Visit us at www.mcscontrols.com MCS Products Visit us at www.mcscontrols.com
Presentation Overview MCS Design Criteria Magnum Hardware & Specification MCS-RO10 Hardware & Specification MCS-SI16-AO4 Hardware & Specification MCS Sensors Specification
MCS Design Criteria First Priority Quality & Service Second Priority Cost Third Priority Ease of Use
Engineering Design Concepts Serviceability Standard Algorithm (Flexible) Control Status (State Machine) Alarms (Descriptive) Actual Compressor Amp Draw Adjustable Setpoints
Engineering Design Concepts Suction, Discharge & Oil PSI (Calculated Oil Differential) Suction & Discharge Superheat Graphing (Static & Dynamic) Windows® Local & Remote Communications Network Multiple Units at the Same Location Expandable
Magnum Board 10 Relay Outputs Power Input Keypad/Display Micro Control Systems, inc. 10 Relay Outputs Power Input Keypad/Display 4 Analog Outputs Communications 4 Digital Inputs 12 Sensor Inputs Extra ½ Amp Fuse
MCS-MAGNUM-PANL (12.0”w x 8.0”h x 2.0”d) Panel Mount Package Micro controller complete and ready to mount in a rain-proof enclosure Display / Keypad can be up to 10 feet away using 6-conductor shielded cable
MCS-MAGNUM-DOOR (12.0”w x 8.0”h x 2.0”d) Door Mount Package Micro controller complete and ready to mount in a door Display / Keypad can be up to 10 feet away using 6-conductor shielded cable
MCS-MAGNUM-OEM (12.0”w x 8.0”h x 2.0”d) OEM Mount Package Micro controller complete and ready to mount Display / Keypad can be up to 10 feet away using 6-conductor shielded cable
Magnum Specifications 10 Relay Outputs, Fused 6.3 amps, 115/230vac 12 Sensor Inputs, Analog or Digital, 0-5vdc 4 Digital Inputs (< 0.5 vdc OFF, > 4.5 vdc ON) 4 Analog Outputs, 0 to 10vdc System expandable to 80 RO’s, 80 SI’s, 20 AO’s Real Time Clock with Battery Backup Backlit Graphics Display & 9 Button Generic Keypad Extended Temp. Range -4°F to 158°F (-20°C to 70°C )
Magnum Specifications Common, Normally Open & Normally Closed for each Relay UL Approved RS-232 communicates @ 19,200 baud, Modem @ 14,400 baud MCS-I/O communicates @ 38,400 baud (RS-485) 1 RS-485 communicates @ 19,200 baud Ethernet port @ 10/100 Mbps Optional Compact Flash Adaptor BACnet IP, Modbus Johnson N2 built-in (LonTalk requires adaptor)
Magnum History Specifications Standard History Samples Optional Compact Flash Adaptor With 1 g byte Flash about 1.5 months at 1 sec sample rate With 1 g byte Flash about 7.5 years at 1 min sample rate (Air Cooled Chiller w/2 screws, 2 circuits, 5 fans per cir, exv’s)
MCS-RO10 (10.87” x 4.00” x 2.50”) 10 Relay Outputs fused at 6.3 amps 1 MCS-I/O Communication (RS-485) Extended Temperature Range -40º to 158ºF (-40°C to 70°C )
MCS-SI16-AO4 (10.87” x 4.00” x 2.50”) 16 Sensor Inputs 0-5vdc / 4 Analog Outputs 0-10vdc 1 MCS-I/O Communication (RS-485) Extended Temperature Range -40º to 158ºF (-40°C to 70°C)
MCS-T100 (2.00”L x 0.20”Diameter) Deep-drawn Stainless Steel Tube Fast, 32° to 212°F (0° to 100°C) < 30 sec ± 0.36°F from 32° to 212°F (0° to 100°C) -40.0°F to 230°F (-40° to 110°C) Bracket available for duct mounting 20’, 40’ or 60’ cable (no breaks)
MCS-200T, MCS-500T, MCS-667T SS with 1/4 inch female flare Range 0 to 200 psi (0 to 13.8 bars) Range 0 to 500 psi (0 to 34.5 bars) Range 0 to 667 psi (0 to 46.0 bars) Packard removable connector 20’, 40 or 60’ cable (no breaks) Accuracy (500) ± 0.5 psi ± 0.03 bars Accuracy (200) ± 0.2 psi ± 0.01 bars
MCS-CT300, 500 & 1500 Center hole diameter 1.00” (300) Accuracy ± 2% PC board on top (Eliminates potential danger) Removable screw terminal block Small footprint with integrated PC board Provides protection for over & under amps
MCS-485-GATEWAY (2.50” x 3.47” x 1.04” Converts RS-232 to RS-485 Nylon collar mount Removable terminal block
MCS-WELL (TUBE) 2.5” deep drawn nickel plated brass tube Small, fast acting 1/4”, 1/2” & 3/4” fittings on well Tube for pipe mounting Well for conduit installations
MCS-CRADLEPOINT CTR500 3G/4G Mobile Broadband Router Mobile Broadband Data Card with Active Subscription USB or ExpressCard, or Smart Phone Tethered Data Plan Suggested Mobile signal at job site.
MCS Magnum Advantages Compressor EEV ( Sporlan / Alco / Siemens) Eliminates need for a second EEV controller Knows where capacity is moving, adjustment is dynamic Provides improved energy efficiency Sporlan EXV’s & Interface Boards Stocked in Florida, USA Support for Scroll, Screws, Recip, & Centrifugal compressors Last 30 Sensor Sample on Lockout Alarms – Info Button Built-in BMS support for BACnet-IP, Modbus & Johnson N2 Adapter for BACnet-MSTP & Lontalk
MCS Magnum Advantages Six Layer Printed Circuit Board Impervious to Electrical Noise Generic Keypad / Backlit Display Control Algorithms Keep System Running Warning, Safeties and Lockout System Micro Extended Temperature Range
MCS Magnum Advantages Windows® Based Support Systems Control ‘STATE’ Machine Precise Descriptive Alarms History Graphing Static & Dynamic High Speed Local/Remote Communications HVAC Controls People