NFPA-12 Edition 2005 What “IMPACT” will the changes to NFPA-12 have on the design and installation of a CO 2 system?

Slides:



Advertisements
Similar presentations
Subcontractor Electrical Safety & NFPA 70E
Advertisements

FHM TRAINING TOOLS This training presentation is part of FHM’s commitment to creating and keeping safe workplaces. Be sure to check out all the training.
Electronic Locking and Exemption Request Form Training
Carbon Dioxide Systems 1.Carbon dioxide properties 2.Storage 3.Uses 4.Limitations 5.Types of systems 6.Local Application 7.Total Flood.
KURSUS PENGENALAN KEPADA PERKHIDMATAN MEKANIKAL DALAM BANGUNAN
Buildings and Structures 2 Fixed Installations Aim To provide students with information to allow them to recognise the types of fixed fire protection.
Hazard Communications Your “Right to Know”. Hazard Communications The Four Stages of the Program  Material Safety Data Sheets (MSDSs)  Labeling and.
Lock Out/Tag Out Training Lock-Out/Tag-Out OSHA Definition. Lockout/Tagout (LOTO) refers to specific practices and procedures to safeguard employees.
© Siemens Industry, Inc Confidential / Drive Your Business Forward Ignite the Power of New Products and Partnerships Siemens Fire Partner Summit.
Fire Detection and Suppression Chapter 7 Special Extinguishing Systems.
Lab Inspections State Fire Marshal’s Office. Applicable Codes 1999 BOCA Business Occupancy 1999 BOCA Fire Prevention Code 2000 NFPA 101, Life Safety Code.
Oxygen Deficiency Hazards ODH SAF 103 Patty Hunt.
Indiana Federation of Ambulatory Surgical Centers September 27, 2013 To promote and provide essential public health services.
Subpart E Means of Egress.
Prevent False Alarms Eugene A. Cable, P.E., M.S.F.P.E. Life Safety Consultants NEHES Honorary Member 412 Horse Heaven Road Averill Park, New York
THE INTERNATIONAL SOCIETY OF FIRE SERVICE INSTRUCTORS Electronic INSTRUCT-O-GRAM Program Lockout / Tagout Policy.
Controlling Hazardous Energy
How to create... A Fire Evacuation Plan.
Environmental Considerations Confined Space Rescue is inherently dangerous and requires performance of rigorous activities under adverse conditions. Regional.
CVFD Training – Fire Protection Systems
PETROSAFE Petroleum Safety & Environmental Services Company.
What you will learn in this session 1.The characteristics of fire, smoke and toxic fumes 2.Fire hazards involved in the working environment 3.Significant.
WELCOME DBI & SFFD Meet the Pros October 11, 2007.
Control Rooms  Serve as operations centers for the control and monitoring of a service or process  Flight control rooms  Power generation control rooms.
Oklahoma State University Hazard Communications
Evolution Industries Jan A Lockout/Tagout (LOTO) program ensures that energized equipment or machines are not started or used while they are being.
Inert Gas Fire Extinguishants
Patrick Thornton, SNS/FPE June 9, 2008
EGRESS AND FIRE PROTECTION
FHM TRAINING TOOLS This training presentation is part of FHM’s commitment to creating and keeping safe workplaces. Be sure to check out all the training.
Lockout/tagout Authorized employees
/0309 Copyright ©2003 Business and Legal Reports, Inc. BLR’s Safety Training Presentations Lockout/Tagout Refresher 29 CFR

Hazard Communication Training Program “Right-to-Know” Program.
Means of Egress and Fire Protection
© 2008 Delmar, Cengage Learning Property Security, Emergency Response, and Fire Protection Systems Chapter 13.
FHM TRAINING TOOLS This training presentation is part of FHM’s commitment to creating and keeping safe workplaces. Be sure to check out all the training.
 The purpose of this Lockout/Tagout Procedure is to have a positive method of confirming that a piece of equipment, machine, or device is not energized.
Your “Right to Know” Foothill-De Anza Community College District Hazard Communications.
Environmental Health and Safety Oklahoma State University Hazard Communications Your “Right to Know”
© 2015 American Society for Healthcare Engineering, a personal membership group of the American Hospital Association 155 N. Wacker Drive, Suite 400 | Chicago,
MINNESOTA CHAPTER AUTOMATIC FIRE ALARM ASSOCIATION Requirements of the 2003 Minnesota State Fire Code relating to Group R Occupancies September 14, 2006.
Means of Egress and Fire Protection. Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers each year There is a long.
Chapter 5 ID 234 Building Codes Fire Resistant Materials and Assemblies.
Exit Routes and Fire Protection
Area of Refuge It’s the Law!
Maine State Fire Marshals Office1 Laws and Codes Relating to Existing Apartment occupancies in the State of Maine Mark Stevens CFI-II, CFPS, CFPE Inspections.
06/01/20161 Benny Hoff TÜV NORD Sweden AB AFS 2002:1 Use of pressure equipment.
OCCUPATIONAL SAFETY AND HEALTH Do you remember those school fire drills ? Well, here you go again !
NFPA 2 Overview Susan Bershad, Staff Liaison, NFPA.
Lock-out tag-out Procedure OSHA and site requirements.
Confined Space Rescue Level I Technical References: Mod 3.
Presented by John Lewandowski and Mike Larabel Inspection, Testing, and Maintenance of Kitchen Hood Systems Michigan Fire Inspectors Society Winter Educational.
Fire Alarm Verification CAN/ULC-S561-03
1 Lockout/Tagout MEETING THE STANDARD MEETING THE STANDARD.
Carbon Dioxide System Design
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection.
LOCKOOUT/TAGOUT THE ULTIMATE GOAL IS: To implement policies and procedures to prevent, as necessary, the release of hazardous energy from power sources--or.
Lock Out / Tag Out The Control of Hazardous Energy
The Control of Hazardous Energy (Lockout-Tagout)
Lockout/tagout Refresher training
Industrial Radiography
Energy Control (Lockout/Tagout)
Energy Control Procedures Lockout/Tagout 29 CFR
The Control of Hazardous Energy (Lockout-Tagout)
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
General Requirements of NFPA 101
Control of Hazardous Energy
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Lock Out Tag Out.
Presentation transcript:

NFPA-12 Edition 2005 What “IMPACT” will the changes to NFPA-12 have on the design and installation of a CO 2 system?

NFPA-12 Edition 2005 Reasons for changes Continuing effort to improve/enhance product features and system designs for “life safety” on both: – Existing Installations –New Systems

NFPA-12 Edition 2005 Who does this affect? –Manufacturers –Designers –Installers –Service –End-users/Owners

NFPA-12 Edition 2005 Application /systems affected: –Total Flood CO2 systems applied to Normally Occupied Spaces –Total Flood CO2 systems applied to Occupiable Spaces –Local Application Systems

Definitions per NFPA-12 Edition Normally Occupied Area. An area or space where, under normal circumstances, persons are present Normally Unoccupied Area (occupiable). An area or space not normally occupied by people but could be entered occasionally be brief periods Unoccupiable Area. An area or space which cannot be occupied due to dimensional or other physical constraints.

Existing Systems Retroactivity. All (NO, Occupiable., Local if exposing personnel) existing systems shall be upgraded to meet the requirements for... Safety signs in paragraph Lockout valves in paragraph & Pneumatic time delays & pre-discharge alarms in paragraph These upgrades shall be completed by June, 2006

Safety Signs Warning signs should be affixed in a conspicuous location... In every protected space At every entrance to protected spaces In spaces near the protected spaces where it is determined carbon dioxide could migrate creating a hazard to personnel...

Safety Signs The safety sign Format Color letter style of signal words message panel letting lettering size safety symbols shall be in accordance with ANSI Z535.

WARNING Carbon dioxide gas discharge into nearby space can collect here. When alarm operates vacate immediately. Carbon dioxide gas may cause injury or death.

Personnel Safety – NFPA 12 continued… WARNING CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH WHEN ALARM OPERATES VACATE IMMEDIATELY Typical Warning signs shall be affixed in conspicuous locations:

Typical Warning signs… WARNING CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH WHEN ALARM OPERATES DO NOT ENTER UNTIL VENTILATED

Typical Warning signs… WARNING CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH WHEN ALARM OPERATES OR WINTERGREEN SCENT IS DETECTED, DO NOT ENTER UNTIL VENTILATED

Typical Warning signs… CAUTION CARBON DIOXIDE GAS DISCHARGE INTO NEARBY SPACE CAN COLLECT HERE. WHEN ALARM OPERATES VACATE IMMEDIATELY. CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH

Typical Warning signs… CAUTION CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH VENTILATE THIS AREA BEFORE ENTERING. A HIGH CARBON DIOXIDE GAS CONCENTRATION CAN OCCUR IN THIS AREA AND CAUSE SUFFOCATION

Typical Warning signs… WARNING ACTUATION OF THIS DEVICE WILL CAUSE CARBON DIOXIDE TO DISCHARGE. BEFORE ACTUATING, BE SURE PERSONNEL ARE CLEAR OF AREA

Safety Signs Exception: Existing installations where facilities have written caution / warning sign procedures in place to provide: information and directions to personnel have a training programs established to educate personnel about signage then said sign procedures can be used in place of ANSI Z535.

No LockoutWith Lockout Items Required to Comply with NFPA 12 Edition 2000 NFPA 12 Paragraph To prevent accidental or deliberate discharge, a “lockout” shall be provided when persons not familiar with the systems and their operation are present in a protected space. NFPA 12 Paragraph Supervision of automatic systems and manual lock-out valves shall be provided unless specifically waived by the A.H.J. Stop/Maintenance (“lock-out”) Valve

Typ. Arrangement w/ Mech Time Delay & Siren Changes Required to Comply with NFPA 12 Edition 2005

New Systems Carbon dioxide total flood extinguishing systems shall not be used in normally occupied enclosures if other fire extinguishing agents can be used to provide an equivalent level of fire protection to carbon dioxide. When CO 2 is determined to be the most suitable agent of choice the designer / installer shall provide documentation... to verify that CO 2 is the most suitable fire suppression agent available.

Examples where CO 2 should not be used Control Rooms Computer Rooms Data Centers IT Equipment Rooms / Centers Telecommunication Rooms Laboratory Rooms Libraries Museums

NFPA 12: Marine Systems 2 separate valves shall be provided for releasing CO 2 into any protected space. 1 valve shall control discharge from the CO2 storage. The 2 nd valve shall control CO 2 discharge into the protected space(s). A separate manually operated control shall be provided to operate each valve… A set of controls shall be located outside at least one of the main means of egress from each protected space. Audible predischarge alarms and a minimum 20 second time delay shall be provided that depend on no source of power other than CO 2.