Presentation is loading. Please wait.

Presentation is loading. Please wait.

Pre-Engineered Water Surface Water Treatment Plants

Similar presentations


Presentation on theme: "Pre-Engineered Water Surface Water Treatment Plants"— Presentation transcript:

1 Pre-Engineered Water Surface Water Treatment Plants
MICROFLOC® Products WaterBoy™ & Aquarius®

2 Topics Discussed Equipment Design Features Application Areas

3 WaterBoy Flow Diagram

4 WaterBoy Features Coagulation, flocculation, 7 1/2° tube settling and mixed media filtration Completely pre-assembled single tank units in sizes up to 60 gpm Standard sizes WB-14, 27, 82 and 133A Standard flows 10, 20, 60 and 100 gpm Clarification based on equivalent settling surface area of 100 gpm / ft2 Detention time in flocculator - 10 minutes

5 Microfloc WaterBoy™

6 WaterBoy Process Operation Backwash
Flow set with influent valve or float Filter level float valve Chemicals added upstream of tank Flash mix and one flocculation stage Flow up through tubes and down through filter Water pumped to storage Filter headloss starts backwash (vacuum) Drain siphon primed Tubes siphon drained Backwash pumped through filters and tubes Drain siphon broken Tubes filled with clean backwash and placed back in operation

7 WaterBoy Application For water temperature above 50° F
Up to 200 NTU Up to 100 true color Up to 10 mg / L iron Up to 5 mg / L manganese For water temperature below 50° F, reduce above criteria by up to 50 % Higher solids loading than Tri-Mite Lower solids loading than Aquarius

8 WaterBoy Sweet Spots Treats surface and ground waters
Size permits portable installations on skids and trailers Ideally suited for small communities, low flow industrial applications, resorts and recreational sites Over 300 installations

9 Microfloc Aquarius®

10 Aquarius Flow Diagram

11 Aquarius Features Coagulation, two stage flocculation, 7 1/2° tube settling and mixed media filtration Two tank system shipped loose Standard sizes AQ-70B, 112B, 150B & 300B Available in 350, 520, 700 and 1400 gpm Clarification based on equivalent settling surface area of gpm / ft2 Detention time in flocculator - 20 minutes

12 Aquarius Design Mixed Media Filter Two-Stage Flocculation
w/ MULTIBLOCK® UD Two-Stage Flocculation Tube Settlers

13 Aquarius Process Operation Backwash Set flow with influent valve
Filter level float valve Chemicals added upstream of tank Two floc stages Flow up through tubes and down through filter Water pumped out to storage Filter headloss starts backwash (vacuum) Waste valve opened Tubes drained Backwash pumped through filters into tubes Waste valve closed Tubes filled with clean backwash and placed back in operation

14 Aquarius Application For water temperature above 50° F,
Up to 400 NTU Up to 200 true color Up to 20 mg / L iron Up to 10 mg / L manganese For water temperature below 50° F, reduce above criteria by up to 50 % Higher solids loading than WaterBoy

15 Aquarius Sweet Spots Economical packaged treatment
Use in industrial applications for power, electronics, pulp & paper, potable water, process cooling water and zero discharge Over 300 installations across North America; over 600 worldwide

16 Summary Economical Plant Designs
Flocculation, Tube Settler, & Mixed Media Filter WaterBoy ideal for low flows & smaller footprint Aquarius targeted for larger flow plants & higher solids

17 Pre-Engineered Water Surface Water Treatment Plants
MICROFLOC® Products WaterBoy™ & Aquarius®


Download ppt "Pre-Engineered Water Surface Water Treatment Plants"

Similar presentations


Ads by Google