ELECTRICAL EARTHING.

Slides:



Advertisements
Similar presentations
Mitigation of AC Induced Voltage On Buried Metallic Pipelines
Advertisements

Bonding and Grounding What? Why? How?
The Electrical GuruTM Paul W. Abernathy,CME
Electrical Installation
Chapter 12 Transformers. Chapter 12 Transformers.
Earthing PRESENTATION BY: Er. Satnam Singh Lecturer(Electrical engg.)
GROUNDING SYSTEMS GROUNDING SYSTEMS. The objective of a grounding system are: 1. To provide safety to personnel during normal and fault conditions by.
Earth Ground Resistance The Basics
Stray Current Investigations A Method of Troubleshooting Stray Current on Underground Residential Distribution (URD) Loops Stacey Mighty Malcolm Distribution.
EE4503 Electrical Systems Design
ASSIGNMENT TEACHER Smt. K.VASUMATHY GROUP MEMBERS:- MANSI DWIVEDI (ET 4 TH SEM) ARTI DWIVEDI (ET 4 TH SEM) DIKSHA CHANDRAKAR (ET 4 TH SEM) MAMTA CHOUDHARY.
Protection against Lightning Overvoltages Overvoltages due to lightning strokes can be avoided or minimized in practice by (d) shielding the overhead lines.
AC Mitigation Overview
Lecture 1: Safety and Protection. 1. A robot may not injure a human being or, through inaction, allow a human being to come to harm. 2. A robot must obey.
SUBSTATION HIGH VOLTAGE COMPONENTS
SHUNT CAPACITOR FUNDAMENTALS AND PROTECTION
Disconnect Switches There are many purposes for disconnect switches in substations and power lines. They are used to isolate or deenergize equipment for.
Circuit Protection Electrical circuits require protection to prevent fire or electrocution in the event of a fault. There are two main types of circuit.
DET 310 UNDERGROUND CABLES
PRESENTATION ON SUBSTATION DESIGN
Bonding, Grounding and the NEC  Presented by The National Association of Certified Home Inspectors
Chapter 7 SYSTEM PROTECTION
Electrical Earthing D.K.Pathirana. Applications of earthing Protect human against lightning and earth fault condition Protect the premises against lightning.
UMKC Senior SUBSTATION DESIGN TEAM
Physiological Effects of Electricity on Human Body by Mohd Yusof Baharuddin.
Protection against Electric Shock (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation.
Electricity at Work.
Electrical Safety INSTRUCTOR’S NOTES:
Electrical Installation 2
IEEE Wind Farm Collector System Grounding for Personal Safety Summary of Topics.
POWER SYSTEM PROTECTION
Grounding, bonding, and ground fault currents
Wiring and Grounding.
Gandhinagar Institute of Technology
A PRACTICAL TRAINING SEMINAR ON PLCC
Need for protection Power system must be kept in operation continuously without major breakdowns This can be achieved in two ways: 1.Implement a system.
Chapter 7 Safety. Introduction This chapter covers the following topics: Dangers of electricity Preventive measures Electrostatic discharge Safety practices.
Typical Telecommunications Network
Outdoor Installation 2: Lightning Protection and Grounding Training materials for wireless trainers.
Submitted to: Submitted by:
Introduction to switchgears
A common 400 Hz AC Power Supply Distribution System for CMS FEE. Authors C. Rivetta– Fermilab. F. Arteche, F. Szoncso, - CERN.
Submitted to: Submitted by:
Top Ten Misunderstandings Regarding Over-Voltage Protection Mike Tachick Dairyland Electrical Industries Inc. SIEO, Jan 2016.
Grounding.
A SEMINAR ON 400 KV GSS(RRVPNL) BIKANER.
SMJE 2103 Overvoltage, Electrical Insulation and Protection Devices.
1 Transmission of Electrical Energy Electrical energy is carries by conductors such as overhead transmission lines and underground cables. The conductors.
Grounding the Electrical System Reference: AAVIM “Electrical Wiring” Created May 2007.
SYNERGY INSTITUTE OF ENGINEERING AND TECHNOLOGY
UNIT-5. ELECTRICAL SAFETY, WIRING & INTRODUCTION TO POWER SYSTEM
Grounding the Electrical System
Grounding And Safety Techniques Ms. Tahoora Qureshi, Asst. Professor
WELCOME TO ALL.
Grounding the Electrical System
ELECTRIC SHOCK AND EARTHING
EARTHING.
THREE-PHASE GROUND-FAULT BASICS
Chemical Transfer.
EET 323 – Electrical System Design Lecture 9: Grounding
Grounding System Design and Testing for Critical Facilities
Safety Meeting Topics Standby Generator Safety
A. Touching both terminals with the hands can cause electrical shock
MAINS ELECTRICITY.
Topic 1: Cables and conductors
Electrical components and systems
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
Substation Equipment's
Presentation transcript:

ELECTRICAL EARTHING

Special Note: The approach here is based on standard IEEE 80 (Safety in AC substation grounding) These discussions are for illustration only Grounding practices are subject to local regulations/codes which will take precedence

Objectives of grounding: Provides an electrical supply system with a reference to the groundmass (system grounding) Protective grounding of electrical equipment enclosures Makes them safe to persons who may come into contact with them Enables the flow of fault current in the event of a failure Provides a low impedance path for accumulated static charges and surges (lightning protection grounding) Helps in mitigating the generation and propagation of noise (grounding of shields and signal reference planes)

Earthing System Shall satisfy Safety, Functional requirements of electrical installation Shall ensure Protection against indirect contact Proper functioning of electrical protective devices Protective and functional requirements are met under expected conditions Earth fault, earth leakage currents can be carried safely Adequate strength appropriate to external influences Adequate value of earthing resistance

Benefits (1) Fault damage now minimal Lower outage times Reduces fire hazard (especially in mines) Lower outage times Less lost production, less lost revenue Touch potentials kept within safe limits Protects human life

Benefits (2) Low Fault Currents reduce possibility of igniting gases Minimizes explosion hazard Lower Magnetic or thermal stresses imposed on plant during fault Transient overvoltages limited Prevents stressing of insulation, breaker restrikes

Fault in an Ungrounded System:

System grounding Provides reference for the entire power system to groundmass Establishes a path for current to ground during insulation failure Provides protection against equipment damage due to faults Provides protection against high voltage transients Enables detection by circuit protective devices for isolation Reduces maintenance time and expenditure

Fault in Ungrounded system Single phase ground fault does not result in flow of high fault currents Voltage to ground of other two phases rises by 73% - Causes insulation stress Fault current = Vector sum of capacitive currents in the distributed capacitive reactance of other two phases

Fault in Ungrounded system Intermittent first fault causes transient voltages up to 6 to 8 times nominal system voltage Such high transient voltage can initiate a second fault at weakest insulation point Uncleared arcing fault can cause extensive damage to system Early detection of first fault therefore of paramount importance

Effect of neutral (system) grounding:

Ground fault current flow:

Grounding methods 1 Ungrounded System Neutral connection on Generator/ Transformer is not connected to earth at all

Grounding methods 2 Solid grounding Neutral connection on Generator / Transformer is connected to earth by a solid Conductor Cost Reductiuons due to avoidance of sensitive relays and grounding device, Grading of insulation towards neutral end. But Circulation of third harmonic currents between neutrals

Grounding methods 3 Resistance grounding Neutral connection on Generator / Transformer is connected to earth (0V) through a fixed resistance to limit the earth fault current Mainly used below 33 KV Full line to line insulation required towards neutral

Grounding methods 4 Reactance grounding Neutral connection on Generator / transformer is connected to earth (0V) through a fixed reactance to limit the earth fault current Can be cheaper compared to resistance

Grounding methods 5 Petersen Coil grounding (arc suppression) Neutral connection on transformer is connected to earth (0V) through a variable reactance to neutralise the capacitive earth fault current. Results in arc extinction

Grounding methods 6 NEC grounding (with and without resistance) In HV delta systems no earth connection is available. A 3 phase neutral grounding compensator is connected to allow earth fault currents to flow - allowing detection of these faults

Protective grounding Protects personnel against shocks Personnel do not experience dangerous high voltages when contacting enclosure accidentally connected to live parts Provides a low impedance path for accumulated static charges and surges (lightning protection grounding) Helps in mitigating the generation and propagation of noise (grounding of shields and signal reference planes)

Importance for Earthing An Electrical equipment is considered dead when At or about zero potential Disconnected/ Isolated from live system Disconnection alone not adequate Can retain stored charge Can acquire a static charge Can accidentally be made alive Nearby live conductors may induce voltage

Importance of Earthing ! Ensure earthing before working on electrical equipment Earthing Connect apparatus electrically to general mass of earth in such a manner as will ensure at all times an immediate safe discharge of electrical energy Connect to earthed metal earth bar or spike with good metallic conductor Earthing by Closing of earthing links Attaching of fixed earthing devices Affixing of portable earthing straps

Importance of Earthing Ensure before applying earth Earthing connection is mechanically, electrically in good condition No broken strands Clamps should be rigid and without defect Applied properly in intimate contact with conductors and earth-bar/ spike Earthing cable tails as short as possible Connect to earth first when installing earthing, disconnect earth last while removing earthing

Hazards of improper Earthing Electrocution Burns from arcing Electric shock leading to falls

Bonding Connecting of various grounding systems and non current carrying parts To achieve potential equalization between different accessible conducting surfaces Potential difference between different accessible conducting surfaces, different grounding systems hazardous

Typical Earthing System

Touch, Step, Transferred Voltages

Touch Voltage Permissible Touch Voltage Voltage at any point of contact with uninsulated metal work Within 2.5 mtrs from ground surface and Any point on ground surface within horizontal distance of 1.25 mtrs from vertical projection of point of contact with uninsulated metal work

Step Voltage Difference in surface potential experienced by a person bridging a distance of 1 mtr with his feet apart, without contacting any other earthed object Shall not exceed twice the value of Touch voltage

Touch potentials (Reb =1 ) Person touches transformer tank now live

Touch potentials (Reb = 10 ) Lower touch potential

Transferred Potential Make Allowances for Transferred potential during design, installation Voltage drop in conductors (where voltage rise in earthing system is transferred by metal work to remote location) Otherwise regard Transferred potential as earthing system voltage rise

Transferred Earth Potential Rise Earthing system shall be designed to prevent Transfer of earth grid potentials to a remote earth Transfer of a remote earth potential into a station Breakdown of cable over-sheaths due to voltage differences

Substation grounding practices-1: Grounding design approach depends upon: Voltage class of the system Type of installation (Utility or consumer) LV Systems: Usually solidly grounded Metallic contact between ground of consumer and system neutral Special cases such as SELV power supplies may be of ungrounded type

Substation grounding practices-2: MV Systems: Self contained systems (E.g., Turbo generators): High resistance grounding Industrial systems: Low resistance Critical systems: Tuned grounding OR Ungrounded (for small systems) Utilities: Solid grounding HV/EHV Systems: Solid grounding

A typical ground electrode: Materials Copper Copper clad steel Galvanized steel Copper clad stainless steel

A typical chemical electrode: Sometimes called a leach electrode Chemical mixtures are added to lower resistance of soil Needs regular maintenance

Ground Potential Rise-Example:

Ground Potential Rise-Example:

Voltages in grounding system:

Area of ground grid: HV (outdoor) substations use a buried ground grid for dissipation of fault current to the soil Lower grid resistance to earth is preferable It reduces the ground potential rise with ref. to remote earth Also reduces mesh voltage. Lower mesh voltage is safer because it lowers touch/step voltages Grid of larger area has lower ground resistance and results in lower grid voltage and mesh voltage Further reduction by using vertical electrodes welded to the grid

Soil resistivity: Soil resistivity should be based on an average of measurements done in the substation area Simple designs assume uniform soil Non uniform soil involves complex design steps and requires computer programs Lower resistivity results in lower ground resistance of the grid

Other issues to be taken note of: Soil layers may differ in resistivity Two layer soil model to be considered if variations are found to be high at different depths Transferred potential due to buried services going to/ from the substation (water mains, cable metallic sheath) Introduce non-conducting sections where feasible to avoid transfer of Ground potential

Special attention to be paid to: Operating handles of equipment: Most fatalities occur due to high touch potential at these points Should be made safe by special arrangements Substation fence: Decision regarding keeping isolated vs connecting to substation ground Surge arrestors: Short, direct and low impedance connections GIS extensions

Effective substation grounding - 1: Size ground conductors adequately Use proper bonding and jointing in ground conductors. Poor joints cause high temperatures during a fault to ground Select appropriate ground electrode system Pay attention to soil resistivity. Carry out soil improvement if resistivity is too high. Use chemical electrodes if situation warrants

Effective substation grounding - 2: Pay attention to step and touch potentials Building foundations can also be used as grounding electrodes Integrate fence of outdoor substations as far as possible. Avoid transferred potential from services entering or leaving a substation Pay special attention to operating handles

Effective substation grounding - 3: Cable trays to be properly grounded Surge arrestors to be grounded using short low impedance connections Carry out temporary grounding for safety when personnel have to work on parts which are normally live

Rings of equal potential on earth fault

Recommended maximum grounding resistance values Substation Capacity Maximum Grounding Resistance (Ω) Below 4.16kV Above 4.16kV Below 1000kVA 5 10 1000kVA ~ 5000kVA 2 More than 5000kVA 1 Small Distribution Transformer Banks 15 25

Grounding Methods - Comparison Characteristics Ungrounded Solid Grounding Low Resistance Grounding High Resistance Grounding Personnel Safety Poor Better Good Best Immunity to Transient Over voltages Voltage stress during ground fault Potential flashover to ground Worst

Grounding Methods - Comparison Characteristics Ungrounded Solid Grounding Low Resistance Grounding High Resistance Grounding Protection against Arc Fault damage Worst Poor Better Best Ease of providing Ground fault protection Good Service Reliability Continuity of Service

Grounding Methods - Comparison Characteristics Ungrounded Solid Grounding Low Resistance Grounding High Resistance Grounding Reduction in Fault frequency Worst Better Good Best Ease of Fault Location Protection device coordination Not possible Maintenance Cost