Presentation is loading. Please wait.

Presentation is loading. Please wait.

Factory Options, Accessories & Economizers

Similar presentations


Presentation on theme: "Factory Options, Accessories & Economizers"— Presentation transcript:

1 Factory Options, Accessories & Economizers

2 Commercial Accessory Review

3 Serial Number Review The first two characters of the serial number are necessary when ordering LP kits.

4 Model Number Review

5 RKNL-C series are DDC or Communicating Units

6 Factory Option Codes

7 Field Installed Accessory Selection

8 Impact of Energy Issues on Economizers
Economizers Yesterday Save money by utilizing free outside air instead of mechanical equipment Provide ventilation with demand control ventilation No direct feedback of operation or fault detection Controllers today More complex control requirements for additional energy savings Simplified diagnostics and verifiable operation Traceable operation and maintenance Meet CA title 24, ASHRAE and ICC codes and standards 64% Installed Rooftop Economizers Do Not Work!

9 Economizers Normal Operation

10 Economizers Economizer Operation

11 Economizers Horizontal Downflow Downflow Configurations Only
Fully Modulating – Allow 100% outside air Horizontal Downflow Shipped As Single Enthalpy Factory Installation Available Downflow Configurations Only Cost is the Same No Additional Cost for Installation Longer Lead Time Plug – n – Play Large Units Small Units Field Configured RRNL, RRPL, RRRL, etc.

12 Economizers

13 Smoke Detectors Economizers Smoke Detector
Factory Installed only in Economizer D4120 in Rheem Replacement Parts If Field installing, Need Sampling Tube RSI 60-SMK-01WH

14 Economizers Dual Enthalpy Separate Item Field Installed Smoke Detector
Installed Option Not Field Installed

15 Backward Compatibility  Forward to Meet New Standards

16 W7220 Economizer Interface
Terminal Options

17 W7220 JADETM Economizer Controller
Information: STATUS SETPOINTS SYSTEM SETUP ADVANCED SETUP CHECKOUT ALARMS 2 LINE LCD 16 CHARACTERS/LINE MENU UP (EXIT) BUTTON SCROLL(UP/DOWN) BUTTONS SELECT (ENTER) BUTTON

18 Economizer System Sensors
New Accurate Sensors

19 New Economizer Sensors
3 position DIP switch C7250A 20k temperature sensors C7400S Sylkbus Two sensors – color coded to match label on module

20 Economizers CO2 Sensor Molex Plugs 9 Pin to 12 Pin Adapters
Separate Item Field Installed Wall Mounted Duct Mounted Available Ordered from Honeywell Molex Plugs 9 Pin to 12 Pin Adapters

21 Power Exhaust Field Installed
Most Applications with RA Duct Static Greater Than 0.2” w.c. Only For Use With Economizers Notes: Economizers include Barometric Relief damper, which is installed. Dampers have rubber seals that minimize air leakage in off cycle, but also attenuate damper blade noise. Barometric Relief Damper

22 Fresh Air Dampers Low Cost Alternative to Economizers
Manual Damper – allows 50% outside air Fixed Blade Motorized Damper – allows 50% air Open During Occupied Mode Some Are Complete Kits Some Are Motor Added to Manual Damper Not For Use With Economizers or Power Exhaust Downflow or Horizontal Applications

23 Roof Curbs RXKG-CAE14 14” Height RXKG-CAE24 24” Height
Factory Sloped Curbs Residential Heat Pumps Not For Sloped Roof 3rd Party for Sloped Applications Curb Adaptors – Listed in Spec Sheets For Previous Generation Rheem/Ruud Only Other Adaptors Available From Third Party Vendors

24 Hail Guards Standard 12 ½ Ton “Designed Out” on Large Units
Slope Coil Design No Longer Necessary Optional 10 Ton and below

25 Heat Exchangers Aluminized Steel 10 Year Warranty Stainless Steel
Optional Good Value 20 Year Warranty Commercial Application Three Phase Lifetime Residential Application Single Phase

26 Other Accessories High & Low Pressure Control
Standard Unwired Convenience Outlet Optional on All Units Requires Separate Power Source Unfused Service Disconnect Gas/Electric Only Not Available for Heat Pumps or Package A/C

27 Sources for Coating Coils
Other Accessories Sources for Coating Coils AERO-MARINE Engineering OR AME. T. Dennis Sutherland ---- Bryson, Texas – Technicoat. Thermo Guard located in Houston TX – BLYGOLD HVAC Corrosion Protection – FL. Contact – Bill Herrera at Prostock Parts in North Carolina also carries part number in a spray can for coating coils for salt air protection. All correspondence is between the Distributor and Coil Coater. Not the Factory.

28 Application Notes Ruud products are designed for human comfort and can be used for other conditioning needs Units are not designed as “make-up air” units or for hostile environments Hot Gas Reheat and VFD Currently Available

29 Additional Notes When installing a package unit on a roof curb remove shipping material from under the unit Prior to start-up remove shipping blocks from under the compressor. Failure to do so may result in transmitted noise Economizer sheet metal hoods and screens are shipped inside the unit for protection. Some parts have subtle differences. Identify all parts prior to assembly Electric Heater kits for Package Heat Pumps and Package Cooling units are not the same kits that are used in residential air handlers

30 Additional Notes KEEP THE ECONOMIZER PLUG
This is a must for diagnostic procedures in the future All Accessory Model Numbers begin with RX (Green) / AX (Gray) For example, RXRD = AXRD except the color Residential Package Economizers are the same for Horizontal or Vertical installation When Installing an Economizer/Hoods Two scratch awls come in mighty handy Layout everything before starting

31 Questions?


Download ppt "Factory Options, Accessories & Economizers"

Similar presentations


Ads by Google