Storage of Flammable and Combustible Liquids

Slides:



Advertisements
Similar presentations
Haz Mat Technician Course
Advertisements

Flash Point-Ignition Point
HAZARD COMMUNICATION REQUIREMENTS Site Specific Written Program Chemical Inventory MSDSs/SDSs Labeling Non-routine Tasks Contractors Training.
Regulations (Standards - 29 CFR) Flammable and Combustible liquids
Flammable and Combustible Liquids
Storage of Flammable Liquids
Flammable and Combustible Liquid & Compressed Gas Handling and Storage
FLAMMABLE AND COMBUSTIBLE LIQUIDS
Use of Steam Tables Saturated Vapor or Liquid
Hazardous Materials Subpart H.
Latent & Sensible Heat To help you understand the refrigerant phases (changes) in a vapour compression system, let us first consider the basic properties.
Compressed Gases.
Chemistry of Fire.
PROPERTIES OF FLAMMABLE MATERIALS. Flammability Flammable Flammable –Capable of being ignited and of burning –Synonymous with combustible.
Fires and Explosions.
Safe Handling of Flammable and Combustible Liquids
By: Dirk Patrick Cloete
Flammable and Combustible Liquids. Flammable liquids v Class I - liquids have flashpoints below 100 degrees F, with vapor pressures not exceeding 40 psia.
Flammable and Combustible Liquids. Flammable liquids Class I - liquids have flashpoints below 100 degrees F, with vapor pressures not exceeding 40 psia.
Fire Triangle In order to understand how fire extinguishers work, you first need to know a little bit about fire. Four things must be present at the same.
Liquid Fuel Safety Cummins Southern Plains, Ltd..
Laboratory Safety-Flammable Liquids Flammable Liquids and Fire Codes for Laboratories.
FLAMMABLE AND COMBUSTIBLE LIQUIDS
Copyright © Flammable & Combustible Liquids.
Fire Safety.
WFU Explore this site Turn in Safety “Quiz” by Monday. Must make an 80%.
Flammable and Combustible Liquids
Flammable and Combustible Liquids Presented by Martina Schmeling Adapted From OSHA.
HAZARDOUS MATERIALS. OSHA Office of Training and Education - Revised by TEEX 12/05/07 2 Terminal Objective Describe the hazards and requirements of working.
CXS490 Carbon Dioxide Systems
Hazardous Materials Subpart H. Subpart H Standards Compressed Gases Acetylene Hydrogen Oxygen Nitrous Oxide Flammable.
Hazard classification
© 2012 Delmar, Cengage Learning Chapter 5 Hazards of Liquids.
PLANT DESIGN.
Hazardous Materials Subpart H. Subpart H Standards Compressed Gases Acetylene Hydrogen Oxygen Nitrous Oxide Flammable.
Indiana Fire Code.
What is Fire? Fire consists of 3 things –heat, fuel, oxygen Fuel is anything that will combine with heat and oxygen to burn. Heat is anything that will.
Flammable and Combustible Liquids. Introduction !The two primary hazards associated with flammable and combustible liquids are explosion and fire !Safe.
FLAMMABLES. 1. PROPERTIES OF FLAMMABLES Combustion (redox) reactions Solids, gases, most commonly liquids Fire Tetrahedron Ignition sources External-
HW Review 1.35 A tank of gas with a total pressure of 12.0 atm contains a mixture of oxygen, nitrogen and argon. If the partial pressure of nitrogen.
Fuel Contamination Gasoline into diesel fuel – Problems Lower diesel flashpoint - fire hazard Poor operability for diesel engines, lower cetane number.
Lesson 7: Just A Phase Key Terms. Solid A solid has definite volume and definite shape. The particles in a solid are closely packed and vibrate in relation.
Liquids Chemistry Mrs. Coyle. Liquids Intermolecular attractions hold molecules of liquids together. Intermolecular attractions hold molecules of liquids.
FLAMMABLE AND COMBUSTIBLE LIQUIDS 1 Bureau of Workers’ Comp PA Training for Health & Safety (PATHS) OSHA 29CFR PPT
Subpart F - Fire Protection & Prevention ( ) Flammables/combustibles - Approved containers Fire protection program/equipment 2A fire extinguishers.
Chapter 7 Fire and Explosions. Fires, Explosions, and Detonations The lowest temperature at which an air- hydrocarbon mixture will explode or burn is.
Flammable Liquids Directorate of Training and Education
Safe Handling of Flammable and Combustible Liquids.
Fire Loss Control - Basic Elements
Safe Handling of Flammable and Combustible Liquids
States of Matter I. Describing the States of Matter:
Flammable and combustible liquids
Flammable and Combustible Liquids
مایعات قابل اشتعال و احتراق پذیر
Working with Phases and Properties of Substances
الهدف من برنامج السلامة في المختبر: 1- فهم قوانين وقواعد السلامة في المنشأة وتطبيقها 2- الوقاية من وقوع الحوادث لا قدر الله . 3- المحافظة على سيرا لعمل.
Combustion and Global Warming
Chapter 7 Fire and Explosions
Flammable & Combustible Liquids
Safe Handling of Flammable and Combustible Liquids
Flammable and Combustible Liquids
Portable Fire Extinguisher Overview
Flammable and Combustible Liquids
Boiling is a liquid-to-vapor phase change process just like evaporation, but there are significant differences between the two. Evaporation occurs at.
Chapter 2 Matter and Change 2.1 Properties of Matter 2.2 Mixtures
Chemistry/Physical Setting
Flammable and Combustible Liquids
Flammable and Combustible Liquids
Ch The Nature of Liquids
Temperature Kelvin Scale Fahrenheit Scale Celsius Scale.
Presentation transcript:

Storage of Flammable and Combustible Liquids 29 CFR 1910.106 The information in this presentation is provided voluntarily by the N.C. Department of Labor, Education Training and Technical Assistance Bureau as a public service and is made available in good faith. This presentation is designed to assist trainers conducting OSHA outreach training for workers. Since workers are the target audience, this presentation emphasizes hazard identification, avoidance, and control – not standards. No attempt has been made to treat the topic exhaustively. It is essential that trainers tailor their presentations to the needs and understanding of their audience. The information and advice provided on this site and on linked sites is provided solely on the basis that users will be responsible for making their own assessment of the matters discussed herein and are advised to verify all relevant representations, statements, and information. This presentation is not a substitute for any of the provisions of the Occupational Safety and Health Act of North Carolina or for any standards issued by the N.C. Department of Labor. Mention of trade names, commercial products, or organizations does not imply endorsement by the N.C. Department of Labor.

Objectives In this course, we will discuss the following: 29 CFR 1910.106 In this course, we will discuss the following: Scope of the standard The four elements of the fire tetrahedron and how the standard aims to interrupt those elements Classifying flammable and combustible liquids Storage requirements for liquids covered under the standard (MS Clip Art)

Flammable & Combustible Liquids 1910.106 (a) Definitions (b) Tank storage (c) Piping, valves, and fittings (d) Container and portable tank storage (e) Industrial plants (f) Bulk plants (g) Service stations (h) Processing plants (i) Refineries, chemical plants, and distilleries (j) Scope

Flammable and Combustible Liquids 1910.106 Are compressed gases in a flammable liquid phase covered under 29 CFR 1910.106? NO! The answer to this questions is no! See definition of liquid (a)(17) And letter of interpretation dated 5/17/76. Photo: MS Clip Art

Scope of the Standard "Scope" 1910.106(j) "Scope" This standard applies to the handling, storage, and use of flammable and combustible liquids with a flashpoint below 200 degrees F. The flash point of the liquid determines if it falls within the scope of the standard. (MS Clip Art)

Flammable & Combustible Liquids The standard focuses on liquid temperature by using Flash Point (FP) and Boiling Point (BP) to establish a Class Rating. Different classes of flammable and combustible liquids pose different hazards and therefore have different rules. (MS Clip Art)

Fire Tetrahedron and the Standard Fuel Combustible Flammable Liquid Increased Surface Temperature Heat Source Production of Vapor Oxygen (Tetrahedron illustration from Wiki Commons: http://commons.wikimedia.org/wiki/Image:Fire_tetrahedron.svg?uselang=zh (I, the copyright holder of this work, hereby release it into the public domain. This applies worldwide.) (Text boxes and text by Andy Sterlen, NCDOL-OSH Division) Flame Established Suitable Chemical Reaction Sustained Combustion

Flash Point Flash point Temperature where a enough evaporated fuel vapor is generated from a liquid to support a flash of combustion after a heat source has been introduced Not fire point Photo: Lawrence Livermore Laboratory

Boiling Point Boiling point 1910.106(a)(5) Boiling point Temperature at which the saturated vapor pressure of a liquid is equal to atmospheric pressure Photo: US Geologic Service)

Flammable Liquids “Flammable liquid” Under the definition Mixtures containing component/s with a flash point of 100°F or higher which make up 99% or more of the total volume of the mixture, are not considered flammable. Therefore, mixtures containing more than 1% of a liquid with a flash point below 100°F are considered flammable. (Illustration by Andy Sterlen, NCDOL-OSH Division)

Classifying Flammable Liquids Class IA A flash point below 73°F and a boiling point below 100°F   Class IB A flash point below 73°F and a boiling point at or above100°F   Class IC A flash point between 73°F and below 100°F Note: A liquid having a flash point at or above 100°F will be classified as Class II or III (combustible).

Combustible Liquids "Combustible liquid" Under the definition 1910.106(a(18) "Combustible liquid" Under the definition Means any liquid having a flashpoint at or above 100° F (OSHA.gov)

Classifying Combustible Liquids Class II A flash point at or above 100°F but below 140°F.   Class IIIA A flash point at or above 140°F but below 200°F.   Class IIIB Liquids having a flash point at or above 200°F. Note: Class IIIB liquids are not covered under the scope of §1910.106.

Flash Point 1910.106(j) As stated previously, the flash point determines if a substance falls within the scope of the standard. Above >100° F (combustible) Below <100° F (flammable) (Illustration by Andy Sterlen, NCDOL-OSH Division)

Class Exercise °F °F Class II Class IB Class IIIB Class IC Class IA Use the FP (Flash Point) and the BP (Boiling Point) to determine the Class using the Flammable Combustible Liquid Chart.

Tank Storage 1910.106(b)(1)(i) Shall be made of steel or other approved nonflammable materials Other materials are permitted for underground use Concrete tanks (must have a special interior lining) and be designed with sound engineering practices Operating pressures must never exceed the design pressure Photo fedcenter.gov

Tank Storage Metal tanks Filler metals used in tank brazing 1910.106(b)(1)(ii)[b] Metal tanks Shall be welded, riveted, and caulked, brazed, or bolted, or constructed by use of a combination of these methods Filler metals used in tank brazing Shall be nonferrous metal or an alloy having a melting point above 1000° F and below that of the metal joined Illustrations: MS Clip Art

Tank Storage Atmospheric tanks 1910.106(b)(1)(iii) Atmospheric tanks Shall be built in accordance with acceptable standards Not exceed 2500 gallons, if originally designed for underground but placed above ground Not be used to store liquids at or above their boiling points (MS Clip Art)

Tank Storage Low pressure tanks Pressure vessels 1910.106(b)(1)(iv) and (v) Low pressure tanks Normal operating pressure of the tank shall not exceed the design pressure of the tank. Pressure vessels may be used as low-pressure tanks. Pressure vessels Normal operating pressure of the vessel shall not exceed the design pressure of the vessel.

Tank Storage Outside aboveground tanks 1910.106(b)(2)(ii) Outside aboveground tanks Spacing - (shell-to-shell) between any two flammable or combustible above ground tanks shall be no less than three feet Unstable liquid - Flammable and combustible liquid storage tanks Distance between tanks shall not be less than ½ the sum of their diameter Photo: Fedcenter.gov (US Government)

Tank Storage Outside aboveground tanks 1910.106(b)(2)(ii)(f) Outside aboveground tanks Liquefied Petroleum Gas (LPG) - containers next to flammable or combustible storage shall have a minimum of 20 feet of separation Must be a minimum of 20 feet between these tanks (Illustrations courtesy of MS Clip Art, with additions from Andy Sterlen, NCDOL-OSH Division)

Tank Storage Normal and emergency venting 1910.106(b)(2) Normal and emergency venting Required on all above ground tanks Enough venting to prevent vacuum or rupture Refer to Table H-10 for venting flow rates Illustration: MS Clip Art

Results of Improperly Vented Tank Photo: NFPA Flammable and Combustible Liquids Code Handbook

Tank Storage Drainage, dikes and walls 1910.106(b)(2)(vii) Drainage, dikes and walls Area surrounding aboveground tanks shall be provided with drainage or be diked to prevent accidental discharge of liquid. If diked, the area should be able to hold the capacity of a full tank. Walls of the diked area shall be of earth, steel, concrete or solid masonry designed to be liquid tight.

Tank Storage 1910.106(b)(5) Supports, foundations and anchorage for all tank locations Tank supports shall be installed on firm foundations. Steel supports or exposed piling shall be protected by materials having a fire resistance rating of not less than 2 hours. Tanks shall rest on the ground or on foundations made of concrete, masonry, piling, or steel.

Tank Storage Supports, foundations and anchorage in flood zones 1910.106(b)(5) Supports, foundations and anchorage in flood zones When a tank is located in an area that may be subjected to flooding, check established flood stage markings. Liquid level in the tank must never go below the established maximum flood line Please note: There are many requirements for tanks that are located in flood zones. For more in-depth detail, refer to 1910.106(b)(5)(vi).

Tank Storage Ignition sources 1910.106(b)(6) Ignition sources Precautions shall be taken to prevent the ignition of flammable vapors. Includes but are not limited to open flames; lightning; smoking; cutting and welding; hot surfaces; frictional heat; static, electrical, and mechanical sparks; spontaneous ignition, including heat-producing chemical reactions; and radiant heat. (Clip Art – OSHA.gov)

Pipes, Valves, and Fittings 1910.106(c) The design (including selection of materials) fabrication, assembly, test, and inspection of piping systems containing flammable or combustible liquids shall be suitable for the expected working pressures and structural stresses. (Clip Art)

Container and Portable Tank Storage Applies only to the storage of flammable or combustible liquids in drums or other containers (including flammable aerosols) not exceeding 60 gallons individual capacity and those portable tanks not exceeding 660 gallons individual capacity. Exceptions: storage of containers, mixtures used for maintenance, containers of < 1 gallon, liquids in fuel tanks for motor vehicles and boats.* *Not all inclusive

Container and Portable Tank Storage Only approved containers and portable tanks shall be used Each portable tank shall be provided with one or more devices installed in the top with sufficient emergency venting capacity to limit internal pressure under fire exposure conditions Flammable and combustible liquid containers shall be in accordance with Table H-12

Containers - Table H-12 Container Type Flammable Liquids Combustible Liquids Class IA Class IB Class IC Class II Class III Glass or approved plastic 1 pt. 1 qt. 1 gal. Metal (other than DOT drums) 5 gal. Safety cans 2 gal. Metal drums (DOT specifications) 60 gal. Approved portable tanks 660 gal. Table: NCDOL-OSH Division Note: Container exemptions: (a) Medicines, beverages, foodstuffs, cosmetics, and other common consumer items, when packaged according to commonly accepted practices, shall be exempt from the requirements of §1910.106(d)(2)(i) and (ii).

Container and Portable Tank Storage Storage cabinets Cabinets shall be labeled in conspicuous lettering, "Flammable Keep Fire Away" Must be fire resistant Contain no more than 60 gallons of Class I or Class II nor contain no more than 120 gallons of Class III liquids Specific requirements for metal and wood Photo: OSHA.gov

Container and Portable Tank Storage Inside storage rooms Shall be constructed to meet the required fire-resistive rating for their use If used for Class I liquids, electrical wiring and equipment in “inside storage” rooms shall be approved for Class I, Division 2 Hazardous Locations Provided with either a gravity or a mechanical exhaust ventilation system

Container and Portable Tank Storage In “inside” storage rooms Maintain one clear aisle at least 3 feet wide Containers over 30 gallons capacity shall not be stacked one upon the other Dispensing shall be by approved pump or self-closing faucet only Storage shall comply with Table H-13 (Photo courtesy of OSHA.gov)

Storage Inside Rooms - Table H-13 Fire Protection (1) Provided Fire Resistance Maximum Size Total Allowable Quantities – gals./sq. ft/floor area Yes 2 hours 500 Sq. Ft. 10 No 4* 1 hour 150 Sq. Ft. 5* 2 Table: NCDOL-OSH Division Footnote(1) Fire protection system shall be sprinkler, water spray, carbon dioxide, or other system. *Note: These numbers are shown incorrectly in 29 CFR 1910.106.

Container and Portable Tank Storage Office occupancies Storage prohibited except if required for maintenance, operation of building and operation of equipment Shall be kept in closed metal containers stored in a storage cabinet or in safety cans or in an inside storage room Photo: MS Clip Art

Container and Portable Tank Storage General purpose public warehouses Refer to Table H-14 – Indoor container storage, or Table H-15 – Indoor portable tank storage Flammable and combustible liquid warehouses or storage buildings

Container and Portable Tank Storage Storage outside buildings Maximum of 1,100 gallons of flammable or combustible liquids Area shall be protected against tampering or trespassers Area shall be graded in a manner to divert possible spills away from buildings Storage shall comply with: Table H-16 – Outdoor container storage, or Table H-17 – Outdoor portable tank storage (MS Clip Art)

Container and Portable Tank Storage Fire control Fire control devices shall be available at locations where flammable or combustible liquids are stored. Open flames and smoking shall not be permitted in flammable or combustible liquid storage areas. Water reactive materials shall not be stored in the same room with flammable or combustible liquids.

Industrial Plants 1910.106(e) Incidental storage or use of flammable and combustible liquids Quantity located outside of an inside storage room or storage cabinet: 25 gallons of Class IA liquids 120 gallons of Class IB, IC, II, or III liquids 660 gallons of Class IB, IC, II, or III liquids Kept in covered containers when not in use Photo: MS Clip Art

Industrial Plants Unit physical operations Each building or unit of equipment is accessible from at least one side for firefighting and fire control purposes. Chemical processes shall be separated from the remainder of the plant by a fire wall of 2-hour minimum fire resistance rating. Ventilated at a rate of not less than 1 cubic foot per minute per square foot of solid floor area.

Industrial Plants 1910.106(e) Portable fire extinguishment and control equipment shall be provided to meet the special hazards of operation and storage. All plant fire protection facilities shall be adequately maintained and periodically inspected and tested. Photo from NCDOL-OSH Division

Industrial Plants 1910.106(e) All plant fire protection facilities shall be adequately maintained and periodically inspected and tested to make sure they are always in satisfactory operating condition. Adequate aisles shall be maintained for unobstructed movement of personnel. (MS Clip Art)

Industrial Plants 1910.106(e) Class I liquids shall not be dispensed into containers unless the nozzle and container are electrically interconnected (grounding). Spills shall be cleaned up promptly.

We are not covering… (f) Bulk plants (g) Service stations (h) Processing plants (i) Refineries, chemical plants, and distilleries Photo from Environmental Protection Agency

Summarizing Storage Requirements Consider the following: Occupancy Class of liquids that will be present Engineering specifications such as fire wall size, fire suppression systems, tank design, etc. Maximum volume restrictions State, County and Local codes Marking and labeling requirements HMIS (OSHA.gov)

Summarizing Storage Requirements The flash point determines if a substance falls within the scope of the standard. The flash point and boiling point together, determine how substances are stored: Container capacity and spacing Maximum amount per location The H-Tables help you determine storage limits, venting capacities, allowable sizes of containers and more...

Summary In this course, we discussed the following: Scope of the standard The four elements of the fire tetrahedron and how the standard aims to interrupt those elements Classifying flammable and combustible liquids Storage requirements for liquids covered under the standard (MS Clip Art)

Thank You For Attending! Final Questions?

Flammable Combustible Liquid Chart Table: NCDOL-OSH Division

Class Exercise °F °F Table: NCDOL-OSH Division Use the FP (Flash Point) and the BP (Boiling Point) to determine the Class using the Flammable Combustible Liquid Chart.