Laboratory Ventilation and Fume Hood Design (Considerations for Academia) October 8, 2002 Gary C. Shaver UNC-Chapel Hill.

Slides:



Advertisements
Similar presentations
PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-
Advertisements

Chemical Fume hood or Biosafety Cabinet
MULTIPLE PROFESSIONAL REVIEWS DOCUMENT SOLUTIONS Architectural and engineering review identifies building code and accessibility repairs needed. ($750,000.
TESTING AND BALANCING IN HEALTHCARE FACILITIES. What is Test & Balance The art of establishing air and water flows to meet design criteria. Total System.
1 Procuring a Design Project engineers perspective on starting the design process and establishing the A/E scope of work Frank C. Quigley General Engineer.
Airflow and BSC Biosafety and Biosecurity Awareness Training
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
Energy Service Productivity Management ©2007 ESPM Energy Consultants, L.L.C. All Rights Reserved.
Innovative Air Distribution for Healthcare Facilities.
DATA ONE, EUROPEAN OPERATIONS CENTRE, ST. PETERSBURG, RUSSIA Presentation of Design Proposal.
Engineering Controls and Laboratory Design Session 4 Laboratory Safety Training.
Lab Banding  More than assigning # of air changes/hour to lab  Lab operations risk assessment with hands on approach to ensure safe operation while reducing.
Break Out Session 3: Group A: Ventilation and Air Quality Chris Cosgrove, Cosgrove FDS, Inc.
Laboratory Fume Hoods In accordance with Title 8 CCR Section , Ventilation Requirements for Laboratory-Type Hood Operations. California State University.
Lab Energy Management Big Ten Mechanical & Energy Conference October
Providing services that help make The University of Memphis a safe and healthful place to learn and work Environmental Health and Safety.
When Do Variable Flow Fume Hoods Save Energy? Implications for lab design and behavior modification Michael Gevelber, Robert Choate, Kevin Sheehan, Brian.
Laboratory Safety-Fume Hoods 29 CFR Laboratory Safety Standard.
Siemens Building Technologies, Inc. ED&G 100 Design Project Fume Hood Face Velocity Control Spring 2004.
ASHRAE Club Project VAV Fumehood Retrofit - Engineering III Building Engineering III Building 40,000 gsf Completed 2002 Designed and constructed in two.
Zettl Group Safety Talk ~Fume Hoods~ 09/28/06 Takashi Ikuno.
Welcome to the Webinar! We hope you are logged in properly, if you are having trouble call We hope you are logged in properly, if you are.
1 FUME HOOD SAFETY Environmental Energy Technologies Division Safety Topic July 12, 2012.
DATA-BASED COMMISSIONING BUILDING-WIDE FUME HOOD FACE VELOCITY REDUCTION MIT Laboratory Energy Efficiency Case Studies.
NARAGHI HALL 3 rd FLOOR VENTILATION MANAGEMENT IMPROVEMENT BEST PRACTICE AWARD HVAC DESIGN/RETROFIT 2014 CALIFORNIA HIGHER EDUCATION SUSTAINABILITY CONFERENCE.
Chemical Fume Hood  A type of local ventilation device that is designed to limit the user's exposure to hazardous or noxious fumes, vapors or dusts.
Passive House Seminar for the Professionals from the Building Sector.
Enclosure Fire Dynamics
The Air We Breathe - Indoor Air Quality and Natural Ventilation Dr Yuguo Li Associate Professor Department of Mechanical Engineering The University of.
Enclosure Fire Dynamics
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
VENTING AND COMBUSTION AIR
12 th U.S. & North America Ventilation Symposium June 2008 Ventilation On Demand (VOD) Auxiliary Fan Project Auxiliary Fan Project D. O’Connor, Sr. Ventilation.
STEAM HEATING.
NFPA Edition Healthcare Facility Management Society Of New Jersey June 18, 2009.
Safety Meets Sustainability Rob Klein, MS, CIH Environmental Health & Safety Yale University New Haven, CT Making Universities Sustainable Copenhagen,
Saving Ventilation Dollars A Look at Economics of Ventilation.
Humidity in Anesthetizing Locations Where Mechanical Systems and Compliance Collide Daniel Swanson | Project Director Healthcare | McKinstry Currently.
Auraria Higher Education Center Case Study John Ismert & Frank Ellis Auraria Higher Education Center Facilities Management.
Brought to you by: Connecticut Energy Code Frederick F. Wajcs Senior Energy Engineer Northeast Utilities February 10, 2011.
Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By Klas C. Haglid, P.E., R.A., CEM 1.
AIR QUANTITY REQUIRED TO TRANSFER HEAT IN A FORCED AIR SYSTEM In all four mechanical systems considered, the transfer of heat, either by taking it out.
HVACR416 - Design IAQ / Ventilation / Pathways. Ventilation Most air handling units distribute a mix of outdoor air and re-circulated indoor air. Some.
FORUM Presented by ART GUADANO, AIA, LEED AP BD+C DURHAMTOWNHALL.
Commissioning of New and Existing Buildings Alexander P. Boucher, P.E., CEM, LEED BD+C.
Rating Laboratories Results from the Labs21 Program Paul Mathew, Dale Sartor Lawrence Berkeley National Laboratory Otto van Geet National Renewable Energy.
Sawyer Environmental Changes Mechanical Engineering Department Capstone Amy R. Dan H. Colby C. Brittany P. Richard G. 1.
HVAC- Body Works 1 Energy Analysis and Comfort Solutions Inc. Consumers – understanding how an HVAC system works.
AIA Guidelines for Design and Construction of Hospital and Healthcare Facilities Presented By: Michael A. Rogers, PE
Sizing Variable Flow Piping – An Opportunity for Reducing Energy
© Module 4—Hazard Prevention and Control Safety Management Worksite Analysis Management Commitment and Employee Involvement Hazard Prevention and.
Welcome!. Strategic Development and Facility Master Planning Board Approved in October 2010 Hot Springs County Memorial Hospital.
Lindab | we simplify construction - Flexibility when it is needed... Premum & Premax With unique JetCone and Angled Nozzles Patent pending solution.
Labs21: Improving the Performance of Laboratories Optimizing Air Changes – one of the Big Hits September 21, 2006 Dale Sartor, P.E. Lawrence Berkeley National.
3M B&CSD - Fire Protection Space for 3M Montage © 3M All Rights Reserved. 3M Fire Barrier Duct Wrap 615 For Ventilation Ducts.
1.  Quick Overview of the History and Need  What is Planned for the Fire Department  What is Planned for the Police Department  Financial Details.
Implementing Wind Responsive VAV Exhaust Systems at NREL's ESIF Building: A Four-Year Follow-Up Otto VanGeet, PE, NREL Brad Cochran, CPP I2SL -August 29,
Maria’s Restaurant Chapter 1 Section 4
Measurement of Transport in the PME EPA03 Task 2.B
Grunenwald Science and Technology Building
ANSI/ASHRAE 90.4 Energy Standard for Data Centers
Controlling Chemical Hazards
Fire Door Inspections Qualified Training
Variable Air Volume (VAV) Exhaust System Implementation Challenges
تهیه و تنظیم: مهندس همت جو
أجهزة الشفط في المختبرات الكيميائية: كيف تعمل ومتى لا تعمل
Creating a Smart Labs Program I2SL CO Education Day
WELCOME WELCOME.
Shut the sash! April 2017 Safety Focus.
Presentation transcript:

Laboratory Ventilation and Fume Hood Design (Considerations for Academia) October 8, 2002 Gary C. Shaver UNC-Chapel Hill

University of NC in Chapel Hill Oldest public University in US Founded in Buildings - over 12 M GSF Main campus- 809 Acres

Person Hall Built Grew GSF Uses – Chapel – Physics and Chemistry – School of Medicine – Pharmacy – Archeology – Arts Sustainable Building

Historic Lab Ventilation Issues Chemistry Dept. Head requested cancellation of laboratory classes due to “poorly ventilated rooms”. – A new lab addition was promptly built

Historic Lab Ventilation Issues Chair of the Dept of Chemistry observes: – “ …students working in the qualitative laboratory with wet handkerchiefs tied about their faces to remove, in part, the poisonous vapors they must take into their lungs.” – Disgrace for the State of NC. Trustees built a new Chemistry building.

Fast Forward to 2002 Deteriorating lab buildings Substandard health, and safety conditions Overcrowding Challenge of attracting/retaining quality personnel

Venable Hall-Chemistry Built in 1925 Multiple additions/upgrades Outdated Replace after 80 years

Student Chem Labs Built K GSF Segmented Constant volume system Vent. Deficiencies – Make up air from roof – Controls broke – System imbalanced

Consequences of Poor Design Poor IAQ Door operation problems $400K budgeted for repairs/balancing Bids were $500K Over budget; resources diverted

Medical Labs Built in ,344 s.f. HVAC repairs-$3.2 M Hood capacity exceeded

Consequences of Poor Design Demand >Design Long repair lead-time Hood use curtailed Restricts expansion

Existing Hoods Poor engineering – Adjacent to door/hall

Existing Hoods Auxiliary Air Poor design Untempered air Balancing issues

Historical Pattern of Laboratory Expansion Growth is constant Demand quickly outstrips facilities Poor design cannot be quickly remedied Systems degrade to critical point then trigger action

Expansion through New Construction and Renovation Greatest expansion in University history Funded through Bond Appropriations State in financial crisis Repair funds severely limited

Laboratory Growth in 10 years $500 Million 1 Million GSF 6 New buildings Major renovations

Campus Master Plan Building Infill Existing-purple New-red Add 5.5 M GSF – Air intake protection – Emergency generators

Exhaust Dispersion Study Science Complex Model buildings/topo Install in wind tunnel Discharge CO Visualize with smoke Evaluate key receptors RWDI

Laboratory Exhaust Hoods Highest energy consumer Critical tool for researcher protection Poorly understood Rapidly changing

Laboratory Exhaust Hoods Emphasis on energy savings Life cycle cost justification Hidden costs - health

Conventional vs. Low Flow Simple design Smaller footprint Sufficient dilution exhaust air VAV adaptable Lower cost Deeper Lower exhaust volume Lower energy use Varied complexity Higher initial cost Safer???

Low Flow Safety & Ergonomic Considerations Deeper hoods – Inability to reach back of hood – Head and torso into hood Horizontal sashes – user options – Full head and torso protection – Full body exposure

A Current Perception “… many investigators are concerned that "voodoo calculations" are being used as a way to market a more expensive, less safe hood with a smaller margin of safety.”

Low Flow Designs Labcrafters Air Sentry Labconco XStream Fisher Hamilton Pioneer & Concept (not shown) Kewaunee Dynamic Barrier LCV

Hood Selection Process Establish user requirements – Sash Type (vertical, horizontal, combo) – Sash openings – Expected use Consider reality (worst case)

High Performance - Low Flow How low can you go??? – Typically fpm at face – Drafts at face Performance Testing – ASHRAE – ANSI/AIHA Z – Modified ASHRAE

Advances in Challenge Testing Obstacles in hood Change tracer gas – Volume – Release point Shorter mannequin Side drafts (fans) Walk-by simulations

High Performance - Low Flow Designing to the Standardized Test? Test Modifications Lower performance – Humans replace mannequins – Lower ejector heights (see Montana State U. studies with Hutchings/Knutsen)

Hood Engineering for Humans Human behavior confounds ideal hood performance Consider over designing Train on proper hood use

Human Factor Packed hood Covered airfoil

Human Factor Hood modifications – Air foils removed – Added inner shelf Exhaust – Dampers adjusted

Human Factor Sash fully open Open waste container Lower airfoil removed

Human Factor Sash fully open Packed hood Air flow dynamics?

Science Complex Phase I Mechanical 10 Exhaust shafts 4 Exhaust heat recovery units (2 shafts/unit) 130 laboratory exhaust hoods Future capacity to add 45 hoods

Hood Selection Process (Science Complex) Sash Type – Combination Typical use – Vertical sash down, horizontal sashes open – 8 foot hoods, horizontals closed, vertical 18 in. Worst case – Vertical sash fully open

Hood Selection Process (Science Complex) Evaluate as constant volume Set flow for restricted opening (100 fpm) Will maximum opening pass? Consider installed product performance

Summary of Findings Advanced hoods reported to: – Meet ANSI/AIHA test criteria AM (AI) Horizontal sash open, vertical down Vertical sash 18 inches, horizontal closed – Pass/fail at full open sash – Use standard and modified ASHRAE 110 – Limited installed base

Science Complex Hood Exhaust with VAV

Noise attenuators – dust and debris Static pressure losses Balancing issues Mechanical complexity User dependent

VAV Considerations VAV Considerations Payback not always realized Commissioning is critical!

Combined Exhaust (Minimize Stacks) Increase Dilution Reduce maintenance Energy recovery Emergency power Fan Redundancy (50%)

Combined Exhaust with Energy Recovery

IMC Section 510 Challenge Defines hazardous exhaust Limits combined exhaust (separate general exhaust) Prohibits incompatible mixing Fire suppression in duct systems Ignores small quantities/high dilutions

IMC Section 510 Challenge Alternate M&M – NFPA 45 Chapter 6 – ANSI/AIHA Z9.2 (in revision) AIHA Lab Safety Committee position paper Code change process in progress (2 yrs) Intent - exclude laboratories

Bidding Wars Specifications – Incorporate recognized standards – Qualifies 3 bidders – Precludes bid challenges Long construction delays Low bid wins but not necessarily the best!

Lessons Learned on Lab Ventilation Keep it simple Minimize mechanical parts Minimize maintenance Maximize flexibility for growth

Lessons Learned on Lab Ventilation Hood selection defines – Space – Mechanical systems Hood design is in continuous flux Selection impacts next 30+ years Maximize safety

Laboratory Exhaust Systems High stakes – Safety – Health – Energy High first costs High operating costs (heating/cooling) Incomplete performance picture High emotions

In Academia: Learn from a rich past Prepare for the distant future and …. In Academia: Learn from a rich past Prepare for the distant future and …. Keep your Cool!