Presentation is loading. Please wait.

Presentation is loading. Please wait.

Safe Handling of Flammable and Combustible Liquids.

Similar presentations


Presentation on theme: "Safe Handling of Flammable and Combustible Liquids."— Presentation transcript:

1 Safe Handling of Flammable and Combustible Liquids

2 Flammable and Combustible Liquids The determining factor in whether a liquid is flammable or combustible is its flashpoint. Flashpoint: The minimum temperature at which a liquid gives off enough vapor within a test vessel in sufficient concentration to form an ignitable mixture with air near the surface of the liquid. Remember, it is the vapors, not the liquid, that Burns! A Chemical’s flashpoint is listed in the MSDS under the Fire and Explosion section

3 Flammable and Combustible Liquids Flammable Liquids Any liquid having a flashpoint below 100 o F (37.8 o C) or lower. NFPA Classes IA, IB, & IC Combustible Liquids Any liquid having a flashpoint at or above 100 o F (37.8 o C). NFPA Classes II & IIIA & B

4 Flammable and Combustible Liquid Classifications Flammable Liquid - any liquid having a flashpoint below 100 o F (37.8 o C) or higher, the volume of which make up 99 percent or more of the total volume of the mixture. Flammable liquids shall be known as Class I liquids. Class I liquids are divided into three classes as follows: Class IA - shall include liquids having flashpoints below 73 F (22.8 °C ) and having a boiling point below 100 F (37.8 °C ). Class IB - shall include liquids having flashpoints below 73 F (22.8 °C ) And having a boiling point at or above 100 F (37.8 °C ). Class IC - shall include liquids having flashpoints at or above 73 F (22.8 °C ) and below 100 F (37.8 °C ).

5 Flammable and Combustible Liquid Classifications (Cont.) Combustible Liquid - any liquid having a flashpoint at or above 100 o F (37.8 o C). Combustible liquids shall be divided into two classes as follows: Class II - shall include those with flashpoints at or above 100 ° F (37.8 °C ) and below 140 ° F (60 °C ), except any mixture having components with flashpoints of 200 ° F (93.3 °C ) or higher, the volume of which makes up 99 percent or more of the total volume of the mixture. Class III - shall include those with flashpoints at or above 140 F (60 °C ).

6 Flammable and Combustible Liquids Classifications (Cont.) Class III liquids are subdivided into two subclasses: Class IIIA – shall include those with flashpoints at or above 140°F (60 ° C) and below 200 F (93.3 ° C), except any mixture having components with flashpoints of 200°F (93.3 ° C), or higher, the total volume of which makes up 99 percent or more of the total volume of the mixture. Class IIIB - shall include those with flashpoints at or above 200 F (93.3 °C ).

7 Classes of Flammable and Combustible Liquids 200 140 100 73 IIIA II IC IAIB 100 COMBUSTIBLE (Flash Point >100 F) FLAMMABLE (Flash Point < 100 F) Boiling Point (F) Flashpoint (F o )

8 Flammable Liquids in the Plant Triethalemine 17 o F Barsol A-2316 54 o F Acetone Solvent 0 o F Barsol A-2343 56 o F Barsol A-3447 0 o F N-Butanol 36 o F Sec. Butanol 72 o F Glycol Ether 94 o F Enamel Reducer 20 o F Isopropyl Alcohol 45 o F Methanol 45 o F MEK 23 o F Xylene 79 o F Toluene 45 o F Gasoline -50 o F 142 Solvent 66/3 61 0 F

9 Explosive Limits Explosive limits involve the concentration level of the given chemical in the air. In popular jargon, a vapor/air mixture below the flammable limit is too lean to burn or explode. A mixture above the upper flammable limits is too rich to burn. Most flammable liquids are volatile, meaning they evaporate quickly, and can reach a concentration in air that could lead to an explosion.

10 Lower and Upper Explosive Levels (LEL/UEL)

11 Controlling the potential for fire and explosion with flammable liquids is done through safe Storage, Transfer, Use and Disposal!

12 Hazards of Flammable Liquids Exposure Control Measures Include: Eliminating flames, static electricity, & sparks from electrical circuits. Temperature. Proper Ventilation. Grounding/Bonding. Spill Control/Emergency Response. Proper disposal of spent flammable liquids and soaked rags.

13 Flammable and Combustible Liquids Definitions Grounding: Applying a grounding wire to a container to eliminate a difference in static charge changes the potential between an object and ground. Bonding: Use of a wire between two drums to eliminate the static charge potential between objects.

14 Flammable and Combustible Liquids Definitions Ventilation: Adequate if it is sufficient to prevent the accumulation of significant quantities of vapor-air mixtures in concentrations over ¼ of the Lower Explosive Limit. Safety Can: An approved red container, of not more than 5 gallons capacity, having a spring- closing lid and spout cover and so designed that it will safely relieve internal pressure when subjected to fire exposure. Oily Waste Can: A self closing metal container used to store oil soaked rags.

15 Container & Portable Tank Storage Design, Construction and Capacity of Containers Only approved containers and portable tanks may be used to store flammable and combustible liquids. Not more than 60 gallons of Class I and/or Class II liquids, or not more than 120 gallons of Class III liquids may be stored in an individual cabinet. FLAMMABLE Keep Fire Away

16 Safe Storage Practices No open flames, smoking, sparks or welding is allowed in flammable liquid storage areas. Store in a cool location. Not outside in direct sunlight. The warmer the flammable liquid is the more vapors it generates! Storage shall be in an open or well ventilated area. Do not store need oxidizers. shall be Drums of flammable liquid shall be grounded. A 10 lbs. fire extinguisher shall be readily accessible within the storage area.

17 Storage Inside Building Flammable or combustible liquid drums shall not be stored so as to limit use of exits, stairways, or areas normally used for the safe egress of people. The storage of flammable or combustible liquids in containers or portable tanks is prohibited in office occupancy areas, except that which is required for maintenance and operation of building and operation of equipment. Leaking containers shall be removed to a storage room or taken to a safe location outside and the contents transferred to an undamaged container.

18 Incidental Storage (Small quantities) Liquids located outside of storage cabinets/ areas shall not exceed:  25 Gallons of Class IA in containers. 120 Gallons of Class IB, IC or Class II liquids in containers.

19 Use and Disposal of Flammable Liquids Open flames, smoking, welding/brazing is prohibited in areas where flammable liquids are store, transferred, used or disposed of. Keep containers and drums sealed when not in use. Clean up spills! Maintain good ventilation. Mixing of flammable liquids is prohibited! (Mixing flammable liquids can lower their combined flashpoint.) Rags used to apply flammable liquids are to be disposed of in a self-closing oily waste can.


Download ppt "Safe Handling of Flammable and Combustible Liquids."

Similar presentations


Ads by Google