1 Programming 2100 Series Controllers

2 Relay Control Programming Basics

3 Offsets and Differentials, 2 Setpoints

4 Offsets and Differentials, 1 Setpoint

5 Proportional Control Programming Basics

6 Direct Acting - Output 12mA @ Setpoint

7 Reverse Acting - Output 12mA @ Setpoint

8 Direct Acting - Output 4 or 20mA @ Setpoint
Cooling Heating

9 Reverse Acting - Output 4 or 20mA @ Setpoint
Cooling Heating

10 Controller Programming

11 2100 Series Controller Programming
Menu-by-Menu Examples Follow Along Onscreen Some Slides Printed in Handout Product Manuals in Reference Section Sub-Systems in Ubiquity Manual Sect. 12

12 Factory Defaults Preprogrammed
Programming Basics Factory Defaults Preprogrammed MUST Change Address – Default is Default is 10X (SL2108 => 108) NO LCD on Device – Must Use: Revelation Professional 2.4 Ubiquity on Standalone QD2040 Ubiquity on Internet Ubiquity Mobile **available for download**

13 Programming Options

14 PC Based Software -- Revelation Professional
Menu Driven Programming Use for Network Setup & Testing, Commissioning, & Load Balancing “Read” Before Making Changes “Write” Before Going to NEXT Menu “Write” vs. “Write Half / Write Page” “Load All” & “Save All” Options *** NOT SUPPORTED AS OF JAN 2009 ***

15 PC Based Software -- Insight
Similar to Revelation Professional… Tab Driven Interface Uses Same Datasheets as Ubiquity Use for Network Setup & Testing, Commissioning, & Load Balancing Shows Current Values (no “read” required) “Write Page” Before Going to New Tab *** NEW SOLUTION AS OF JAN 2009 ***

16 Internet Style Software – Ubiquity
Similar to Revelation Professional Single Page for all Programming Info Shows Current Values (no “read”) Writes all Values on “Submit” “Read Controller” Option if Needed Same for Internet Based Site and Standalone QD2040

17 QD2040 Multi-Function Site Comm. Center
Stand-Alone/Dial-In, Dial-Out, or Ethernet Configuring the Controller Network Controller Addressing Setup Web Page Veris Meter (ModBus) Support XML Support Several Models Available REG & –MAX

18 Where to Get Help or Answers
Instructions Sent with Product TCS Basys Controls Catalog Ubiquity Manual Training & Reference Manual Call TCS Directly –

19 2100 Series Controllers

20 SL2105 - Five Channel Lighting Module
Independent, 365-Day Scheduling for ALL 5 Channels Digital & Analog Light Sensor Inputs Analog Current or kW Input 5 Relay Outputs 2 “Demand Limit” Outputs Astronomical Clock

21 SL2108 - Eight Channel Lighting Module
Independent, 365-Day Scheduling for ALL 8 Channels Digital & Analog Light Sensor Inputs Analog Current or kW Input 8 Relay Outputs 2 “Demand Limit” Outputs Astronomical Clock

22 Indoor or Security Lighting Outdoor or Landscape Lights
SL2105 & SL2108 Applications Indoor or Security Lighting Outdoor or Landscape Lights Parking Lot Lights and Signs Daylight Harvesting Lighting Load Shedding Power Monitoring

23 SL2108 – eight channel lighting controller

24 SL2108 – eight channel lighting controller

25 SL2108 – eight channel lighting controller

26 Screenshots or Live View…
Skip to Next Controller…

27 SL2108 – eight channel lighting controller

28 SL2108 – eight channel lighting controller

29 SL2108 – eight channel lighting controller

30 SL2108 – eight channel lighting controller

31 SL2108 – eight channel lighting controller

32 SL2108 – eight channel lighting controller

33 SL2108 – eight channel lighting controller

34 SL2108 – eight channel lighting controller

35 SL2108 – eight channel lighting controller

36 SL2108 – eight channel lighting controller

37 SL2108 – eight channel lighting controller

38 SZ2141 - Refrigeration Controller
Control 1 Cooler with Defrost & 2 Freezers with Defrost and Fan 6 RTD Inputs (-40 to 160°F) 5 Analog Inputs (4 to 20mA) 6 Digital Inputs 8 Relay Control Outputs 1 Relay Alarm Output

39 SZ2141 - Refrigeration Controller

40 SZ2141 - Refrigeration Controller

41 SZ2141 - Refrigeration Controller

42 SZ2141 - Refrigeration Controller

43 SZ2141 - Refrigeration Controller

44 Screenshots or Live View…
Skip to Next Controller…

45 SZ2141 - Refrigeration Controller

46 SZ2141 - Refrigeration Controller

47 SZ2141 - Refrigeration Controller

48 SZ2141 - Refrigeration Controller

49 SZ2141 - Refrigeration Controller

50 SZ2144 – Large Refrigeration Monitor
3 RTD (-40 to 160°F) or Thermistor (-20 to 120°F) Inputs 3 RTD Inputs (20 to 220°F) 2 Analog Inputs (4 to 20mA) 3 Analog Inputs (0 to 5V) 8 Digital Inputs 1 Relay Output (local alarm)

51 SZ2144 – Large Refrigeration Monitor

52 SZ2144 – Large Refrigeration Monitor

53 SZ2144 – Large Refrigeration Monitor

54 SZ2144 – Large Refrigeration Monitor

55 SZ2144 – Large Refrigeration Monitor

56 Screenshots or Live View…
Skip to Next Controller…

57 SZ2144 – Large Refrigeration Monitor

58 SZ2144 – Large Refrigeration Monitor

59 SZ2144 – Large Refrigeration Monitor

60 SZ2144 – Large Refrigeration Monitor

61 SZ2144 – Large Refrigeration Monitor

62 Control 4 Boilers with Chiller Support
SZ Boiler Controller Control 4 Boilers with Chiller Support Automatic Rotation of Boilers & Pumps 365-Day Scheduling 6 RTD & 5 Digital Inputs 1 Analog Input (4 to 20mA) 2 Analog Outputs (4 to 20mA) 9 Relay Outputs

63 One or Two Boilers with Reset
SZ2165 Application SZ Boiler Controller One or Two Boilers with Reset

64 SZ Boiler Controller

65 SZ Boiler Controller

66 SZ Boiler Controller

67 SZ Boiler Controller

68 SZ Boiler Controller

69 SZ Boiler Controller

70 SZ Boiler Controller

71 Screenshots or Live View…
Skip to Next Controller…

72 SZ Boiler Controller

73 SZ Boiler Controller

74 SZ Boiler Controller

75 SZ Boiler Controller

76 SZ Boiler Controller

77 SZ Boiler Controller

78 SZ Boiler Controller

79 SZ2166 - Chiller Controller
Stage 4 Chillers with Boiler Support Automatic Rotation of Chillers & Pumps 365-Day Scheduling 6 RTD Inputs 5 Digital Inputs 2 Analog Outputs (4 to 20mA) 9 Relay Outputs

80 SZ2166 - Chiller Controller

81 SZ2166 - Chiller Controller

82 SZ2166 - Chiller Controller

83 SZ2166 - Chiller Controller

84 SZ2166 - Chiller Controller

85 SZ2166 - Chiller Controller

86 SZ2166 - Chiller Controller

87 Screenshots or Live View…
Skip to Next Controller…

88 SZ2166 - Chiller Controller

89 SZ2166 - Chiller Controller

90 SZ2166 - Chiller Controller

91 SZ2166 - Chiller Controller

92 SZ2166 - Chiller Controller

93 SZ2166 - Chiller Controller

94 SZ2166 - Chiller Controller

95 SZ2161 - Heat Pump Water Loop Controller
Control 4 Boilers & a Water Tower Automatic Rotation of Boilers & Pumps 365-Day Scheduling 6 RTD Inputs 5 Digital Inputs 12 Relay Outputs 2 Analog Outputs (4 to 20mA)

96 SZ2161 Application Cooling Tower

97 SZ2161 - Heat Pump Water Loop Controller

98 SZ2161 - Heat Pump Water Loop Controller

99 SZ2161 - Heat Pump Water Loop Controller

100 SZ2161 - Heat Pump Water Loop Controller

101 SZ2161 - Heat Pump Water Loop Controller

102 Screenshots or Live View…
PLUS Loop Sub-System and Supply Loop Sub-System Skip to Next Controller…

103 SZ2161 - Heat Pump Water Loop Controller

104 SZ2161 - Heat Pump Water Loop Controller

105 SZ2161 - Heat Pump Water Loop Controller

106 SZ2161 - Heat Pump Water Loop Controller

107 SZ2161 - Heat Pump Water Loop Controller

108 SZ2161 - Heat Pump Water Loop Controller

109 HVAC Sub-Systems – Loop Control Setup Guide
Click “Create Loop System” button Select sub-system definition (Loop Controls) Enter a descriptive name for sub-system Select master & secondary master controllers from drop-downs (only appropriate, available controllers will be shown) Select fallback flow switch & related control point from drop-downs Select the desired master controller schedule from drop-down Click the “Submit” button

110 HVAC Sub-Systems – Loop Control

111 HVAC Sub-Systems – Loop Control

112 HVAC Sub-Systems – Loop Control

113 SZ2181 - Air Handling Unit Controller
Enthalpy Based Economizer Option 365-Day Scheduling 6 RTD & 5 Digital Inputs 4 Analog Inputs (4 to 20mA) 3 Analog Outputs (4 to 20mA) 2 Heat & 2 Cool Stages 2 Selectable Heat and/or Cool Stages

114 SZ2182 – Advanced AHU Controller
Enthalpy Based Economizer Option 365-Day Scheduling 6 RTD & 5 Digital Inputs 4 Analog Inputs (4 to 20mA) 4 Analog Outputs (4 to 20mA) 2 Heat & 2 Cool Stages 2 Selectable Heat and/or Cool Stages

115 Face & Bypass Damper Control Static Pressure Control
SZ2182 Applications Dehumidification Face & Bypass Damper Control Static Pressure Control Heat Pump with Economizer Control

116 SZ2181 - Air Handling Unit Controller

117 SZ2181 - Air Handling Unit Controller

118 SZ2181 - Air Handling Unit Controller

119 SZ2181 - Air Handling Unit Controller

120 SZ2181 - Air Handling Unit Controller

121 Screenshots or Live View…
PLUS VAV Sub-System and Superzone™ CZS Sub-System

122 SZ2181 - Air Handling Unit Controller

123 SZ2181 - Air Handling Unit Controller

124 SZ2181 - Air Handling Unit Controller

125 SZ2181 - Air Handling Unit Controller

126 SZ2181 - Air Handling Unit Controller

127 SZ2181 - Air Handling Unit Controller

128 HVAC Sub-Systems – VAV System Setup Guide
Click “Create VAV System” button Click “Add Sub-system” button Click “Controllers” to expand table of options Click “Controller Selection” to expand table Select controllers to include in sub-system (only allowable controllers are selectable in this list) Click “Controller Detail” to expand table Select units for Discharge Air Temp. Sharing Click “System Parameters” to expand table Enter a descriptive name for sub-system

129 HVAC Sub-Systems – VAV System Setup Guide
Select master/main controller from drop-down (only appropriate, available controllers will be shown) Set other “System Parameter” options: Occupied Mode Operation Unoccupied Mode Operation VAV System Type (pressure independent for this example) Duct Static Pressure Controller Backup Discharge Air Sensor Warm Up Mode Operation Morning Warm Up Termination Time/Temp & Options Secondary Boiler & Chiller Master Controllers Click “Submit” button

130 HVAC Sub-Systems – VAV System

131 HVAC Sub-Systems – VAV System

132 HVAC Sub-Systems – CZS System Setup Guide
Click “Create Superzone System” button Click “Add Sub-system” button Click “Controllers” to expand table of options Click “Controller Selection” to expand table Select controllers to include in sub-system (only allowable controllers are selectable in this list) Click “Controller Detail” to expand table Select units for Discharge Air Temp Sharing & for Voting functions Click “System Parameters” to expand table

133 HVAC Sub-Systems – CZS System Setup Guide
Enter a descriptive name for sub-system Select master/main controller from drop-down (only appropriate, available controllers will be shown) Set other “System Parameter” options: Occupied Mode Operation Cool Priority Mode Operation Heat Priority Mode Operation Voting Mode Operation Unoccupied Mode Operation Backup Discharge Air Sensor Bypass Damper Controller Minimum Demand

134 HVAC Sub-Systems – CZS System Setup Guide
Set other “System Parameter” options: (cont’d) Tie Break Controller Priority Zone Controller Majority Maximum Run Time Minority Maximum Run Time Enable Hot Deck/Cold Deck Secondary Boiler and Chiller Master Controllers Hot Deck/Cold Deck Unoccupied Options Click “Demand Proportioning” to expand table & set desired options Click “Submit” button

135 HVAC Sub-Systems – Superzone™ System

136 HVAC Sub-Systems – Superzone™ System

137 HVAC Sub-Systems – Superzone™ System

138 Where to Get Help or Answers
Instructions Sent with Product TCS Basys Controls Catalog Ubiquity Manual Training & Reference Manual Call TCS Directly –