Presentation is loading. Please wait.

Presentation is loading. Please wait.

RVS-DN Technical Presentation

Similar presentations


Presentation on theme: "RVS-DN Technical Presentation"— Presentation transcript:

1 RVS-DN Technical Presentation
Yuval Paz – Technical Support Manager March 2008

2

3 Presentation Content 1. Presentation 2. Power Wiring 3. Control wiring
4. Programming 4. Protection

4 Main Features Heavy Duty Design: 400% In, 30 sec. at 50°C, 4 starts an hour Comprehensive Range: A, V Third Generation Digital Field proven experience Fully featured: Control, Comprehensive motor Protection & Supervision User Friendly: Default settings, LCD display, Selectable languages

5 RVS-DN Approvals UL Approved : 8-820A,
1100A and above are designed to meet UL requirements USA cUL Approved : 8-820A 1100A and above are designed to meet cUL requirements Canada CE Approved (EMC & Safety) : A 1800A and above are designed to meet CE requirements European Lloyd’s Approved (ENV 1 & ENV 2) : A 1800A and above are designed to meet Lloyd’s specifications for ENV1 & 2 requirements Marine & Offshore Germaniche Lloyd’s Approved: A 1800A and above are designed to meet Germaniche Lloyd’s specifications Marine & Offshore 56 40

6 RVS-DN Approvals China Compulsory Certificate China
GOST certificate of conformity Russia Det Norske Veritas Marine & Offshore Registro Italiano Navalo Marine & Offshore 56 40

7 Selector Guide – Frame A
To Motor Control terminals (Plug-in) LCD (selectable languages) To by-pass (option) Line LEDs (status display) IP 20 Finger protected for safe operation Model RVS-DN 8 RVS-DN 17 RVS-DN 31 RVS-DN 44 RVS-DN 58 RVS-DN 72 85 41

8 Selector Guide – Frame B
(Bus bar cover removed) Model RVS-DN 85 RVS-DN 105 RVS-DN 145 RVS-DN 170 Line Power Section Control Module (Identical for sizes B-G) To Motor Preparation for bypass contactor is standard in this model To Bypass contactor (not shown in the picture) 85 41

9 Selector Guide – Frame C
Control Module Power Section To Motor Line To Bypass contactor C/Ts Model RVS-DN 210 RVS-DN 310 RVS-DN 390 85 41

10 Selector Guide – Frame D
Control Module Power Section To Motor Line To Bypass contactor C/Ts Model RVS-DN 460 RVS-DN 580 RVS-DN 820 85 41

11 Selector Guide – Frames C,D UL/Marine
Load Line C/Ts Control module Power section (Bus-bar cover removed) Model RVS-DN 210 RVS-DN 310 RVS-DN 390 RVS-DN 460 RVS-DN 580 RVS-DN 820 RVS-DN 950 In RVS-DN 950A C/Ts are mounted outside the soft starter RVS-DN 950A and up must be operated with an external bypass 85 41

12 Selector Guide – Frame E
Control Module Power Section C/Ts Normally mounted Outside the Soft starter To Motor Line Model RVS-DN 1100 RVS-DN 1400 RVS-DN 1800 This model must be operated with an external bypass 85 41

13 Selector Guide – Frame F
Model RVS-DN 2150 Line Power Section C/T Control Module To Motor This model must be operated with an external bypass 85 41

14 Selector Guide – Frame G
Model RVS-DN 2400 RVS-DN 2700 RVS-DN 3000 Line Power Section External C/T are available Control Module To Motor This model must be operated with an external bypass 85 41

15 Selector Guide – 1000V Models
RVS-DN 105A RVS-DN 170A RVS-DN 210A RVS-DN 310A RVS-DN 390A RVS-DN 460A 1000V models 1000V models must be operated with an external bypass 85 41

16 Selector Guide – 1000V Models
RVS-DN 105A RVS-DN 170A RVS-DN 210A RVS-DN 310A RVS-DN 390A RVS-DN 460A 1000V models 85 41

17 Selector Guide – How to Select?
System voltage Motor current and connection Starting conditions Options and control voltage 85 41

18 Selector Guide – How to Select?
System voltage VAC, 50/60Hz, +10% -15% VAC, 50/60Hz, +10% -15% VAC, 50/60Hz, +10% -15% VAC, 50/60Hz, +10% -15% VAC, 50/60Hz, +10% -15% Models: 105A, 170A, 210A, 310A, 390A, 460A. 85 41

19 Selector Guide – How to Select?
Motor current and connection Starter current ≥ motor FLA ! ! ! 85 41

20 Selector Guide – How to Select?
Motor current and connection In line/Inside delta When soft starter is connected “inside delta” lower current is running through the soft starter. Soft starter MUST Be connected exactly as shown in the manual 85 41

21 Selector Guide – How to Select?
Motor current and connection In line/Inside delta Advantages: Smaller dimensions Less expensive Soft Starter Disadvantages: Six wire to the motor – more complicated wiring. No pulse start No curve selection (Curve 0! Only) No energy save No slow speed No phase sequence “off” mode. Although current inside delta is reduced by 1.73 (√3), Soft starter current is reduced by 1.5. For example: for a 870A motor, you can choose a 580A soft starter when connected “inside delta” 85 41

22 Selector Guide – How to Select?
Starting conditions The RVS-DN is able to start at 4xIn, 30 seconds at 50°C 85 41

23 Selector Guide – How to Select?
Options: Communication - RS-485 (Modbus) Communication – Profibus Insulation tester Analog card – Thermistor in and Analog out Harsh environment treatment. Preparation for Bypass contactor Line and load bus bars at bottom Remote panel mounting replacing the original panel. Russian characters LCD display Marine approval UL & cUL approval Tachometer card for special drive systems 85 41

24 Models 8-820A can operate continuously without a bypass contactor
All models from RVS-DN 950A and up and RVS-DN 1000V must be implemented with a bypass contactor Bypass preparation is standard in models RVS-DN A. 85 41

25 Current flow during start
Bypass Contactor Current flow during start 85 41

26 Current flow with bypass contactor
Soft starter must be ordered with preparation for bypass contactor 85 41

27 Bypass contactor connection
Line To motor Bypass Contactor C / T M 85 41

28 How to control the bypass contactor?
L N M End of Acceleration Relay RVS-DN 85 41

29 Control Module (B-G models)
Optional boards: Control Plug Insulation Test board Analogue board Tacho encoder board (only one option can be installed) Control Transformer Dip Switches Power Supply Board Microprocessor & EPROM Fan control jumper Optional comm. boards: RS 485 (MODBUS) Profibus Others upon request Control Supply I / O terminals 85 41

30 Control Module (B-G models)
Auxiliary Relays : C/O, 8A/250VAC * Immediate - with On and Off delays * Fault - prog. Fault / Fail- safe * End of Acceleration - with On delay 8 dip switches 85 41

31 Dip Switches in Control Module
No. Function OFF (default) ON Display Minimum Maximum 2 Tacho feedback Disabled Enabled 3 Mains / Generator Mains Generator 4 Always OFF 5+6 Language selector English, French, German, Spanish, Russian* 7 Extended range Disabled Enabled 8 Software lock Open Locked * Russian display must be specified when ordering. OFF 85 41

32 Dip Switches in Control Module
Dip switch #7 functions Parameter Range Switch #7 - Off Range switch #7 - On INITIAL VOLTAGE 10-50% 5-80% CURRENT LIMIT % % ACCELERATION TIME 1-30 seconds 1-90 seconds MAX. START TIME 1-250 seconds PHASE LOSS Y/N Yes Yes/No MAX SLOW SP TIME O/C or WRONG CON protection in Inside Delta mode. Protection active in normal set Protection active in high set 85 41

33 Presentation Content 1. Presentation 2. Power Wiring 3. Control wiring
4. Programming 4. Protection

34 Mains Wiring In line wiring M L1 L2 L3 Fuses or Circuit breaker
Line Contactor (when required) Soft Starter M

35 Mains Wiring In line wiring with bypass contactor
“Preparation for By-pass” eliminates the need for additional O / L M

36 Mains Wiring In line wiring with pf capacitors M Capacitor (when used)
must be at Line side. A capacitor contactor is not mandatory. L1 L2 L3 Soft starter Motor Fuses or circuit breaker M

37 Presentation Content 1. Presentation 2. Power Wiring 3. Control wiring
4. Programming 4. Protection

38 Control Wiring Control wiring = Wiring terminals in the bottom of the control module (B-G models)

39 ! Control Wiring Aux Contact “Immediate” “End of Acc.” “Fault”
Stop Soft Stop Start E.Save / Slow Sp / Reset D. Adjust / Rev. / Reset Common External Fault Tacho feedback Neutral Aux Contact “Fault” “End of Acc.” “Immediate” 86 94

40 Control Wiring Terminal 21 3P+N+GR - Connect terminal 21 to neutral
3P+N - Connect terminal 21 to neutral 3P+GR - Connect terminal 21 to ground 3P - Leave terminal 21 unconnected 3P - Leave terminal 21 unconnected 3P+GR - Leave terminal 21 unconnected

41 Control Wiring - Terminal 21
Neutral N (1) For Mains system with Ground and / or Neutral - connect Terminal 21 to N or Gr. (2) For Mains system without Ground and Neutral - leave Terminal 21 open N or Gr. (1) 86 95

42 Control Wiring L N Same voltage for Control Supply (1-3) and Control Commands (4-9) Common Neutral Soft Stop Stop E.Save / Slow / Reset D. Adjust / Reverse / Reset Start 86 96

43 Control Wiring D. Adjust / Reverse / Reset E.Save / Slow / Reset
Soft Stop Common Stop Start Neutral Different voltages for Control Commands (4-9) can be AC or DC (must be specified) L N Control Command voltage 86 97

44 Control Wiring - Start / Stop
Motor will soft start when C closes and stop immediately when C opens L N Common Soft Stop Stop E.Save / Slow / Reset D. Adjust / Rev. / Reset Start C 86 98

45 Control Wiring - Start / Stop
E.Save / Slow / Reset D. Adjust / Rev. / Reset Soft Stop Common Stop Start C Motor will soft start when C closes and soft stop when C opens L N 86 99

46 Control Wiring - Start / Stop
Common Soft Stop Stop E.Save / Slow / Reset Start C2 C C1 D. Adjust / Rev. / Reset Push-button operation - Motor will soft start when C closes, soft stop when C1 opens and stop immediately when C2 opens 86 100

47 Control Wiring - Start / Stop
Common Soft Stop Stop E.Save / Slow / Reset Start C L N D. Adjust / Rev. / Reset 86 101

48 Control Wiring - Energy Save
E.Save / Slow / Reset D. Adjust / Rev. / Reset Soft Stop Common Stop Start C Energy Save will operate when Terminal 7 is designated as Energy Save and C closes. For automatic operation use a jumper. L N 86 102

49 Control Wiring - Slow Speed
Slow Speed will operate when Terminal 7 is designated as Slow Speed and C closes before motor starting. Common Soft Stop Stop E.Save / Slow / Reset Start L N C D. Adjust / Rev. / Reset 86 103

50 Control Wiring - Remote Reset
D. Adjust / Rev. / Reset E.Save / Slow / Reset Soft Stop Common Stop Start C1 C2 * Remote (hardwire) Resetting will operate when Terminal 7 or 8 are designated as Reset and C1 or C2 close L N 86 104

51 Control Wiring - Dual Adjustment
D. adjust / Reverse / Re. E.Save / Slow / Reset Soft Stop Common Stop Start C Dual Adjustment (secondary parameter setting) will operate when Terminal 8 is designated as Dual Adjust and C1 closes. L N 86 105

52 Control wiring - D.G. Programming
D. Adjust / Reverse / Re. E.Save / Slow / Reset Soft Stop Common Stop Start C D.G. Program will operate when Dip Switch 3 “Generator” is set to On, Dip Switch 1 “Display format” is set to On, Terminal 8 is designated as Dual Adjust and C closes. L N 86 106

53 Control Wiring - Slow Speed Reverse
D. Adjust / Reverse / Res. E.Save / Slow / Reset Soft Stop Common Stop Start C1 C2 Slow Speed Reverse will operate when Terminal 7 is designated as Slow Speed, Terminal 8 is designated as Reverse and when closing C1 (before starting) and C2 (before or during motor running) L N 86 107

54 “Immediate Relay” Immediate / Shear pin L Relay
Selection by designating the Immediate Relay as: * Immediate - with On and Off delays * Shear pin - When relay is designated as Shear-pin 86 109

55 “Immediate Relay” - Immediate
Immediate Relay Applications * Operating a valve * Opening / closing a brake Off Delay after Stop On delay after Start 86 110

56 “Immediate Relay” - Immediate
Creating special Starting Curves: 1. Designate “Imm Relay” as Immediate and set On Delay time 2. Designate Terminal 8 as “Dual Adjust” and set parameters Immediate Relay D. Adjust On delay Voltage Ramp-up 86 111

57 Bypass Contactor End of Acceleration Relay M
L N M End of Acceleration Relay RVS-DN 86 112

58 Fault Relay Fault Relay 1 2 3 4...9 13 14 15 16 17 18 19 20 21
Fault Relay Fault Relay programmable : Fault - upon fault change position, returns upon fault reset Fault Fail Safe - Upon Control Supply connection change position, upon fault returns, returns upon fault reset. 86 113

59 Control Wiring - External Fault
External Fault input - connected between 19 and 21 (Neutral), use short wires, can be used only when 21 is connected to Ground or Neutral 86 114

60 Control Wiring - Optional Cards
25 26 27 Motor Insulation Alarm 23 24 22 Communication Board (+) RS485 (-) RS485 N.C. Digital Tacho Board Encoder (-) (+) Ground (+) Analogue (-) Analogue Thermistor 28 29 30 31 32 Analogue I/O Board 86 115

61 Control Wiring – Fan Control
Internal Jumper When connected to A - fan (s) will operate as long as Control Supply is connected to Terminals 1-3 When connected to B - fan (s) will operate when Control Supply is connected to Terminal 2 (for example through a N.C. contact of the by-pass contactor) When connected to C - Fan (s) will operate when relay K closes (Automatically upon start signal, stops 5 min. after stop signal or when by-pass contactor closes. Notes : It is recommended to leave at factory default (A). For size A, 44-72A, modification should be done by a field technician. 2 L1 N B A C 3 1 Jumper K 86 115

62 Presentation Content 1. Presentation 2. Power Wiring 3. Control wiring
4. Programming 4. Protection

63 RVS-DN Programming

64 RVS-DN Programming LED indications Green On
Lights when the control supply voltage is connected to the RVS-DN. Yellow Start Lights during soft start, indicating that motor supply voltage is ramping up. Run Lights after completion of the starting process, indicating that motor is receiving full voltage. This LED flashes during slow speed operation. S.Stop Lights during soft stop, indicating that the motor supply voltage is ramping down. Red Stop Lights when the motor is stopped. E.Save/Slow Lights when ENERGY SAVE is in operation. Flashes when the motor is running in SLOW SPEED. D.Adj./Rev Lights when DUAL ADJUSTMENT is in operation. Flashes when motor is running in SLOW SPEED REVERSE. Fault Lights upon operation of any of the built-in protections. Flashes when the INSULATION ALARM optional relay is activated.

65 Presentation Content 4. Programming Shows only when dipswitch #1 is ON
MONITORING PAGE MAIN PARAMETERS START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA Shows only when dipswitch #1 is ON

66 Monitoring Page % OF MOTOR FLA 55% AMP. VOLT 0 0 MOTOR INSULATION
MOTOR INSULATION 52.8Mohm THERMISTOR RES. 3.1 Kohm OPTION CARD NOT INSTALLED

67 Presentation Content 4. Programming MONITORING PAGE MAIN PARAMETERS
START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA

68 Main Parameters STARTER FLC 58 AMP. MOTOR FLA CONNECTION TYPE LINE
As indicated on soft starter’s label As indicated on soft motor’s label. If motor is connected inside delta set MOTOR FLA= (motor rated FLA/√3) Can be set as low as 50% of FLC Set To INSIDE DELTA if soft starter is connected inside delta.

69 Main Parameters UNDERCURR. TRIP 0% OF FLA UNDERCURR. DELAY 10 SEC. UNDER CURRENT - Trips the RVS-DN when the motor current drops below the level that was set for a time period longer than UNDER CURRENT DELAY. Adjustments: Trip Current: Off, 20-90% I FLA Trip Delay 1-40 sec. Applications Dry running pumps Broken belt / gear Closed air inlet (fan) 40 sec. Start I FLA 20% 80% 20 90% 2 83 83

70 Main Parameters O/C SHEAR PIN 850% OF FLA O/C DELAY 0.5 SEC. O/C – SHEAR PIN - Operational when RVS-DN is energized and has three trip functions: At all time - If I > 850% of FLC it trips the RVS-DN within 1 cycle (overrides the value of the O/C – SHEAR PIN setting). At starting process - If I > 850% of FLA it trips the RVS-DN after O/C DELAY (see here after) At run time - If I > O/C – SHEAR PIN setting of FLA it trips the RVS-DN after O/C DELAY Note: The O/C SHEAR PIN is not intended to replace the fast acting fuses, required to protect the thyristors. Adjustments: Trip Current: % of FLA Trip Delay 0-5 sec. Trip 850% IFLA 83 83

71 Main Parameters OVERLOAD TRIP 115% OF FLA OVERLOAD DELAY 4 SEC-AT 5 FLA OVERLOAD TRIP - is operational when running (the RUN LED is lit). Incorporates a thermal memory register that calculates heating minus dissipation of the motor. Trips when the register fills up. The thermal register resets itself 15 minutes after the motor stops. . Adjustments: Trip Current: % of FLA Trip Delay 1-10 sec. 150% 10 sec t 75% 500% 1 sec I 115% O/L setting trip time at 500% FLA 83 83

72 Main Parameters UNDERVOLT. TRIP 300 VOLT UNDERVOLT. DELAY 5 SEC. UNDER VOLTAGE - Trips the RVS-DN when the motor voltage drops below the level that was set for a time period longer than UNDER VOLTAGE DELAY. Adjustments: Trip Voltage: V * Trip Delay 1-10 sec. * V (RVS-DN 1000V) 10 sec. Start Voltage 120V 600V 1 83 83

73 Main Parameters OVERVOLT. TRIP 480 VOLT OVERVOLT. DELAY 2 SEC. OVER VOLTAGE - Trips the RVS-DN when the motor voltage is above level that was set for a time period longer than OVER VOLTAGE DELAY. Adjustments: Trip Voltage: V * Trip Delay 1-10 sec. * V (RVS-DN 1000V) Voltage 750V 150V Start 1 10 sec. 83 83

74 Presentation content 4. Programming MONITORING PAGE MAIN PARAMETERS
START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA

75 Start Parameters SOFT START CURVE 0 (STANDARD) SOFT START CURVE 1 !! SOFT START CURVE 2 !! SOFT START CURVE 3 !! SOFT START CURVE 4 (TORQUE) START CURVE 0 – Standard curve (Default). This curve is the most suitable curve for preventing prolonged starting and motor overheating. Note: When RVS-DN is connected Inside Delta, the RVS-DN will always use CURVE 0 regardless of the curve defined. START CURVES Pump Control - Induction motors produce peak torque of up to 3 times the rated torque towards the end of starting process. In some pump applications, this peak may cause pressure surge in the pipes. Start Curves 1, 2, 3 – During acceleration, before reaching peak torque, the Pump Control Program automatically controls the voltage ramp-up, thus, reducing peak torque. 83 83

76 Start Parameters When starting with a standard soft starter - Starting Torque is reduced drastically, however Peak Torque still remains high, causing high Acceleration Torque towards the end of the starting process. Peak & Acceleration Torque must be reduced to extend the Acceleration time. SOFT START CURVE 0 (STANDARD) SOFT START CURVE 1 !! SOFT START CURVE 2 !! SOFT START CURVE 3 !! SOFT START CURVE 4 (TORQUE) Time Voltage With soft starter Speed Torque M start Accel. D.O.L Load soft 83 83

77 Start Parameters SOFT START CURVE 0 (STANDARD) SOFT START CURVE 1 !!
2 !! SOFT START CURVE 3 !! SOFT START CURVE 4 (TORQUE) Time Voltage Area of Pump Control Start Curves With soft starter Speed 1 2 3 DOL Torque D.O.L 4 83 83

78 Start Parameters SOFT START CURVE 0 (STANDARD) Start Curve 4 (Torque) – Torque Controlled acceleration, provides a smooth time controlled torque ramp for the motor and the load (pump). Note - Always start with Start Curve 0. If towards end of acceleration, peak torque is too high (pressure is too high), proceed to Curve 1, 2, 3 or 4 if necessary. SOFT START CURVE 1 !! SOFT START CURVE 2 !! SOFT START CURVE 3 !! SOFT START CURVE 4 (TORQUE) Time Torque Peak over speed (Torque) acceleration IV Tn Time = t1 Time < t1 Time > t1 Slight time increase smoothes the Peak Linear Torque increase Ideal Conditions 83 83

79 Start Parameters PULSE TIME 0 sec. PULSE TIME - Intended to start high friction loads that require high starting torque for a short time. A pulse of 80% Un without CURRENT LIMIT is initiated to break the load free. Pulse duration is adjustable, 0.1–1sec. After this pulse the voltage is ramped down to INITIAL VOLTAGE setting before ramping up again to full voltage according to the START PARAMETERS settings. Note:There is no PULSE START function when RVS-DN is connected Inside Delta. Un time sec. 83 83

80 Start Parameters INITIAL VOLTAGE 30% INITIAL VOLTAGE - determines the Initial Torque (the Torque is reduced in the square proportion of the voltage reduction). Note: When INITIAL VOLTAGE is set its maximum value, this displays changes to INITIAL CURRENT. Adjustments: 10-50% (80%) Un, should be set so that motor starts turning immediately after Start signal initiated % FLA when INITIAL CURRENT is reached INITIAL CURRENT 100% 10% Initial Voltage 50% Un 83 83

81 Start Parameters INITIAL CURRENT - determines initial Ramp-Up starting Current. When needed, increase Initial Voltage to Max. (over the 50% or 80% respectively). The LCD displays INITIAL CURRENT and the starter will linearly Ramp Up the current following the desired acceleration time. INITIAL CURRENT 100% Current I init.(100%) Imax (400%) Time Linear Current increase Ideal Conditions Start time 83 83

82 Start Parameters CURRENT LIMIT 400% OF FLA CURRENT LIMIT - determines the maximum current during acceleration process and the acceleration time to full speed. Adjustments: % (500%) of FLA Set to the highest acceptable current. U start t soft start U C. L U1 Un I start RPM 400% 100% Current Limit 83 83

83 Start Parameters CURRENT LIMIT/starting time ratio
400% OF FLA CURRENT LIMIT/starting time ratio Lower CURRENT LIMIT => Longer start time Time 4 x In 5 10 15 20 25 30 In 3 x In 83 83

84 Start Parameters ACC. TIME 10 SEC. ACCELERATION TIME - Determines the Voltage Ramp-up Time, from Initial to Full Voltage. Adjustable :1-30 (90) sec. Set to the shortest acceptable time. Time Voltage Ramp-up Time Un U start 30 (90) sec 1 83 83

85 Start Parameters MAX. START TIME 30 SEC. MAX. START TIME - Preventing Stall condition, trips the starter if current is not reduced below Motor FLA within the adjusted time. Adjustments: 1-30 (250) sec. Max. Starting Time Starting Current 20 10 30 83 83

86 Start Parameters NUMBER OF STARTS 10 STARTS PERIOD 30 MIN. START INHIBIT 15 MIN. Limits the NUMBER OF STARTS during the period of time defined by STARTS PERIOD. If you try to start even one more time within that period the START INHIBIT period will take effect. During the START INHIBIT period the WAIT BEFORE RST XX MIN message will be displayed. Adjustments: NUMBER OF STARTS – 1-10, OFF STARTS PERIOD, START INHIBIT min. 83 83

87 Start Parameters RUN CONTACT DEL. 5 SEC. RUN CONTACT DELAY - Sets time delay for END OF ACCELERATION relay to close. Adjustments: sec. L N M End of Acceleration Relay RVS-DN 83 83

88 Presentation Content 4. Programming MONITORING PAGE MAIN PARAMETERS
START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA

89 Stop Parameters SOFT STOP CURVE SOFT STOP CURVE 0 (STANDARD)
1 !! SOFT STOP CURVE 2 !! SOFT STOP CURVE 3 !! SOFT STOP CURVE 4 (TORQUE) STOP CURVE 0 – Standard Curve (Default) – voltage is linearly reduced from nominal to zero. The most stable and suitable curve for preventing prolonged stopping and motor overheating. STOP CURVES 1, 2, 3 Pump Control – In some pump applications, when pumping to higher elevation a considerable part of the torque is constant and does not decrease with speed. It may happen that during the deceleration process when voltage decreases the motor torque abruptly falls below load torque (instead of smoothly decreasing speed to zero), thus closing the valve and causing water hammer. Curves 1, 2 and 3 eliminate the water hammer phenomenon. In pump applications the load torque decreases in square relation to the speed, thus correcting control of voltage to reduce torque adequately and to smooth deceleration to a stop. Note: It is recommended that STOP CURVE 0 be used for all standard applications (not pumps). To reduce water hammer, select STOP CURVE 1, then 2, then 3 in that order. 83 83

90 Stop Parameters When stopping with a D.O.L starter - speed is quickly reduced and flow abruptly stopped. This may cause a Water Hammer (mechanical shock and audible noise) with severe damage to pipes, joints, fittings, valves, etc. SOFT STOP CURVE 0 (STANDARD) SOFT STOP CURVE 1 !! SOFT STOP CURVE 2 !! SOFT STOP CURVE 3 !! SOFT STOP CURVE 4 (TORQUE) DOL opens Un Speed 83 83

91 Stop Parameters Stopping with a standard soft starter - when pumping to a higher elevation, motor torque may quickly fall below load torque (as torque decreases at the square of voltage reduction). This may cause abrupt stalling instead of smoothly decreasing speed to zero, creating the Water Hammer phenomenon SOFT STOP CURVE 0 (STANDARD) SOFT STOP CURVE 1 !! SOFT STOP CURVE 2 !! SOFT STOP CURVE 3 !! SOFT STOP CURVE 4 (TORQUE) Stalling point Un Speed “Soft stop” 83 83

92 Stop Parameters SOFT STOP CURVE 0 (STANDARD) SOFT STOP CURVE 1 !!
2 !! SOFT STOP CURVE 3 !! SOFT STOP CURVE 4 (TORQUE) Time Voltage Area of Pump Control Stop Curves With soft starter Speed 1 2 3 DOL Torque D.O.L 4 Time 83 83

93 Stop Parameters DEC. TIME 10 SEC. DECELERATION TIME - Used for controlled deceleration of high friction loads. Determines the motor’s voltage ramp down time. Adjustments: 1-30 sec. (90) Un Speed Deceleration Time 2 30 / 90 sec 83 83

94 Stop Parameters FINAL TORQUE 0 (MIN.) FINAL TORQUE - Determines torque towards the end of a soft stop. If the current still flows after speed is softly reduced to zero, you should increase the FINAL TORQUE setting. Adjustments: 0(MIN)-10(MAX) Time Check Valve closes and motor stops Voltage Speed Area of Pump Control Final Torque DOL 83 83

95 Presentation Content 4. Programming MONITORING PAGE MAIN PARAMETERS
START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA

96 Dual Adjustment DA: INIT. VOLT. 30% DA: INIT. CURRENT 100% DA: CUR. LIMIT 400% OF FLA DA: ACC. TIME 10 SEC. DA: DEC. TIME DA: MOTOR FLA 31 AMP. Two sets of parameters - for Variable Loads, Two Speed Motors and D.ADJ.:GENERATOR PARAMETERS 83 83

97 Dual Adjustment Using two starting characteristics, the starter will accelerate to DA-IV reaching 100% current limit. After Tx (Imm. Relay delay) voltage to terminal 8 is switched off, using the standard characteristic to complete acceleration. Useful to prevent initial high acceleration. (Applications: Submersible pumps, Drum fans with resonating frequency, etc). U% 100 t 2 25 10 1 Tx 83 83

98 Dual Adjustment Control wring for Dual Adjustment implementing two starting characteristics: 83 83

99 D.ADJ.:GENERATOR PARAMETERS
Usage of D.ADJ.:GENERATOR PARAMETERS mode: The D.ADJ.:GENERATOR PARAMETERS must not always be used when a diesel generator is supplying the RVS-DN. Only use D.ADJ.:GENERATOR PARAMETERS when the normal starting process fails, i.e. SHORTED SCR or WRONG CONNECTION faults occur, and only after you have tested and are sure that the SCRs, motor and motor connections are not faulty.

100 D.ADJ.:GENERATOR PARAMETERS
To operate D.ADJ.:GENERATOR PARAMETERS mode: Set dip switch # 3 and dip switch #1 to on Insert a contact (or jumper) between Control Supply and input terminal 8 (DUAL ADJUST) and close contact to operate the D.ADJ.:GENERATOR PARAMETERS. Dual Adjust LED will light. Set the DUAL ADJUST parameters to the values necessary for the application (e.g., shorter ACCELERATION TIME, lower CURRENT LIMIT, etc.).

101 D.ADJ.:GENERATOR PARAMETERS
Control wring for D.ADJ.:GENERATOR PARAMETERS:

102 Presentation Content 4. Programming MONITORING PAGE MAIN PARAMETERS
START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA

103 EN. Save & SL. SPD Parameters
SAVING ADJUST. 0 (MIN.) SAVING ADJUST - potential saving and P.F. improvement on lightly loaded motors . Adjustable: 0-10 (Min-Max) . Note – may not meet CE requirements I motor time In Un 83 83

104 EN. Save & SL. SPD Parameters
SLOW SPEED TORQ. 8 SLOW SPEED TORQUE - Motor operates at 1/6 speed, Forward or Reverse (no contactors required) Adjustable: 1(MIN)-10(MAX). 1-30 SEC (250) Applications: Positioning Sewage pumps MAX SLOW SP TIME 30 SEC. Speed Nn 1/6 Forward 1/6 Reverse Max. Slow Speed Time 30 Sec. 83 83

105 Presentation Content 4. Programming MONITORING PAGE MAIN PARAMETERS
START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA

106 Fault Parameters PHASE LOSS Y/N YES PHASE LOSS - protection trips the RVS-DN when 1 or 2 phases are missing for more than 1 sec. Notes: The range of the PHASE LOSS can be extended to YES or NO by using the EXPANDED SETTING Do not set PHASE LOSS to NO unless it is found to be necessary in the field! 83 83

107 Fault Parameters PHASE SEQ. Y/N NO PHASE SEQ - protection trips the RVS-DN when phase sequence is wrong. Notes: When RVS-DN is connected Inside Delta, you can not set PHASE SEQUENCE protection to NO. Set to NO when reversing contactors in the input. 83 83

108 Fault Parameters Motor Insulation (optional) - tests motor insulation level when motor is not running (requires a Line Contactor or disconnecting a Line C/B etc. ). Adjustments: Alarm Level: Mohm Trip Level: Off, Mohm Applications Submersible pumps Harsh environments Motors not running for a long period of time. INSULATION ALARM OFF INSULATION TRIP OFF S 83 83

109 Fault Parameters The RVS-DN can be automatically reset for UNDER VOLTAGE and PHASE LOSS faults. To start the motor after UNDER VOLTAGE and PHASE LOSS faults have been cleared, remove the START signal and recommence the signal. Note: AUTO RESET function has a non-programmable time delay of 60 seconds. AUTO RESET NO 83 83

110 Fault Parameters Motor Thermistor Input - Over Temp Protection (option, in place of Insulation Card) Adjustments: THERMISTOR TYPE: PTC or NTC Trip Level: Off, Kohm Note - the Analog card contains also Analog Output, related to motor’s current (0-10VDC, 4-20mA, 0-20mA) THERMISTOR TYPE PTC THERMISTOR TRIP OFF 83 83

111 Fault Parameters If the UNDER CUR. RESET setting is OFF then RVS-DN will not automatically reset after an UNDER CURRENT TRIP fault occurs. If you set the UNDER CUR. RESET setting to a time value then RVS-DN will automatically reset with a delay (the time defined for UNDER CUR. RESET), but only after the start signal is removed. To restart the motor recommence the start command. Adjustment: 10-120min., off UNDER CUR. RESET OFF 83 83

112 Presentation Content 4. Programming MONITORING PAGE MAIN PARAMETERS
START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA

113 I/O Programming Parameters
PROG. INPUT #7 RESET PROG. INPUT #8 DUAL ADJUSTMENT FAULT RELAY TYPE FAULT IMM/ S.PIN RELAY IMMEDIATE RELAY ON DELAY 0 SEC. RELAY OFF DELAY AN. OUT PARAMETER I, % OF FLA RESET, SLOW SPEED, ENERGY SAVER DUAL ADJUSTMENT, SLOW SPD REVERSE, RESET FAULT, FAULT-FAIL SAFE IMMEDIATE, SHEAR PIN SEC.(IMMEDIATE), 0.0-5SEC (SHEAR PIN) I, % OF FLA; I, % OF FLC or inverted(1000V) 83 83

114 Presentation Content 4. Programming MONITORING PAGE MAIN PARAMETERS
START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA

115 Comm. Parameters Modbus menu Profibus menu PROTOCOL MODBUS BAUD RATE
PARITY CHECK EVEN SERIAL LINK NO. OFF S. LINK PAR. SAVE DISABLE SER. LINK CONTROL FRONT COM ADDRES COMM. PROTOCOL PROFIBUS BAUD RATE AUTO (PROFIBUS) PROFI.NETWORK ID 126 S. LINK PAR. SAVE DISABLE SER. LINK CONTROL FRONT COM ADDRES OFF STORE ENABLE COMM. PARAMETERS Modbus menu Profibus menu 83 83

116 Presentation Content 4. Programming MONITORING PAGE MAIN PARAMETERS
START PARAMETERS STOP PARAMETERS DUAL ADJUSTMENT PARAMETERS EN. SAVE & SL. SPD PARAMETERS FAULT PARAMETERS I/O PROGRAMMING PARAMETERS COMM. PARAMETERS STATISTICAL DATA

117 Statistical Data LAST STRT PERIOD NO DATA LAST STRT MAX I
TOTAL RUN TIME 0 HOURS TOTAL # OF START LAST TRIP TRIP CURRENT 0 % OF FLA TOTAL # OF TRIPS PREVIOUS TRIP -2 NO DATA . PREVIOUS TRIP -9 83 83

118 Presentation Content 1. Presentation 2. Power Wiring 3. Control wiring
4. Programming 4. Protection

119 Protection Under/Over Frequency
Operational when the RVS-DN is energized and protects the motor when the frequency is less than 45 or greater than 65Hz. Phase Loss Operational when the RVS-DN is energized, provided this protection has not been de-activated. Phase loss protection trips the RVS-DN when 1 or 2 phases are missing for more than 1 sec. Phase Sequence Operational when the RVS-DN is energized, provided this protection has not been de-activated. Phase sequence protection trips the RVS-DN when phase sequence is wrong. 83 83

120 Protection Wrong Connection
Operational after start signal. Trips if motor is not properly connected to the RVS-DN’s load terminals, when internal disconnection is detected in the motor winding. This protection is not active when D. ADJ.: GENERATOR PARAMETERS is selected. C R 400V 83 83

121 Protection Shorted SCR
Trips the RVS-DN if one or more of the SCRs have been shorted. This protection is not active when D. ADJ.: GENERATOR PARAMETERS is selected. Heat-Sink Over Temperature Thermal sensors are mounted on the heat-sink and trip the RVS-DN when the temperature rises above 85ºC External Fault External Fault becomes operational when RVS-DN is energized. The RVS-DN will trip if contact closes for more than 2 sec. 83 83

122 Protection Timing And Occurrence Active During Start Run Stop
Soft Stop Too many starts with START INHIBIT period Electronic overload with curve selection O/C shear pin (jam) RVS-DN protection – trip immediately at I≥850% FLC Motor protection – trip function During start – factory set at 850% FLA after O/C DELAY. During run – adjustable 200 – 850% FLA after O/C DELAY. Under current adjustable time delay Phase loss Phase sequence 83 83

123 Protection Timing And Occurrence Active During Start Run Stop
Soft Stop Under voltage with adjustable time delay. Time delay is override in case of PHASE LOSS. Over voltage with adjustable time delay Long start time (stall protection) Shorted SCR Wrong connection (load loss) External fault – input from a N.O. contact SCR protection by Metal Oxide Varistors (MOV) RVS-DN over-temperature RVS-DN internal test, when the On LED is lit. Motor insulation test (optional) – Two levels for alarm & trip. When installed, operates when mains voltage is removed. Motor thermistor (optional) – programmable PTC/NTC, with adjustable trip level. 83 83

124 RVS-DX Technical Presentation
Yuval Paz – Technical Support Manager

125 RVS-DX

126 Presentation content 1. Presentation 2. Power & control Wiring
3. RVS-DX vs. RVS-DN

127 Main features Digital Soft Starters with internal bypass and motor protection 8-1100A; V For enhanced Applications and Price Driven Market Includes most of the RVS-DN winning features. Standard Duty Design include bypass: 350% In, 15 sec. at 40°C Range: A, V Third Generation Digital circuitry Field proven experience Incorporating : Soft Start, Current Limit, Soft Stop, Comprehensive Motor Protection, built-in internal bypass Simple Installation and operation Narrow footprint (book type) Power and cos phi measurements UL, cUL to 170A

128 Starter Frame Motor KW Type Size 400V RVS-DX 8 4 RVS-DX 17 7.5
RVS-DX 31 D RVS-DX RVS-DX 58 D RVS-DX RVS-DX 85 D RVS-DX RVS-DX 145 D RVS-DX RVS-DX RVS-DX D RVS-DX RVS-DX D RVS-DX RVS-DX RVS-DX RVS-DX 950 D7 550 RVS-DX Starter should be selected according to motor’s Full Load Amp and starting conditions 85 132

129 RVS-DX Front Panel Sizes : D1 8-44A LED’s for status D2 58-72A display
Line LCD for programming Data & statistics display Simple 6 pushbutton operation IP A Finger protected for safe operation End of Acceleration and fault relays (Plug-in) Load Control terminals (Plug-in) 65 133

130 RVS-DX Internal Components
End of Acceleration & Trip (prog.) Relays – 1 N.O. each SMT components Compact size Aluminum case Built-in Bypass for minimum heat dissipation 35 136

131 AX, DX Internal view Line C/T Bypass Relay Latched, 12VDC
>145A two in parallel Thyristor Semitop up to 44A Standard above it Motor 35 136

132 Presentation content 1. Presentation 2. Power & control Wiring
3. RVS-DX vs. RVS-DN

133 Power & control wiring

134 Presentation content 1. Presentation 2. Power & control Wiring
3. RVS-DX vs. RVS-DN

135 RVS-DN vs. RVS-DX Construction RVS-DN RVS-DX Starting ratings
400% In, 30 50°C 350% In, 15 Built-in Bypass - Enclosed, rugged construction Preparation for by-pass contactor Internal Bypass Starter voltage range 220-1,000V V Starter current range 8 – 3,000A 8 – 1,100A Operating temperature range 0 – 50°C 0 – 40°C 129

136 RVS-DN vs. RVS-DX Start / Stop Features RVS-DN RVS-DX
Digital Micro Processor base Soft Start Soft Stop Current Limit Torque Control – optimizing starting & stopping process Current Control Pulse Start (Kick Start) Dual Adjustment - 2 start/stop characteristics and overload, designed for varying load applications and 2 speed motors Pump Control - six start / stop curves 129

137 RVS-DN vs. RVS-DX Start / Stop Features (Continued) RVS-DN RVS-DX
Slow Speed - 1/ 6 nominal speed for positioning Electronic Reversing at Slow Speed Linear Acceleration - tacho. feedback 0-10V - Special Starting Process - for weak diesel generator supplies Energy saver 129

138 RVS-DN vs. RVS-DX Motor & Starter Protection RVS-DN RVS-DX
Too Many Starts with Start Inhibit period Electronic Overload with Curve Selection Electronic Fuse with two settings for Start & Run Under Current, adjustable Time Delay Phase Loss Phase Sequence Under Voltage with adjustable Time Delay Over Voltage with adjustable Time Delay Long Start Time (Stall Protection) 129

139 RVS-DN vs. RVS-DX Motor & Starter Protection (Continued) RVS-DN RVS-DX
Shorted SCR Wrong Connection (Load Loss) External Fault - input from a N.O contact SCR Protection by Metal Oxide Varistors Starter Over Temperature Motor Insulation test, two levels for Alarm & Trip Optional No 129

140 RVS-DN vs. RVS-DX Displays RVS-DN RVS-DX
LCD - two lines 16 characters, language selection between English, French, German, Spanish, displaying: Parameter settings, Motor current, Insulation level (when option is included), Statistical Data : Last start current & time, Total Run time, Total number of Starts & Trips, Last Trip Language selection by Internal dip-switch Software Illuminated LCD Indicating lights for complete status display 8 LEDs 4 LEDs 129

141 RVS-DN vs. RVS-DX Control RVS-DN RVS-DX
Digital, Microprocessor Control Opto-isolated control inputs Auxiliary relays (total No. of relays) 3 C/O 8A/250V, 1800VA 2 N/O 5-8A/250V “Immediate” contact” with adjustable On & Off time delays. “End of acceleration” contact with adjustable time delay “Fault” contact Immediate contact can be set as Shear Pin Alarm - Local and Remote Reset (hard wired or by communication) 129

142 (consult factory for smaller sizes)
RVS-DN vs. RVS-DX Control (Continued) RVS-DN RVS-DX Communication RS485 with MODBUS protocol for full control (parameter modification, start, stop, reset etc + supervision) Option Communication Profibus protocol for full control (parameter modification, start, stop, reset etc + supervision) Option for 75A and up (consult factory for smaller sizes) 210 and up Analog Card includes: Analog output, related to motor’s current, selectable 0-10VDC or 4-20mA or o-20mA and Thermistor input selectable as PTC or NTC. 129

143 Analog soft starters Technical Presentation
Yuval Paz – Technical Support Manager

144 RVS-AX Analog Soft Starter with internal bypass* and motor protection
8-170 A; V For Simple Application and the Price Driven Market * Internal bypass in A models 64 130

145 RVS-AX Advantages UL cUL
Standard Duty Design include bypass: 300% In for 30 sec, 350% In for 20 sec 400% In for 5 sec. at 40°C, 4 starts per hour. Range: 8-170A, V Third Generation Analog Field proven experience Incorporating : Soft Start, Current Limit, Soft Stop, Motor Protection, internal bypass (31-170A models) Narrow footprint (book type) Simple Installation and operation UL cUL 64 131

146 RVS-AX Selector Guide Starter Frame Internal Motor KW
Type Size ByPass V RVS-AX RVS-AX RVS-AX 31 A ■ 15 RVS-AX ■ 22 RVS-AX 58 A ■ RVS-AX ■ 37 RVS-AX 85 A ■ 45 RVS-AX ■ 55 RVS-AX 145 A ■ 75 RVS-AX ■ 90 Starter should be selected according to motor’s Full Load Amp and starting conditions 85 132

147 RVS-AX Line Sizes : A1 8-44A A2 58-72A A3 85-105A A4 145-170A
Potentiometers for simple adjustments LEDs for status display IP A Finger protected for safe operation (8-44A models ) Control terminals (Plug-in) Load 65 133

148 RVS-AX - Control wiring
End of Acc. Fault No Connection Start Stop Neutral * Control voltage to the electronic circuitry is derived from three phase supply * Connect Neutral to terminal 3 to enable Phase Loss Protection (when Neutral is not available or not connected to Terminal 3 starter may not detect Phase Loss of lightly loaded motors. * Use “dry contact” between terminals 1&2 to start/stop the soft starter. * Do no apply start/stop signal to terminals 1&2 simultaneously with voltage to terminals L1, L2, L3. 86 135

149 RVS-AX - Easy Adjustments
Motor FLC % Starter FLA setting * Initial Voltage % Un Current Limit % Motor FLA setting Ramp-up Time sec. Ramp-down Time sec. Overload Trip 115% Motor FLA setting, factory set. * e.g. for motor 100A and Starter 105A, set x 100 = 95% 35 136

150 RVS-AX - Motor Protection
Electronic overload Phase Loss Heatsink Over Temperature Built in bypass (31-170A models) 83 137

151 RVS-AX - Applications Pumps Fans and blowers Compressors
Transport systems Conveyors Weak mains and generator networks 53 147 4

152 Solstart Plus Analog Soft Starters with internal bypass and motor protection 31-170A; V For Simple Application and the Price Driven Market Unique – 2 phase control, motor protection and bypass 64 130

153 Solstart Plus - Sizes and features
Solstart+ type FLC [A] Dimensions WxHxD [mm] Start/stop by Voltage free contact EOA Relay Fault Relay Aluminum case Din Rail mounted Solstart + 31 31 65x190x114 O - Solstart + 44 44 Solstart + 58 58 120x265x121 Solstart + 72 72 120x265x12-1 Solstart + 85 85 Solstart + 105 105 Solstart + 145 145 129x275x182 Solstart + 170 170 65 133

154 Solstart Plus - Control wiring
Start/Stop Fault End of Acc. * ~ { Control Voltage * End of Acceleration output relay from 58A and up. 86 135

155 Solstart Plus - Easy Adjustments
Motor FLC % Starter FLA setting * Initial Voltage % Un Current Limit % Motor FLA setting Ramp-up Time sec. Ramp-down Time sec. Overload Trip % Motor FLA setting, factory set. * e.g. for motor 100A and Starter 105A, set x 100 = 95% 35 136

156 Solstart Plus - Motor Protection
Electronic overload Under Voltage Phase Loss Heatsink Over Temperature Built in bypass 83 137

157 Solstart Plus - Applications
Pumps Fans and blowers Compressors Transport systems Conveyors Weak mains and generator networks 53 147 4

158 Solstart Analog Soft Starters with internal bypass 31-170A; 230-600V
For Simple Application and the Price Driven Market Unique – 2 phase control and bypass 64 130

159 Solstart - Technical Advantages
Current Range: A Initial Voltage: % Ramp-up Time: Sec. Ramp-down Time: Sec. Starts per hour 4. (10 starts per hour for light loads) Protection IP 20 Mounting DIN Rail (8-31A) 141

160 Solstart - Marketing Advantages
Motors A , V 690V is available) (4-37KW, 5-40HP) Standard Duty Design include bypass: 350% In for 5 sec, 4 starts per hour. (Up to 10 starts per hour at light loads) Includes a bypass Second Generation Easy settings & operation Compact Small foot print Cost Effective Simple replacement for Star/Delta Systems Starts single phase motors as well as three phase motors 141

161 Solstart - Two-phase Control
a. Voltage is control no two phases only b. Internal by-pass relays c. One phase Motor start (only in 230V version) U V W End Of Acceleration (31-170A) 142

162 Solstart 8-170A – Din rail and EOA relay
W L2 L3 L1 U V 8-22A Start W L2 L3 L1 U V 31-170A EOA Din Rail Standard EOA relay - NA Din Rail – Optional (31-58A) EOA relay - Standard

163 Solstart - Easy Adjustments
A, V - Soft Start - Soft Stop - Compact - Easy to use 35 143

164 Solstart - Technical details
Max. Current: A Initial Voltage: % Ramp-up Time: Sec. Ramp-down Time: Sec. Starts per hour: 4 (Max. 10 starts per hour for light applications) Protection: IP 20 (31-58A) Adjustment: Three potentiometers Mounting: DIN Rail up to 22A, Option 31-58A Dual Phase Bypass: One phase (L2-V) direct connection End Of Acceleration: Standard Relay output A, N.A. 8-22A Enclosure: ABS No Smoke Plastic 8-22A, Molded Aluminum A

165 Solstart - Applications
Small Pump Motors Fans and blowers Compressors Transport systems Conveyors 53 147 4

166 Analog soft starters comparison
RVS-AX Solstart Solstart Plus Starting capacity 300% 30 sec. 4 starts per hour 350% 5 sec. 4 starts per hour 300% 15 sec. 4 starts per hour Range 8-170 31-170 Controlled phases 3 2 Control voltage No control voltage V AC/DC Control input Dry contact Protection Electronic overload Phase loss Heat sink over temperature No Protection Under voltage LEDs ON RampUp/Down Run Overload Over temperature Ramp Fault Settings IV-10-50% Ramp Up-2-30sec Ramp Down sec IV-10-80% Ramp Up-0.5-5sec Ramp Down-0.5-5sec Ramp Up sec Ramp Down sec Output contacts End of acceleration End of acceleration (31A and up) End of acceleration (58A and up) 53 147 4

167 The End 53 147 4


Download ppt "RVS-DN Technical Presentation"

Similar presentations


Ads by Google