Presentation is loading. Please wait.

Presentation is loading. Please wait.

Variable Air Volume (VAV) Exhaust System Implementation Challenges

Similar presentations


Presentation on theme: "Variable Air Volume (VAV) Exhaust System Implementation Challenges"— Presentation transcript:

1 Variable Air Volume (VAV) Exhaust System Implementation Challenges
Colorado I2SL Chapter Education Day Colorado State University August 28, 2018 Ryan Parker, PhD - CPP, Inc.

2 Learning Objectives Understand the use of dispersion modeling to aid in development of a simple turndown or wind-responsive VAV exhaust system Identify the key processes and interactions required for a successful simple turndown or wind-responsive VAV exhaust implementation Understand challenges involved with the VAV exhaust implementation process as they pertain to mechanical operation, controls programming, and client expectation Increase knowledge of future operation and maintenance considerations for VAV exhaust systems

3 Outline/Agenda Dispersion modeling Overview CPP Implementation Process
Wind Tunnel Design Criteria Development CPP Implementation Process Overview Sequence of Operation (SOO) Development Implementation Challenges Mechanical Issues Variable Frequency Drives (VFDs), Isolation/Bypass Dampers, Pressure Sensors, Fan Curves Building Management System (BMS) Existing Conditions and Client Expectations Operation and Maintenance User Interface Importance of Continued Maintenance

4 Dispersion modeling Overview
Wind Tunnel Scale Model Concentration Measurements Meteorological Data Probabilities and Turndown Today’s Tour

5 Dispersion modeling Overview
VAV System Types Laboratory/Fume Hood Vivarium General Lab Exhaust Other Exhaust Radioisotope, Perchloric Acid, Biological Safety Cabinet, Hazardous Storage Cabinet Laboratory/Fume Hood Teaching vs. Research ASHRAE HVAC Applications Handbook , ANSI/AIHA Z9.5 Chemical Inventory, ACGIH Vivarium General Exhaust Other Radioisotope, Perchloric Acid, Biological Safety Cabinet, Flammable Storage Cabinet

6 CPP Implementation Process
Overview Feasibility Energy Optimization Wind Tunnel Assessment Pre-Functional Testing (On-site) Sequence of Operation (SOO) Code Development Implementation Testing (On-site) Commissioning/Final Reporting Feasibility Trend Data Bypass Damper Fan Speed Duct Static Pressure Motor Power AHU Load Energy Optimization Wind Tunnel Assessment Simple Turndown vs. Wind Responsive Pre-Functional Testing On-Site Testing Gather Fan Operation Data Evaluate Fan Combinations Determine Problem Areas Sequence of Operation Code Development Based on Energy Optimization Assessment and Pre-Functional Testing Duct static pressure within acceptable limits Maintain minimum fan speed at or above critical fan speed Minimize bypass damper flow Number of Fans/Staging Controls Contractor Interaction/Review Troubleshoot Prior to Implementation Implementation Testing On-Site Implementation Method of Operation Procedure VAV Exhaust and Anemometer Evaluate SOO and Troubleshoot Flip the Switch Commissioning/Final Reporting Obtain Trend Data Compare with Metrological Data Identify and Correct Anomalies and Deviations

7 CPP Implementation Process
Sequence of Operation Code Development Based on Energy Optimization Wind Tunnel Assessment and Pre-Functional Testing Control Priority Duct static pressure within acceptable limits Maintain minimum fan speed at or above critical fan speed Minimize bypass damper flow Priorities: 1) Building operation 2) Safety 3) Energy savings

8 CPP Implementation Process
Sequence of Operation Code Development Simple Turndown vs. Wind Responsive New construction or existing building

9 Implementation Challenges
Mechanical Issues Building Management System Existing Conditions and Client Expectations Solution: Pre-functional testing Preventative maintenance PID adjustment by experienced controls contractor

10 Implementation Challenges
Mechanical Issues Isolation/Bypass Damper Operation Not always functional Slow response time PID tuning difficulties once fan speed changes are introduced Solution: Pre-functional testing Preventative maintenance PID adjustment by experienced controls contractor

11 Implementation Challenges
Mechanical Issues Pressure Sensors Location Calibration Interaction with other mechanical systems Solution: Pre-functional testing Relocation of pressure sensors Redundant sensors rather than averaging

12 Implementation Challenges
Mechanical Issues Fan Curves Availability Pulley/sheave sizing Duct static pressure variation Solution: Pre-functional testing Pulley and sheave measurement Tachometer readings on motor/fan

13 Implementation Challenges
Mechanical Issues Anemometer Communication protocol Error handling Wind speed vs. wind direction averaging Mast/anchoring Testing and maintenance Siemens input resistance from 250 ohm to 500 ohm WindSonic could not have more than 300 ohm signal resistance Optical isolator had to be used. Need Ryan’s picture from Auburn

14 Implementation Challenges
Mechanical Issues Building Management System (BMS) Existing Conditions and Client Expectations Solution: Pre-functional testing Preventative maintenance PID adjustment by experienced controls contractor

15 Implementation Challenges
Building Management System (BMS) BMS point mapping Troublesome if incorrect or incomplete Refresh rate Availability of live trending Controller upgrade Solution: Provide pre-functional checklist to ensure items are mapped before pre-functional testing can occur Discuss trending requirements with controls contractor to ensure success

16 Implementation Challenges
Building Management System (BMS) Sequence of operation interpretation Lookup table interaction Trend data

17 Implementation Challenges
Building Management System (BMS) PID loop tuning VFD ramp speed Trend data Control Priority Duct static pressure within acceptable limits Maintain minimum fan speed at or above critical fan speed Minimize bypass damper flow

18 Implementation Challenges
Mechanical Issues Building Management System Existing Conditions and Client Expectations Solution: Pre-functional testing Preventative maintenance PID adjustment by experienced controls contractor

19 Implementation Challenges
Existing Conditions and Client Expectations Safe response time vs. acceptable HVAC response time Acceptable duct static pressure range Static pressure limits Scheduling

20 Operation and Maintenance
User Interface Clear and informative graphics Descriptive, commented code Consistent message to BMS staff

21 Operation and Maintenance
Importance of Continued Maintenance User access Checks/alarms Project documentation Full realization of project benefit Error Anemometer Alarm Error Access to maintenance mode switches, system feedback, informative data Communication Fault

22 Conclusions VAV Exhaust Implementation Challenges
Dispersion modeling is an important aspect in developing a simple turndown or wind-responsive VAV exhaust system A variety of challenges exist with VAV exhaust implementation, but many can be overcome with planning and pre-functional testing Tools include pre-functional testing, concurrent code review, sequence of operation bench testing, method of procedure documentation, informative graphics, and accurate trend data Access to maintenance mode switches, system feedback, informative data

23 Ryan Parker, PhD Project Engineer rparker@cppwind.com
Questions? For More Information Ryan Parker, PhD Project Engineer CPP, Inc. 2400 Midpoint Drive, Suite 190 Fort Collins, CO 80525 (970)


Download ppt "Variable Air Volume (VAV) Exhaust System Implementation Challenges"

Similar presentations


Ads by Google