Lecture Notes 3 Transformers

Slides:



Advertisements
Similar presentations
CHAPTER 5: TRANSFORMER AND MUTUAL INDUCTANCE
Advertisements

ENERGY CONVERSION ONE (Course 25741)
Alternating Current Circuits
AHBMH DEE2113 : Chapter 5 - Transformer & Mutual Inductance 1 CHAPTER 5: TRANSFORMER AND MUTUAL INDUCTANCE Review of Magnetic Induction Mutual Inductance.
Transformers and Coupled Circuits
electronics fundamentals
Topic 1 : Magnetic Concept and Transformer
Transformers.
Transformer.
Single –phase transformer.
Transformers.
Electrical Machine-I EE 2107 Dr. Md. Sherajul Islam
Main article: Leakage inductance
CHAPTER 6: TRANSFORMER BAKISS HIYANA ABU BAKAR
Chapter 2 Transformers.
Transformers Mechanical and Electrical Systems SKAA 2032
FOWLER CHAPTER 12 LECTURE 12 TRANSFORMERS. TRANSFORMERS CHAPTER 12 TRANSFORMERS ARE MULTIPLE WINDING INDUCTORS. WORK ON THE PRINCIPLE OF MUTUAL INDUCTANCE.
BENE 1113 PRINCIPLES OF ELECTRICAL AND ELECTRONICS
DC/AC Fundamentals: A Systems Approach
Electronics Fundamentals 8 th edition Floyd/Buchla © 2010 Pearson Education, Upper Saddle River, NJ All Rights Reserved. chapter 14 electronics.
TRANSFORMER mohd hafiz ismail hafizism, january 2007.
Single Phase Transformer
1.6 Real Single-Phase Transformer.
Electricity and Magnetism 29 Alternating Currents and Power Transmission Chapter 29 Alternating Currents and Power Transmission.
1 ECE 3336 Introduction to Circuits & Electronics Set #16 Transformers Fall 2011, TUE&TH 4-5:30 pm Dr. Wanda Wosik.
Power System Fundamentals EE 317 Power System Fundamentals Lecture 6 Lecture 6 06 October 2010.
POWER CIRCUIT & ELECTROMAGNETICS
Chapter 13 Magnetically Coupled Circuits
EET 103 Transformer Chapter 5 1. A transformer is a device that changes ac electric energy at one voltage level to ac electric energy at another voltage.
Modeling of Power Transformers A Static Device. Transformers The transformer enables us to utilize different voltage levels across the system for the.
EKT 451 CHAPTER 1 TRANSFORMER SHAIFUL NIZAM MOHYAR
BASIC ELECTRICAL TECHNOLOGY Chapter 6: Single Phase Transformer
By: Dr Rosemizi Abd Rahim
Electrical Transformer 1 By: Dr Rosemizi Abd Rahim Click here to watch the electrical transformer animation video
Chapter 2 Transformers Edit by Chi-Shan Yu Electric Machinery.
LITAR ELEKTRIK II EET 102/4. SILIBUS LITAR ELEKTRIK II  Mutual Inductance  Two port Network Pengenalan Jelmaan Laplace Pengenalan Jelmaan Laplace Kaedah.
3/17/2014 PHYS , Dr. Andrew Brandt 1 PHYS 1442 – Section 004 Lecture #15 Monday March 17, 2014 Dr. Andrew Brandt Chapter 21 Generator Transformer.
CHAPTER 1 Transformer School of Computer and Communication Engineering, UniMAP Prepared By: Amir Razif A. b. Jamil Abdullah EMT 113: V-2008.
Electrical Machines LSEGG216A 9080V. Transformer Operation Week 4.
EKT 451 CHAPTER 1 Transformer.
Transformer DKT Introduction to Transformer.  Transformer is a device that changes ac electrical power at one voltage level to ac electric.
1 ELECTRICAL TECHNOLOGY EET 103/4 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
1 ELECTRICAL TECHNOLOGY EET 103/4 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
POWER CIRCUIT & ELECTROMAGNETICS EET 221 Transformer.
Transformer DKT Introduction to Transformer.  Transformer is a device that changes ac electrical power at one voltage level to ac electric.
SMJE 2103 Electrical Power System
Chapter 13 Magnetically Coupled Circuits
SMJE 2103 Electrical Power System 3- Ph Power Apparatus.
1 :. Introduction These are special type of transformers used for the measurement of voltage, current, power and energy. As the name suggests, these transformers.
Parul Institute Of Technology Name Of Subject:-Electrical Machines Name Of Faculty:-(1) Suresh Sahoo (2) Yogendra Tiwari E&C 3 rd Sem. Prepaid By :- Sr.No.NameEnrolment.
Chapter 13 Ideal Transformers
Dr inż. Agnieszka Wardzińska Room: 105 Polanka cygnus.et.put.poznan.pl/~award Advisor hours: Monday: Wednesday:
1 ELECTRICAL TECHNOLOGY ERT 105/3 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
{ PRESENTATION ON TRANSFORMER. 1. INTRODUCTION: - TRANSFORMER : A static device- Utilized for raising or lowering the voltages. Transfers electrical energy.
Electronics Technology Fundamentals Chapter 10 Inductors.
Chapter 13 Ideal Transformers
TRANSFORMERS.
Lesson 8: Ideal Transformer Theory and Operation
CHAPTER 4 SINGLE-PHASE TRANSFORMER
Ideal Transformers Chapter Objectives:
GOVERNMENT ENNGINEERING COLLEGE , BHUJ
TRANSFORMER mohd hafiz ismail hafizism, january 2007.
Transformers.
Transformers. Transformer An A.C. device used to change high voltage low current A.C. into low voltage high current A.C. and vice-versa without changing.
Electromechanical Systems
TRANSFORMER.
Chapter 14.
Transformers.
Prof.mrs najma siddiqui
TRANSFORMER.
Presentation transcript:

Lecture Notes 3 Transformers EE212 Passive AC Circuits Lecture Notes 3 Transformers EE 212 2010-2011

Magnetic Circuit What is the relationship between magnetic flux and magnetomotive force, Fm? What is the relationship between electric current, i, and magnetomotive force? Magnetic field strength, H = Fm / l EE 212 2010-2011

Magnetic Circuit What is Faraday’s Law? The voltage induced in an electric circuit is proportional to the rate of change of the magnetic flux linking the circuit EE 212 2010-2011

Magnetic Circuit Consider a coil around a magnetic core. If a current i flows through the coil, a magnetic flux  is generated in the core. a b i  L vab = L di dt  = N i in webers (Wb) N = number of turns in the coil Rm = constant known as reluctance (depends on the magnetic path of the flux) Direction of flux by Right-Hand Rule Rm = in ampere-turns/Wb l = length of magnetic path A = cross-section area m = permeability Fingers curled around coil – direction of current Thumb – direction of flux EE 212 2010-2011

B-H Curve Flux Density, B = in teslas, T Magnetic field strength, H = in AT/m B = m H EE 212 2010-2011

Coupled Circuits Circuits that affect each other by mutual magnetic fields a b i1 f1 L1 vab c d vcd f2 L2 i2 ± depending on whether the fluxes add or oppose each other L1, L2: self inductance M: mutual inductance ratio of induced voltage in one circuit to the rate of change of current in another circuit The flux f2 generated by current i2 in Coil 2 induces a voltage in Coil 1, and vice-versa. EE 212 2010-2011

Coupled Circuits in Phasors If input signals are sinusoidal waveforms, coupled circuits can be in phasor representation ± depending on flux directions Left hand side equations imply a four element equivalent circuit with two dependent sources. a b Vab I1 L1 c d Vcd I2 L2 M EE 212 2010-2011

Equivalent Circuit with Dependent Sources EE 212 2010-2011

Dot Convention a b i1 f1 L1 c d f2 L2 i2 Dots are placed at one end of each coil, so that currents entering the dots produce fluxes that add each other. The dots provide information on how the coils are wound with respect to each other. A current i entering a dotted terminal in one coil induces a voltage M with a positive polarity at the dotted terminal of the other coil. (currents entering the dots produce upward fluxes) (+) if both currents enter the dotted terminals (or the undotted terminals). (-) if one current enters a dotted terminal and the other current enters an undotted terminal. a b I1 L1 c d I2 L2 Vab = (jwL1) I1 + (jwM) I2 for the currents as shown EE 212 2010-2011

Coefficient of Coupling, k k = 0 ≤ k ≤ 1 k depends on the magnetic properties of the flux path. When k = 0, no coupling k = 0.01 to 0.1, loosely coupled k > 0.5, close coupled, e.g. air core k ≈ 1.0, e.g. power transformer all the flux generated by one coil is linked to the other coil (i.e. no leakage flux) k = 1.0 ideal transformer EE 212 2010-2011

Transformer f if v1 N1 + - e2 N2 e1 primary winding secondary When a voltage V1 is applied to the primary winding, an emf e2 is induced in the secondary winding. The induced emf lags the inducing flux by 900. E1 N2 E2 N1 If + - V1 e2 = N2 V1 = -E1 If f E1 E2 Faraday’s Law EE 212 2010-2011

Transformer Application in Power System V/I step up/down Y/D conversion circuit (dc) isolation Z matching (for max power transfer, min. reflection from load) Instrument Transformers: CT (current transformer) PT or VT (voltage transformer) EE 212 2010-2011

Ideal Transformer No leakage flux  Coupling Coefficient, k = 1 , i.e. the same flux f goes through both windings = = a (turns ratio) e1 = N1 and e2 = N2 => Turns ratio (a or n) is also known as the transformation ratio. No Losses No voltage drops in the windings: V1 = - e1 Instantaneous powers in primary and secondary are equal (i.e. all the energy from the primary is transferred to the secondary winding). e1 i1 = e2 i2 Therefore, Be careful, the turns ratio can be defined as N2/N1. = = a EE 212 2010-2011

Transformer Loading a secondary current I2 is drawn by the load I2 generates a flux that opposes the mutual flux f (Lenz’s Law: effect opposes the cause) reduction in f would reduce induced emf e1 since source voltage V1 is constant, and V1 = - e1, f must remain constant the primary winding must draw an additional current I’1 from the source to neutralize the demagnetizing effect from the secondary e1 N2 e2 N1 I1 V1 + - ZL V2 I2 Primary current I1 = I’1 + If EE 212 2010-2011

Ideal Transformer No leakage flux, i.e., k = 1 Self-inductance, L1 = L2 = ∞ i.e., magnetizing current = 0 Coil losses are negligible With polarities, dots and currents as shown: V2 = V1 /a I2 = a I1 Z1 = a2 Z2 where Z2 is the load impedance Z1 is the impedance seen by the source a b Vab I1 L1 c d Vcd I2 L2 M + + ● ● - - EE 212 2010-2011

Actual Transformer - resistance in primary and secondary windings v1 N1 + - e2 N2 e1 ZL R1 R2 v2 - resistance in primary and secondary windings - leakage reactance in pr. and sec. windings - voltage drops in both windings (leakage impedance) - losses - copper loss primary: I12·R1 secondary: I22·R2 - iron loss (core loss) Core loss depends on voltage and frequency eddy current loss hysteresis loss EE 212 2010-2011

Iron (Core) Losses Eddy Current Loss: emf induced in core generates eddy currents which circulate in the core material, generating heat. laminations (silica sheets between core layers) – to reduce eddy current, and minimize loss EE 212 2010-2011

Iron (Core) Losses Hysteresis Loss: The direction of the magnetic flux in the core changes every cycle. Power is consumed to move around the magnetic dipoles in the core material, and energy is dissipated as heat. Hyst. loss  (vol. of core) x (area of hyst. loop) EE 212 2010-2011

Transformer Construction Coil Winding Core Assembly Core-Coil Assembly Tank-up Accessories Mounting and Finishing EE 212 2010-2011

Core Assembly EE 212 2010-2011

Core-Coil Assembly Core vertical sides – limbs, top horizontal side – yoke Yoke is removed to insert the coils into the limbs LV coil is first placed on the insulated core limbs Insulating blocks are placed at the top and bottom of the LV coil Cylinder made out of corrugated paper is placed over the LV Coil HV coil is placed over the cylinder The top yoke is fixed in position LV and HV windings are connected as required EE 212 2010-2011

Tank-up EE 212 2010-2011

Accessories Mounting Connections of LV and HV coil ends to the terminal bushings are made Transformer tap changer and protection accessories (e.g. Buchholz relay, Conservator, Breather, temperature indicator, etc.) are installed Tank is closed Functions of Transformer Oil Cooling muffle noise displace moisture (avoid insulation degradation) EE 212 2010-2011

Transformer Cooling EE 212 2010-2011

Typical Power Transformers Pole-mounted Single-phase Transformer Three-phase Transformer EE 212 2010-2011

Transformer Rating Rated kVA Rated Voltage primary and secondary: (transformers are normally operated close to their rated voltages) Rated Current (FL Current) is the maximum continuous current the transformer can withstand For single phase transformer: Rated primary current = Rated VA / Rated Pr Voltage When rated current flows through a transformer, it said to be fully loaded. The actual current through a transformer varies depending on the load connected at different times of the day. EE 212 2010-2011

Equivalent Circuit Represent inductively coupled circuits by a conductively connected circuit Equivalence in terms of loop equations Assume a load impedance is connected to the secondary. KVL at Loop 1: V1 + - L22 R1 R2 V2 M N2 N1 L11 I1 I2 -V1 + R1I1 + jwL11I1 - jwM I2 = 0 KVL at Loop 2: R2I2 + V2+ jwL22I2 - jwM I1 = 0 inductively coupled circuits turns ratio, = a The loop equations are: EE 212 2010-2011

Equivalent Circuit (continued) Consider following substitutions: V1 + - aV2 aM I1 R1 L1 a2R2 a2L2 M  a·M L2  a2·L2 R2  a2·R2 V2  a·V2 I2  conductively connected circuit KVL at Loop 1: -V1 + R1I1 + jwL1I1 + jwaM (I1-I2/a) = 0 KVL at Loop 2: jwaM (I2/a - I1) + jw a2L2.I2/a + jw a2R2.I2/a + aV1 = 0 Let L11 = L1 + aM and L22 = L2 + M/a The loop equations remain the same: V1 - V2 R1 + jwL11 - jwM - jwM R2 + jwL22 = I1 I2 EE 212 2010-2011

Transformer Equivalent Circuit a2ZL V1 + - I1 R1 X1 a2R2 a2X2 Ie If Ic Rc Xf ZL = load impedance Ie = excitation current If = magnetizing current Xf = magnetizing reactance equivalent circuit referred to the primary side R1, R2= primary, secondary winding resistance X1, X2= primary, secondary leakage reactance I1, I2= primary, secondary current Rc = core loss resistance (equivalent resistance contributing to core loss) Ic = core loss equivalent current EE 212 2010-2011

Example: Transformer Equivalent Circuit A 50-kVA, 2400/240-V, 60-Hz distribution transformer has a leakage impedance of (0.72 + j0.92) W in the high voltage (HV) side and (0.0070 + j0.0090) W in the low voltage (LV) winding. At rated voltage and frequency, the admittance of the shunt branch of the equivalent circuit is (0.324 – j2.24)x10-2 S [siemens] when viewed from the LV side. Draw the circuit: a) viewed from the LV side b) viewed from the HV side Turns ratio, a = 2400/240 = 10 0.72/a2 W j0.92/a2 W 0.0070 W j0.0090 W j44.6429 W 308.642 W a) 0.72 W j0.92 W 0.0070a2 W j0.0090a2 W 308.642a2 W j44.6429 a2 W b) Units of admittance used to be mhos [ohm backwards]. Still see it sometimes, but SI unit is siemen [same as the company]. EE 212 2010-2011

Transformer: Approximate Equivalent Circuit Re Xe Rc Xf Re = R1 + a2R2 Xe = X1 + a2X2 where, R2 and X2 are referred to the primary side Re and Xe  obtained from Short Circuit Test Rc and Xf  obtained from Open Circuit Test Re Xe For transformers operating close to full load Xe For transformers in a large power network analysis EE 212 2010-2011

Short Circuit Test Connect meters on HV side as shown Short circuit LV side Energize HV side with a variable voltage source and increase voltage gradually to get rated current reading on the Ammeter Take the V, I and P readings from meters LV HV Vsupply + - W A V Re Xe Rc Xf I V + - P = copper loss = I2 Re  Re = Ze =  Xe = Equivalent circuit referred to HV side X1 ≈ a2 X2 ≈ R1 ≈ a2 R2 ≈ EE 212 2010-2011

Open Circuit Test Connect meters on LV side as shown Vsupply W A V + - LV HV Connect meters on LV side as shown Open circuit HV side Energize LV side with rated voltage Take the V, I and P readings from meters Rc Xf I V + - If Ie Ic P = core loss =  Rc = Ie = I , Ic = Equivalent circuit referred to LV side If =  Xf = EE 212 2010-2011

Transformer Efficiency Efficiency, h = Power Output / Power Input Power Output = |VL| |IL| cos  = |IL|2 RL Power Input = Power Output + Cu losses + Core losses Cu Loss – varies with load current Core Loss – depends on voltage (usually a constant for practical purposes) Transformer efficiency is maximum when Cu loss = core loss Transformer efficiency is maximum when Cu loss = core loss EE 212 2010-2011

Transformer Efficiency (continued) Power transformers: - usually operate at rated capacity, - designed to have max. h at full load Distribution transformers: carry a widely varying load - designed to have max. h at less than full load - always energized despite load levels – designed to have low core loss Transformer efficiency is maximum when Cu loss = core loss EE 212 2010-2011

Example: Transformer Find the equivalent circuit of a 50-kVA, 2400/240-V transformer. The following readings were obtained from short circuit and open circuit tests: If rated voltage is available at the load terminals, calculate the transformer efficiency at full load with 0.8 p.f. lagging (b) 60% load with 0.8 p.f. lagging. What is the voltage at the HV terminals of the transformer? If rated voltage is applied at the primary terminals, calculate the transformer efficiency at full load with 0.8 p.f. lagging EE 212 2010-2011

Transformer Example 2 The transformer is used to step down the voltage at the load end of a feeder whose impedance is 0.3 + j1.6 ohm. The voltage at the sending end of the feeder is 2400 V. Find the voltage at the load terminals when the connected load is Zero 60% load at 0.8 p.f. lagging Full load at 0.8 p.f. laging Full load at 0.5 p.f. leading What will be the current on the low voltage side if a short circuit occurs at the load point? EE 212 2010-2011

Voltage Regulation When a constant rated voltage is applied to the primary, At no load - no current, and therefore no voltage drop in transformer - secondary voltage, Vsec = rated voltage As load (resistive or inductive) increases - voltage drop in transformer (Vdrop) increases - secondary voltage decreases (reverse is the case with capacitive load increase) EE 212 2010-2011

Voltage Regulation (continued) To maintain rated voltage at the secondary, At no load, primary voltage required, Vpr = rated voltage At a certain load, required Vpr = rated voltage + Vdrop in transformer Voltage regulation is the change in primary voltage required to keep the secondary voltage constant from no load to full load, expressed as a percentage of rated primary voltage. Load p.f. has a big effect on voltage regulation. EE 212 2010-2011

Example A 50-kVA, 2400/240-V, 60-Hz transformer has a leakage impedance of (1.42+j1.82) ohms on the HV side. The transformer is operating at full load in all 3 cases below. 1. Calculate the voltage regulation at 0.8 p.f. lagging unity p.f. 0.5 p.f. leading EE 212 2010-2011

Voltage Control The allowable voltage variation at the customer load point is usually ± 5% of the rated (nominal) value. Control measures are taken to maintain the voltage within the limits. Use of transformer tap changers: on-load/off-load Injecting reactive power (Vars): series/shunt compensation EE 212 2010-2011

Autotransformers Used where electrical isolation between primary side and secondary side is not required. Usually relatively low power transformers Can be readily made to be variable. Can think of it as two separate windings connected in series. Usually it is a single winding with a tap point. Can be used as either step-up or step-down transformer EE 212 2010-2011

Autotransformers (continued) Schematic diagrams: Can be connected series opposing, but not terribly useful. This makes a three-terminal transformer (rather than the typical 4-terminal). Middle terminal is often variable rather than a fixed tap. See next slide. From J.D. Irwin, “Basic Engineering Circuit Analysis”, 3rd ed. Macmillan EE 212 2010-2011

Autotransformers (continued) From Jackson et al. “Introduction to Electric Circuits” 8th ed., Oxford EE 212 2010-2011

Autotransformers (continued) Assume N1 = 200 and N2 = 100 Let Vsource = 120 V Then what is V2? I1 = 5 A (from apparent power and source voltage) Assume I2 is 15 A. Then Sload = ?, and Ssource = ? EE 212 2010-2011

Autotransformers (continued) What is the node equation at the tap? Node equation: I1 + IZY = I2 therefore, IZY = From transformer action: N1I1 = N2IZY therefore, That is, only part of the load current is due to the magnetomotive force that the current in the primary coil exerts on the secondary coil. The remaining portion is direct conduction of the source current to the load. EE 212 2010-2011