VRF Applications in PNW RTF RTUG Meeting October 26, 2011 Kevin Campbell Reid Hart, PE Technical Research Group.

Slides:



Advertisements
Similar presentations
HVAC Equipment Efficiency Overview Building Performance Matters.
Advertisements

Chapter 3. HVAC Delivery Systems
BUILDING AIR CONDITIONING
Energy Savings Impacts of the Advanced Energy Design Guide: Small Office Buildings Bing Liu, P.E. Research Engineer Pacific Northwest National Laboratory.
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
Commercial Mechanical Requirements
Foundations of Real Estate Management BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building ®
Foundations of Real Estate Management TM BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building.
The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.
University of Iowa Indoor Practice Facility Outside-the-box HVAC Lincoln Pearce, PE – KJWW Engineering David Hahn – University of Iowa Chilled Water Plant.
T OPPORTUNITIES FOR ENERGY EFFICIENCY AT TRIBAL GAMING FACILITIES.
Energy in Focus Energy Savings with Water Based Systems By Maija Virta Specialist of Indoor Environment Technology.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee September 28, 2011 Mira Vowles, P.E., CEM.
ASHRAE Presentation: VRF Overview Mitsubishi Electric Presenter: Phone number ©2011 Mitsubishi Electric& Electronics USA, Inc.
Engineer Fahad Hasan Associate Yousuf Hasan Associates, Consulting engineers District cooling.
HVAC Systems Overview HVAC Overview - # 1 Tom Lawrence
RETScreen® Energy Efficiency Projects
VRF for the Seventh Plan Preliminary Approach and Data for a Variable Refrigerant Flow Measure for the Seventh Plan Regional Technical Forum January 21,
Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement.
Air Conditioning Systems
PSU Building Thermal and Mechanical Systems Laboratory Environment A/E Kurt M. Shank, M.S. & Stanley A. Mumma, Ph.D., P.E. College of Engineering Department.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee April 25, 2012 Mira Vowles, P.E., CEM Emerging.
SEEM Tool Overview Regional Technical Forum Member Orientation January 22, 2013.
Brought to you by: Connecticut Energy Code Frederick F. Wajcs Senior Energy Engineer Northeast Utilities February 10, 2011.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee November 16, 2011 Mira Vowles, P.E., CEM.
Prioritization of VC HP Measures Variable Capacity Heat Pump Measure RTF Sub-Committee June 22, 2011 meeting.
1 Medical Office Building. 2 Occupancy – 400 persons 8 a.m. – 5 p.m. Monday - Friday Building Characteristics Three stories 40,000 square feet (200’ x.
Building Simulation. BMEABMEA uilding odeling nergy nalysis.
SENIOR THESIS PRESENTATION
Results from the California Energy Efficiency Potential Study – Existing Residential and Commercial Jean Shelton July 27, 2006 San Francisco, California.
November 2004 Low Hanging Fruit Low Cost Energy Efficiency Opportunities in Cleanrooms.
Ray & Joan Kroc Corps Community Center Mathias Kehoe | Mechanical Option April 09, 2012.
STUDY ON HVAC SYSTEM STUDY ON HVAC SYSTEM
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee February 22, 2012 Mira Vowles, P.E., CEM.
Hilton Hotel at BWI Airport Nathan Patrick The Pennsylvania State University Architectural Engineering – Mechanical Option.
ROAD TO CLIMATE FRIENDLY CHILLERS Hydrocarbons & Absorption Chillers Systems: Development & Potential Dr. Alaa Olama Sept. 2010, Cairo, Egypt.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee February 27, 2013 Mira Vowles, P.E., CEM.
Built Green™ vs. LEED ® : Energy Impacts of Residential Green Building Programs Jonathan Heller P.E. March 6, 2009.
Whitman-Hanson Regional High School Energy Efficient Systems: HVAC All fans and pumps are VFD controlled with fully reactive controls Condensing gas-fired.
The Data Center Challenge
Learning Outcomes Upon completion of this training one should be able to: Identify hydronic chilled water system applications. Define the difference between.
CRAC March 4, Windows Update Regional Technical Forum March 4, 2003.
University of Maryland’s Gossett Field House College Park, MD Jason Borowski Architectural Engineering Mechanical Option Pennsylvania State University.
Northwest Power Planning Council Residential Space Conditioning and Domestic Hot Water Conservation Resource Assessment Overview of Analytical Process.
Roof Top Unit Overview (MAGNUM) Visit us at Revision- 12/17/2015.
HEATING AND COOLING SYSTEMS
Grocery VSD Measure Deemed Savings Reid Hart, PE & Ken Anderson September 28, 2010.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee July 24, 2013 Mira Vowles, P.E., CEM Emerging.
Greenbriar East Elementary School Fairfax, Virginia Michelle L. Siano Mechanical Option Spring 2005 Senior Thesis.
Straumann USA 60 Minuteman Road Andover, MA Kevin Kaufman Mechanical Option The Pennsylvania State University Architectural Engineering.
Advanced Energy Engineering Technology Modeling Building Energy Systems Session 10: Modeling for ventilation and other energy-consuming equipment.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
EQuest Modeling Building Energy Systems Session 4: Building energy and modeling overview.
Learning Outcomes Upon completion of this training one should be able to: Identify hydronic chilled water system applications. Define the difference between.
Green Server Room Construction Primary concerns when building a server room is size and cooling. Size can be diminished with the use of virtual servers.
The New Student Housing Building at The Mount St. Mary’s University Emmitsburg, Maryland Erik Shearer Mechanical Option Advisor: Dr. Srebric Spring 2007.
Objectives Propose residential system related final project –Compare VAV systems with DOAS systems.
Michael Reilly, Jr. – Mechanical Option Advisor – James Freihaut, PhD & Dustin Eplee The Pennsylvania State University Nassau Community College Life Sciences.
Heat Pump Water Heaters: Interior, Ducted Installations Presentation to the Regional Technical Forum December 13, 2011 Ben Larson, Ecotope
© INTECHNICA Energy efficiency assessment Systematic Approach to Green Production Energy Efficiency Assessment Supported by: The sole responsibility.
HVAC Replacement Case Study
The Data Center Challenge
Types of HVAC Technology Used in Business Establishments
Chilled Beam Performance:
The Ed Roberts Campus Berkeley, CA Introduction Existing Systems
HCB 3-Chap 19A: All-Air Systems_Single Zone
Frenger “Radiant” chilled beam performance at 1 Shelly St - Sydney
Case Study: Marks & Spencer Oxford Street
Energy Management Introduction Rantharu Attanayake BSc. (Eng), MSc, MBA EE – Energy Management Mobile :
Presentation transcript:

VRF Applications in PNW RTF RTUG Meeting October 26, 2011 Kevin Campbell Reid Hart, PE Technical Research Group

Modeled Office Building Basic Qualities Simulation Runs 1.RTU, no economizer 2.RTU, with Economizer and fan control 3.VRF, Heat Pump, no Economizer 4.VRF, Heat Recovery no Economizer 2 Floors2 Floor Area25,000sq ft Ventilation Rate15cfm/person Lighting Density1.2watts/sq ft Equipment Density1.0watts/sq ft

3 System Parameters RTU VRF SystemRTUVRF SEER/EERSEER 13 Cooling COP Heat AFUE (gas)80.6%- Heating COP (HP)-4.06 Supply Fan Eff. (total)36%60% Supply Fan total SP DOAC total SP-2.25 DOAC Fan Eff. (total)-53%

Impact of VRF on HVAC Energy Fans have significant savings! (even more if no RTU fan control) Heating savings in northern climates (switch gas to Electric) Cooling savings except PNW where OSA economizer wins Both cooling and heating benefit from variable compressor 4

Small Office Comparison Two Models in PNW Duct leakage: ES high; PECI none Separate ventilation fan: PECI 2.5”’; ES ? ES: refrigerant piping loss factor; PECI none 5

PNW Office Energy End Use Comparison 6 *PECI small office utilizes economizer and fan controls. Energy Solutions small office includes duct leakage.

Differences Are Not Suprising A simple fan VSD measure had a wide range of savings when load variation was considered. Differences indicate need for: Regional standard buildings Range of loads to capture variation Expected value savings or other process to generate population values 7

Modeled Medical Clinic Basic Qualities Simulation Runs 1.VAV (dX) Electric Reheat + Economizer + SAT reset 2.VRF Heat Pump 3.VRF Heat Recovery Building Patient rooms with variable occupancy More perimeter zones Diagnostic equipment room 8 Floors1 Floor Area20,000sq ft Ventilation Rate20cfm/person Lighting Density1.2watts/sq ft Equipment Density1.0watts/sq ft

Impact of VRF on HVAC Energy Fans have significant savings! Heating always savings since no reheat with VRF Cooling savings due to improved part load efficiencies and high cooling requirements of VAV reheat 9

Healthcare/Medium Office (VAV) Compare Two Models in PNW 10

PNW Office VRF Energy Use per SF 11 *PECI VAV with electric reheat and SAT reset. Energy Solutions VAV with electric reheat.

Other Heat Recovery Options: Domestic Hot Water VRF Water Heater Standard to 115°F Booster to 160°F Applicable for buildings with both: Heat rejection (server; equipment; kitchen; cooling) Hot Water Load (Restaurants, Dorms, Hotel, Medical) Efficiency Improvement VRF water heating percentage savings vs. gas 12 Water Heat Mode% Site Btu’s% MW/NE Cost Heat Pump80%8% Heat Recovery93%69%

Exhaust Air Heat Recovery Adapt the old run- around or loop heat pump concept In heat mode, cool exhaust air In cool mode, heat exhaust air Feed general loop or pre conditioning at DOAC Need to verify airside pressure tradeoffs This strategy not in models 13

Conclusions Modeling tools and load/system assumptions have significant impact on predicted savings VRF systems can provide significant HVAC savings with lower fan energy and better part load efficiencies Buildings with low heating loads in economizer friendly climates have less significant savings Exhaust and DHW heat recovery applicable Notes: Proper control set-up & commissioning is important, as simulations are based on perfect control operation Simulations are not monitored results 14

15 Questions? Contact: Kevin Campbell PECI