1 New Product Enhancements & VERSION 6.06 Firmware Enhancements GV3000/SEGV3000/SE

2 Feature and Enhancement Summary 1) NEW Expanded Bookshelf Drive Rating 2) NEW Enclosure Kits for Power Modules 3) VERSION 6.06 Firmware Enhancements “FAST FLUX” Added to Sensorless Vector NEW- Regulator Output Configurations NEW- RMI Output Configurations NEW- Analog Input Configurations Modified Parameter Ranges NEW- OCL Speed Control Features

3 NEW Model: 430ER4060 Expanded Bookshelf family NEW Model No.: 430ER4060 Up to 43A V/Hz @ 2kHz Up to 32A Vector @ 2kHz Same programming and functionality Saves panel space Braking circuitry is standard, just add appropriate resistor Offers the user more selections to fit their installation needs NEW - Expanded Bookshelf Drive Rating

4 NEW - Expanded Power Module Ratings Expanded Power Module family 30-60HP @ 460VAC Available 6-01 (50-60HP), 8-01 (30-40HP) Complete power module line from 1-200HP

5 NEW - Expanded Power Module Ratings

6 UL Approved Packaging for Nema Type 1 3 different kits for 460VAC units 2CK4100 ( for 60 to 100 Hp ) 2CK4125 ( for 125 Hp ) 2CK4200 ( for 150 to 200 Hp ) Allows for Machine or Wall mounting Conduit connects to Top & Bottom covers The Drive must be a Rev. 0.7 or higher version drive to accept this kit NEW - Enclosure Kits for Power Modules

7 Improves Sensorless Vector Operability Provides a quick response to a RUN command by eliminating motor “pre-magnetizing” delay Improves coordination of starting up multi-drive systems operating in Sensorless Vector Control Setting U.21 to zero will activate this feature “FAST FLUX” Added to Sensorless Vector

8 “Drive Ready” relay output added Output is energized when there are no faults active Output is de-energized when there are one or more faults active Relay Output can be configured to be energized or de-energized when a fault occurs Provides greater flexibility to user NEW - Regulator Output Configurations

9 Two new Output selections Output turns on based upon speed reference Tie output into machine logic to energize downstream equipment Output is energized when the Terminal Strip start & stop inputs are closed Output is de-energized when when either one of the inputs are open Tie into machine logic so downstream equipment doesn’t start unless this output is energized r.056 and r.053 adjust hysteresis and level NEW - RMI Output Configurations

10 Start and Stop the drive via Speed Reference level P.011 = 12 will allow this mode of operation P.000 must be rE ( Remote / Terminal Strip ) Allows operator to control the drive from only a pot Works in V/HZ, SVC, FVC User configurable turn-on / turn-off levels ! NEW - Analog Input Configurations

11 Trim Gain and Draw Gain Range is now +/- 100% Zero Speed Hold Time Keep the motor magnetized for a longer time period Increased from 20 sec to 655 sec Modified Parameter Ranges

12 Now when RMI (Remote Meter Interface) card is installed Outer Control Loop Speed Reference can come from RMI analog input or Preset Speeds 1-8 When no option is installed Outer Control Loop Speed Reference can come from Preset Speeds 1-8 Greater flexibility when using an outer control loop More options for using the OCL control without the RMI board NEW - OCL Speed Control Features


Download ppt "New Product Enhancements & VERSION 6.06 Firmware Enhancements GV3000/SEGV3000/SE."