Aqualean Product Presentation 1 By Laurent Domenget Product Manager, Rooftop & Packaged Air Units.

Similar presentations


Presentation on theme: "Aqualean Product Presentation 1 By Laurent Domenget Product Manager, Rooftop & Packaged Air Units."— Presentation transcript:

1 Aqualean Product Presentation 1 By Laurent Domenget Product Manager, Rooftop & Packaged Air Units

2 AQUALEAN - Introduction 2 Water-to-Air Packaged Unit (air conditioner) Cooling only or Reversible From 2 to 20 kW For buildings equipped with a water-loop:  Open-plan and cellular office buildings  Hotel rooms  Shopping areas  …

3 AQUALEAN - Main Characteristics 3  High efficiency system connected to a water loop (balanced or unbalanced water loop)  R410 Scroll compressor & Electronic expansion valve  Compact solution and reduced height for easy integration in narrow dropped-ceiling  Ceiling installation for sale surface optimization  Quiet operation thanks to variable speed fan motor  Low energy consumption with airflow rate variation  Zoning requirements in cellular office buildings  Independent consumption monitoring and maintenance  Wide communication interfaces (ModBus, LonWorks, BACnet)  Fireproof insulation

4 AQUALEAN - Range 4 AQUALEAN 002003007008010012015018020 Net Cooling Capacity (kW) 2,22,76,88,010,211,214,517,019,0 Net EER 4,2 4,03,94,0 4,34,14,0 Voltage 230V/50Hz/1Ph400V/50Hz/3Ph AQUALEAN 002003007008010012015018020 Net Heating Capacity (kW) 2,93,38,09,512,313,517,019,522,0 Net COP 4,54,63,8 3,93,83,73,83,6 Voltage 230V/50Hz/1Ph400V/50Hz/3Ph COOLING HEATING Heating condition: Air inlet temperature 20°C DB – Water inlet temperature 20°C at nominal water flow Cooling condition: Air inlet temperature 27°C DB/19°C WB – Water inlet temperature 30°C at nominal water flow Cooling limits Heating limits

5 AQUALEAN – Technical Description 5 Dimension: Cabinet: Galvanised steel (not painted) 3 access panels to compressor area and electronic board for maintenance Airflow configuration: From factory: On the side (90°) Size 007 to 015: In-line possible on site by turning the fan Size 018 & 020: In-line possible on site by turning fan and by removing 2 sheet metal parts Hanging device: Unit can be easily connected to the ceiling thanks to hanging device. Installer can use a threaded bar connected to the ceiling and fix the unit with nuts

6 AQUALEAN – Technical Description 6 Insulation: 25mm A2,s1,d0 / M0 insulation in air section (Size 002&003: M1 insulation) Thermal/acoustic insulation in compressor area Supply fan: Direct drive forward curved blades with variable speed supply fan. Galvanized steel casing and blades. (Size 002&003: plastic blades and casing) Filter: Washable G2 filter on rail Condensate drain pan: Large sloped drain pan with ¾” connection Air/Refrigerant Heat Exchanger: Aluminium fins and copper tubes designed to provide the higher heat exchange. Water/Refrigerant Heat Exchanger: Brazed Stainless Steel Plate Heat Exchanger Optimized to reduce pressure drops (less than 50kPa) (Size 002&003 : coaxial HE)

7 AQUALEAN – Technical Description 7 Compressor: Scroll compressor with internal thermal protection and vibration absorbent blocks. (Size 002&003 : Horizontal rotary compressor) Thermodynamic circuit: R410A refrigerant Electronic Expansion Valve 4-way valve (for reversible units) Copper tubes Filter drier Liquid receiver Controler: Climatic 60 controler Master/slave up to 10 units DC60 customer display with integrated thermostat to be connected on site (optional for size 002&003) ModBus/BACnet/Lonworks communication Temperature sensor: -Supply air/Return air -Water inlet/Water outlet -Evaporating refrigerant (+Discharge refrigerant for size 002&003) Low pressure transducer High pressure switch Condensate level sensor (size 002&003)

8 AQUALEAN - Article number explanation 8

9 AQUALEAN – Airflow configuration 9  Supply airflow On the side (90°)  Supply airflow In-line Units leave the factory with airflow configuration supply on the side of the unit (90° angle versus return). The fan can be easily re-positionned, on site, to have the supply outlet in-line.

10 AQUALEAN – Heating options 10  Electrical heater AQUALEAN 002003007008010012015018020 Electrical Heater Small -2 kW3 kW5 kW Electrical Heater Medium -5 KW9 kW Electrical Heater High -9 kW12 kW Small electrical heater size complies with Spanish RITE regulation (maximum 1,2x compressor capacity) NOTE: Only SMALL electrical heaters are available for REVERSIBLE units

11 AQUALEAN – Control options 11  ModBus/BACnet/Lonworks interface A communication interface can be added to the Climatic controler in order to communicate to a Building Management System. Communication table are already loaded into the controler. Available protocols:ModBus (RS485 or TCP/IP) BACnet (RS485 or TCP/IP) Lonworks (RS485)  DS60 Service display This display provides access to the full controler menu to set all parameters. Service Display

12 AQUALEAN – Safety & Electrical options 12  Main switch Main disconnect switch is lockable to make a safe access to electrical panel. It is installed on the electrical panel door and control all parts. It can also be used as an emergency cut off.  Compressor phase protection Three phase protection located at the electrical box of the unit to ensure that the compressor will not operate if phases are connected wrongly. Only available for 400V 3Ph 50Hz units.

13 AQUALEAN – Hydraulic options 13  Water filter The water filter protects the unit against particles (greater than 1mm) getting inside the water circuit, and prevents the water heat exchanger getting dirty or clogging. The water filter must be fitted in the water inlet of the unit. Increase pressure drops (see documentation for values). Supplied loose.  Flow switch and water differential pressure transducer The flow switch or the water differential pressure transducer stops the unit if water flow is lower than the minimum flow. Automatic reset. Supplied loose.

14 Options – Other options 14  Low noise Compressor noise attenuation jacket.  Low water loop temperature (LWLT) Addition of a 3-way valve and high pressure transducer to operate the unit below 15°C (down to 0°C). The controler will monitor the 3-way valve (+VFC for the water pump). The 3-way valve is supplied loose (pressure transducer factory mounted).

15 AQUALEAN – eLencal v2.0 15 AQUALEAN will be available for selection in the new eLencal v2.0 In Light Configuration.

16 AQUALEAN – Technical details 16 * Air inlet: 27°C DB/19°C WB – Water Inlet 30°C ** Air inlet 20°C DB – Water inlet 20°C

17 17


Download ppt "Aqualean Product Presentation 1 By Laurent Domenget Product Manager, Rooftop & Packaged Air Units."