David Mcfarlane1 CMS Gas Systems (Nitrogen, Argon & CO2)

Slides:



Advertisements
Similar presentations
Parker domnick hunter Industrial Gas Generation
Advertisements

E906 Gas System 1/7/09 LANL Meeting D. Northacker UIUC.
Gas Laws.
David Capal, CEM, CHFM, SASHE David Womack 1.5 Contact Hours /0.15 CEU AHA/ASHE.
André Augustinus 16 June 2003 DCS Workshop Safety.
Compressed Gases.
The RPC Closed loop Gas System. Schedule for completion - update Status Supplier: ok Mixer: ok Humidifier: ok Purifiers: installed, but not completely.
1 MEDICAL GASES We breathe earth’s atmosphere composed of:  Nitrogen (78%)  Oxygen (21%)  Carbon Dioxide (0.03%)  Argon and trace gases (0.93%) Neon,
Gas Laws Mr. Gates Created by Educational Technology Network
Daya Bay Muon Subsystem Review, 7/28-29/2007, IHEP, Beijing Daya Bay RPC Gas System: Design Report & Budget Estimate Changguo Lu, Kirk McDonald Princeton.
Stefan Moeller Exp. Areas Conventional October 24, Experimental Areas - Conventional Facilities Stefan Moeller.
By Will Parnell. * The system creates propulsion using an inert gas such as Nitrogen or Helium as the fuel. * The gas is stored under high pressure, then.
Molar Volume, Density and Molar Mass
To Do… Discussion tomorrow. LonCapa Exam Review (due Friday, February 14 by 7 pm) Exam Tuesday, February 18 1.
Chapter 12 The Behavior of gases
Central Region Discussion Power and Cooling GDE Beijing-CFS.
June 2004 Andrea Gaddi, PH-CMI USC Installation Commissioning Task Force 1st Run Meeting, June 3rd, 2004.
Gases Review. Pressure Conversions kPa = ________atm.
Point 5 - Cooling Network - Key Primary Water Chilled Water Mixed Water Eau Bruite Standard Power Diesel Backup Comp Air Primary Water at 20-25C – Produced.
Elemental Analysis. Elemental Analysis (EA) - Weight percentages of C, H, N, S done by combustion in O 2 - Gas chromatographic analysis of CO 2, H 2 O.
Dick Loveless 20 January Status of UXC Dick Loveless 20 January 2010.
Homework Check (The Ideal Gas Law) 1.If I contain 3 moles of gas in a container with a volume of 60 L at a temperature of 400 K, what is the pressure inside.
GIF++ gas systems 21/01/2014Ernesto, Roberto PH-DT-DI gas service1.
Summer Updates- Summer Student Report Emine Altuntas Stephen Fee Supervisors: Mar Capeans, Ivan Glushkov, Roberto Guida Gamma Irradiation Facility.
J.Pothier CERN EP/CMIC.Schäfer CERN EP/L3D. J.Pothier CERN EP/CMIC.Schäfer CERN EP/L3D SAFETY J.Pothier (GLIMOS) C.Schäfer (deputy GLIMOS) DISMANTLING.
Computer Rooms 101 Geoffrey Day. Will the floor collapse? 42RU rack - 115kg 40 * 1Ru servers - HP DL360, 16.78kg each Shelves, cables etc 15KG per rack.
Gas cutting equipment. MIG WELDING  MIG welding :  metal inert gas welding: a method of welding in which the filler metal wire supplies the electric.
Active gas system status. S.Konovalov, K.Zhukov. Active gas system operation. S.Konovalov "Active gas system..."TRT Overview  Good design.
Section Six.
Magnet & services projects P. Tropea 9 Nov 2011 – CMS upgrade workshop.
TOF Gas System Project Overview. Content Prototype for Aging tests done for RPC’s TOF Gas System: parameters and module layouts. Special Technology: channel.
19/02/2014A. D'Auria CERN/PH-DT-DI Maintenance ID flushing system:  Maintenance 2 dryers  Installation 2 flow meters  Maintenance of several hygrometers.
Gas Systems for Particle Detectors R.Guida on behalf of the PH-DT-DI/Gas Service Team PH-DT Seminar CERN September 4 th, 2014.
Associated detection/extinction systems D. Swoboda.
Nitrogen 78% Oxygen 21% Gases in Dry Air Trace Gases 1% Trace Gases Percentage by Volume Argon Carbon dioxide Neon Helium Methane Krypton Hydrogen 0.93.
TK Dry Gas System Operation  System overview  Dry Gas Consumption  Interlocks and thresholds  Documentation  Operational model  Final comments.
Festo in BiotechPharma and Cosmetics
Exhaust to atmosphere G1 V1 V2 V3 LN2 Storage Vessel 150 l Dewar Cryostat Exhaust to atmosphere Nitrogen or helium gas bottle LN2 Circuit for MIT Test,
Cable Layouts, Connectors for the LHC GAS SYSTEMS GAS COORDINATION MEETING, OCTOBER 2005 PH / DT1 GS.
Total Cross Section, Elastic Scattering and Diffraction Dissociation at the LHC January 17, 2003TOTEM plenary meeting -Marco Bozzo1 CSC detectors for T1.
HW Review 1.35 A tank of gas with a total pressure of 12.0 atm contains a mixture of oxygen, nitrogen and argon. If the partial pressure of nitrogen.
GIF++ gas systems 11/07/2014Ernesto, Roberto PH-DT-DI gas service1.
LH2 Safety Issues for MICE 1.O2/LH2 separation 2.No Ignition sources near LH2 3.Adequate ventilation 4.Affects: Windows: absorbers and vacuum Primary and.
Composition of the atmosphere. Composition of the Atmosphere ▪Composition = what something is made of. ▪ “Air” is all around us and it behaves often like.
Johan Bremer, 22th-26th September 2008 Cryogenics Operations 2008, CERN, Geneva, Switzerland 1 CRYOGENICS OPERATIONS 2008 Organized by CERN Safety aspects.
Luke or MTS Q anode. MOBY DICK  Purpose of Moby Dick:  Can we even get to ~10 ppb O 2 and H 2 O?  What other things in Moby will cause loss of LAr.
TS-CV-Detector Cooling 22-Jan-04P. Tropea - JCOV1 Design, construction and installation of a double loop fluorocarbon 150 kW cooling plant for the CMS.
CMS consolidation activities of detector cooling system Detector cooling project P. Tropea.
SOME CEDAR NEWS Lau Gatignon / EN-MEF TD meeting 12/07/2011  Summary of HAZOP and Zoning meeting  Forthcoming CEDAR related work at CERN.
ATMOSPHERE 17.1 ATMOSPHERE IN BALANCE. KATRINA.
Gay-Lussac’s LawGay-Lussac’s Law  Pressure and temperature relationship  Pressure results from molecular collisions  Pressure of gas is DIRECTLY proportional.
26/03/2014L-Ph. DE MENEZES & F. MERLET CERN/PH-DT-DI New recuperation system for n-Pentane:  Installation of the module in parallel of the first.
Overview on the Proposal for a new Gamma Irradiation Facility at CERN GIF++ Mar CAPEANS April 29 th, 2009 April 29, 091M.C.
RPC DSS & DCS Action Matrices Review Anton Dimitrov CMS Action Matrix Review 2015, 06.Mar.2015, CERN, Geneva.
CMS-GEM gas system GEMs for CMS High Eta Muons - Workshop III, CERN April R.Guida PH-DT-DI.
The closed loop system at ISR We moved the system at ISR in January. Preliminary tests has been done in order to verify the possible use in the “ISR conditions”:
Totem Gas Systems ( T1, T2 ) F. Hahn and S. Haider PH / DT1.
Service Agreements Emmanuel Tsesmelis CERN / TS-LEA RRB Scrutiny Group 31 August 2006.
GIF++ gas system Outline:  Beam and cosmic trigger  Gas distribution panels  Gas detection (present and final layout)  Conclusions 14/1/2015R. Guida,
Avogadro's Principle “Equal volumes of gases at the same temperature and pressure contain equal numbers of particles” It doesn’t matter what type of gas.
1 04 April 2007 L. Roy Detector Safety System for infrastructure - General fire detection (barracks, cavern) - Sniffer system (smoke detection above the.
Dalton ’ s Law of Partial Pressures Learning Goals … … use Dalton’s Law to find the partial pressure of a gas... use Dalton’s Law of Partial pressures.
Status of Gas Barrack(SPS) and Exhaust JAILLET David EN/EA/CT.
Totem Gas Systems ( T1 , T2 ) S. Haider PH / DT1.
Gas System Commissioning
CMS Galaxy varian CP-4900 GC Gas Analysis
R. Guida PH-DT-DI Boston Students Program CERN, 16/1/2013
Compressed Gases.
Partial Pressures.
Presentation transcript:

David Mcfarlane1 CMS Gas Systems (Nitrogen, Argon & CO2)

David Mcfarlane2 Overview Different types Uses Layout of individual systems Consumption figures so far Operational troubling shooting Final Comments

David Mcfarlane3 Different types Experimental gases –Experimental gases required for specific experiments. Experimental primary gases –Nitrogen –Argon –CO2 Flushing gases (Permanent inertion) –Nitrogen Fire Suppression gases (Temporary inertion) –Nitrogen Compressed air system –Nothing to do with this group!!!!!!!!

David Mcfarlane4 Experimental gases SF6, CF4, C2H2F4, Ar/H2 & I-C4H10 These gases are used by RPC, CSC, DT and TOTEM. Supplied from the SGX5 gas building. –Via the USC55 gas room into the UXC55 cavern

David Mcfarlane5 Experimental Primary gases Argon, CO2 & Nitrogen. To be used by the detectors groups for use directly related to the operation of the detectors themselves and operation of control racks. –Eg, Argon is used as part of the mixture of the CSC system –Eg, Nitrogen is used to operate pneumatic valves within the control racks. Supplied from the SGX5 building. Stored in bottles, batteries (Argon has a dewar) This system is controlled and operated by TS/LEA

David Mcfarlane6 Primary gas layout

David Mcfarlane7 Current Consumption figures (2007)

David Mcfarlane8 Flushing gases (permanent inertion) Nitrogen. Used by several experiments to flush areas between detectors to insure an inert,dry and helium free atmosphere is maintained. –Eg, Tracker. Supplied from a 50m3 dewar located just outside SDX5. The Dewar is controlled and operated by AT. This system is controlled and operated by CMS.

David Mcfarlane9 Flushing gas layout

David Mcfarlane10 Fire Suppression gases (Temporary inertion) Nitrogen. Used only in the event of a fire being detected inside the detector. Supplied from 2 tanks located just outside the SGX5 building. This system is controlled and operated by PH.

David Mcfarlane11 Fire Suppression layout

David Mcfarlane12 Operational troubling shooting No piquet is forseen from TS/LEA Who to contact? –TS/LEA – Mats Wilhelmsson –CMS –Christoph Schäfer/ Gerd Fetchenhauer –AT – Goran Perinic –PH – Stefan Haider / Mar Capeans Possible failure areas? –Unreported increases in consumption

David Mcfarlane13 Final comments The 3 Nitrogen systems are completely separate. They are supplied from different sources Different people are responsible for different systems DO NOT “MIX & MATCH!!!!!” If the experimental Nitrogen system fails, then all of the detector control racks will stop working!!! Before using any of these systems, make sure you inform the correct operator of your estimated consumption and flow rate figures.