1 New features, more applications with PQube 3 Power Analyzers
PSL Symposium Prague Jun 2018

2 New features, more applications with PQube 3 Power Analyzers
Data Centers UPS Monitoring Utilities grid operators, DER/PV integrators Utilities & commercial /industrial Manufacturing Healthcare facilities New product (summary) New features (summary)

3 Data Centers Problem solving: Explain, justify costly investments in design for reliability – during design and during operation Problem solving: measure & optimize power profile optimization up to four (4) 3-phase PDUs NEW ! Problem solving: Prevent PDU overloading (breaker trips) Load shedding ---- colocation /shared hosting / in-house

4 Data Centers NEW Load shedding: CRAC = computer room air conditioning
Firmware Q3 2018 NEW Load shedding: Turn OFF CRAC units before the PDU overloads (circuit breaker trip) and Turn CRAC units back ON when the overall consumption is back within limits CRAC = computer room air conditioning

5 Data Centers How load shedding works Ex: 2 threshold load shedding
Consumption (PDU load) CR AC #2 OFF Relay 2 Trigger threshold Hysteresis Relay 2 Return Threshold CRAC #1 OFF Hysteresis How load shedding works Ex: 2 threshold load shedding Watts Relay 1 Trigger threshold Relay 1 Return Threshold Up to 4 X 3-phase loads or up to 8 thresholds … Relay 1 Active Relay 2 Active

6 Data Centers Load shedding works with relays… which relays?
RM8 – 8 relay output module Up to 2 modules …. 16 relays

7 Data Centers Impact of earthquake on specific racks/equipment:
The “shake” is not identical from one rack to the other Detect seismic wave impact or mechanical shock impact – LOCALLY

8 Data Centers : who to sell to ?
PDU RACKS UPS POC GENSET

9 Manufacturing: alarm & control
New! RM8 + PQube 3 or PQube 3e additional relays 1+8 = 9 relays New! PQube 3r PQube 3 with 3 additional relays 1+3 = 4 relays

10 Utilities: grid operators, DER/PV integrators
Problem solving: insure generation performance remains in compliance with regulations during and after commissioning Voltage /VAR response Voltage/ frequency ride through Net /import /export energy Solar and environment conditions Grid stability : real time measurements, phasor measurements – > New! GRID ANALYZER

11 Utility Grid operators, DER/PV integrators

12 Monitoring UPS performance
Problem solving: identify root cause of power outage Did the UPS work properly? NEW! : Input AND output power monitoring NEW! : assess UPS equipment performance = efficiency! Firmware Q3 2018

13 Monitoring UPS performance
With PQube 3e and VAT1-600! Option: Battery bank monitoring

14 Monitoring UPS performance

15 Utilities, oil/water treatment industries
Problem solved: integration of PQube 3 analyzer with existing SCADA systems Communication protocol : DNP 3.0 (IEEE ) Level 1 – polling data points Level 2 – alarm when value exceeds a dead band (configured by the DNP3 client application) Level 3 – encryption (version 3.7.0) DNP3 opens door to larger bids…

16 Utilities and industries (Europe, Asia, South America)
Problem solving: reduce time, training & personnel to prepare and review compliance reports EN50160 embedded reports Condensed summary Sent by .. daily, weekly.. Compliant New in 3.6.X ! Non compliant

17 New feature : EN 50160 embedded reports
EN50160 limit (100%) 95% of the variations above the nominal voltage compliance margin 95% of the variations below the nominal voltage Pass/fail status

18 New feature : EN 50160 embedded reports
EN50160 limit (100%) Individual harmonic compliance margin Here, 95 % of the time Harmonic rank 15 is below 22% of the max compliance threshold Individual harmonic pass/fail status

19 Utilities and industry
Problem solving: Reduce time, training & personnel to prepare reports The embedded ITIC graph Firmware release Q3

20 Utilities and industry verticals
Firmware release Q3 A great sag/swell event overview sent from your PQube 3 ! Quickly identify the events out of the compatibility curve. Delivered with the embedded report: Daily, weekly, monthly

21 Healthcare facilities

22 Healthcare facilities
> Power monitoring > disturbance detection > operational environment monitoring New ! Vibration detection New in 3.6.X !

23 New products, new modules Summary
PQube 3 : 32GB internal memory (Jan2018) Combination PMU and Power Analyzer : GridAnalyzer PQube 3 for control applications: PQube 3r Extension relay module : RM8

24 2kHz-150kHz Conducted emissions
New in firmware 3.6.x (3.6.3 released Apr 2018) 2kHz-150kHz Conducted emissions Change to balanced sensitivity map Separate color maps sensitivity for 2-9kHz and 8-150kHz GIF graphs

25 Improvements: 2kHz-150kHz color map
3-Phase view Phase by phase view

26 New features Summary EN 50160 embedded reports Protocol DNP3
2kHz ~ 150kHz conducted emissions: > Phase by phase color maps (optional) > Separate sensitivity for 2-9kHz and 8-150kHz Vibration detection and recording Analog channels configurable gain and now configurable offset

27 This was “what’s new” Thank you! Questions , please…