area adjacent to a fire wall Should the exposure become involved - calculate flow as new fire building

22 EXPOSURE PROTECTION Exposure “C” 25% Exposure “B” Fire Exposure “D” 25% Building 25% Exposure “A” 25%

23 Exposure Fire Building Exposure “B” “D” Base Flow = 1000 GPM Exposure “B” = 250 GPM (25%) Exposure “D” = 250 GPM (25%)

24 INTERIOR EXPOSURE ( Fire Resistive Structure) 5 EXPOSURE 25% 4 EXPOSURE 25% 3 EXPOSURE 25% 2 EXPOSURE 25% 1 FIRE FLOOR

25 EXPOSURE PROTECTION “Fire Resistive” Structure 25% Exposure “B” 250 gpm 25% Exposure “D” 250 gpm 3 Exposure 250 gpm (25%) 2 Exposure 250 gpm (25%) 1 Fire Floor Total Fire Flow = 1000 GPM Total Exposure Flow = 1000 GPM Total Flow Required = 2000 GPM

26 PERCENTAGE OF INVOLVEMENT GPM = L x W + EXPOSURE x PERCENT OF INVOLVEMENT 3

27 PERCENTAGE OF INVOLVEMENT Fire Building Exposure “D” 1000 GPM 250 GPM (25%) 100% Involvement = 1250 GPM 75% Involvement = 950 GPM (1250 x.75) 50% Involvement = 625 GPM (1250 x.50) 25% Involvement = 325 GPM (1235 x.25)

28 Individual Activity 5.1 Fire Flow Calculation

29 15’ 20’ Fire building is 30’x 50’ Exposure B Fire Building 20’ Exposure D15’

30 RESOURCE CAPABILITY AND DISTRIBUTION DATA

31 KNOW INITIAL ATTACK CAPABILITY Measured in terms of ability to flow GPM If fire flow requirements exceed resources, get help

32 RESOURCE CAPABILITY AND DISTRIBUTION DATA Capability/Distribution evaluation parameters Requires an aggressive interior fire attack

33 INTERIOR FIRE ATTACK FLOW RATES AND PERSONNEL REQUIRED Hose size Flow Rates Personnel/Lines 1-1/2” 100 gpm 2 1-1/2” 150 gpm 2 1-3/4” 150 gpm 2 2” 240 gpm 3 2-1/2” 300 gpm 4+

34 FOUR MAJOR FUNCTIONS ON THE INCIDNET SCENE COMMAND VENTILATION SEARCH FIRE CONTROL

35 Insert building fire 40’ x 90’ slab foundation “Distribution at simple incidents”

36 FIRE INVOLVEMENT 1-story structure 40 x 90 (3600 Sq. Ft) built on a slab 25% involvement, no exposures gpm = 300

37 Personnel Requirement Incident Commander 1 Ventilation 2 Primary Search/Fire Attack/ Pump Operation 7 Total Personnel Required 10

38 Insert 2 story building fire - lot’s of fire-Titled- distribution at complex incident Distribution at complex incident 60 X 60

39 FIRE INVOLVEMENT 2-story structure 60 x 60 (3600 Sq. Ft) built on a slab 25% involvement, 1 second floor exposure gpm = 600

40 Incident Commander 1 1st and 2nd Floor Supervisors 2 Ventilation 4 Primary Search/Fire Attack/ Pump Operation 4- 1-3/4” lines 12 Total Personnel Required 19

41 CONCLUSION gpm divided by personnel = gpm per person 300 gpm divided by 10 persons = 30 gpm per person

42 CONCLUSION gpm divided by personnel = gpm per person 600 gpm divided by 19 persons = 31.5 gpm per person

43 ANALYSIS The average fire flow on the incident scene in the United States ranges between 25 and 50 gpm per person engaged in fire control efforts, as stated in the charts above.

44 ANALYSIS If the fire flow is below 25 gpm/person, you are probably using 1 1/2” hose. Consider switching to 1 3/4” hose; or, you have counted people who are not doing any of the jobs (reserves).

45 ANALYSIS If the fire flow is greater than 50 gpm/person, you either have too few people doing ventilation and primary search; or you are using too few people on each hoseline. NO master streams allowed during interior attack.

46 PROACTIVE USE OF THE DATA Have each unit that responds report the number of personnel on board. Multiply your department’s average flow per person to get your total capability responding to this alarm.

47 PROACTIVE USE OF THE DATA What total flow for 10 personnel? What total flow for 15 personnel? What total flow for 20 personnel?

48 INTERIOR FIRE ATTACK AND PERSONNEL REQUIRED Hose size Flow Rates Personnel/Line 1-1/2” 100 gpm 2 1-3/4” 150 gpm 2 2” 150 gpm 2 1-3/4” 240 gpm 3 2” 240 gpm 3 2-1/2” 300 gpm 4+

49 Large Group Activity 5.2: Personnel Capability and Distribution Data

50 Insert 1 story building, 50’ x 90’ approx 25% involved

51 QUICK ACCESS PERFIRE PLANNING

52 WHO DOES THE PREFIRE PLANNING Proactive fire departments Chief officers leading professional departments Professional fire officers –paid/volunteer

53 PURPOSE For first-in officers A form from which you can read important data Does not take the place of a more detailed prefire plan for complex facilities Training reference for target hazards

54 BUILDINGS REQUIRING A PREFIRE PLAN Target hazards Other important structures/facilities Consider smaller structures

55 WHO USES QUICK ACCESS PREFIRE PLANNING First-in company officers/chief officers Later arriving chief officers Training Officers

56 Large Group Activity 5.3: Quick Access Preplanning

57 Insert slide # 57, module 5

58 Insert slide # 58, module 5

59 Insert slide # 59, module 5

60 Insert slide # 60, module 5

61 Insert slide # 61, module 5

62 Insert slide # 62, module 5

63 Insert slide # 63, module 5

64 Insert slide # 64, module 5

65 Insert slide # 65, module 5

66 Insert slide # 66, module 5

67 Insert slide # 67, module 5

68 Insert slide # 68, module 5

69 Insert slide # 69, module 5

70 Large Group Activity 5.4: Building Construction and Fire Behavior Predictions

71 Single family

72 Single family fire shot

73 Apartment shots / multi angle and fire

74

75 Large single family use micto stuff

76 Large single

77 Large single strip

78

79 Wheels in motion fire today

80

81 Wheels in motion fire

82

83 Wheels after fire

84 Large mercantile

85 highrise

86

87 Ordinary construction

88

89 Insert slide #89, module 5

90

91 Insert slide #91, module 5

92 Insert slide #92, module 5

93 Insert slide #93, module 5

94

95 Insert slide #95, module 5

96

97

98 SUMMARY Fire flow requirements must be understood because of the effect on tactical decisions, resource needs, and safety concerns on the incident scene. Knowing your resource capability in terms of gpm per person on the scene assists in decision making.

99 SUMMARY Prefire planning provides “must know” information which increases one’s ability to make correct decisions at an incident.