Presentation is loading. Please wait.

Presentation is loading. Please wait.

Inert Gas Fire Extinguishants

Similar presentations


Presentation on theme: "Inert Gas Fire Extinguishants"— Presentation transcript:

1 Inert Gas Fire Extinguishants
CXS490 New Technology Inert Gas Fire Extinguishants

2 Introduction relevant standard is NFP-A2001
At least four inert gases or gas mixtures commercialized clean total flooding fire suppression agents design concentrations of 35-50% by volume reduces ambient oxygen concentration 14% to 10% by volume agents mixed with air - extinguish by physical mechanisms agents consist of nitrogen, argon & blends of these One blend contains 8% carbon dioxide.

3 Inert Gases Not liquefied gases like Halocarbons
stored as high pressure gases require high pressure storage cylinders may have storage volume and weight impact. use pressure reducing devices at or near the discharge manifold reduces the pipe thickness requirements alleviates concerns regarding high pressure discharges.

4 Inert Gases Discharge times - one (typical) to two minutes
limit some applications - rapidly developing fires (explosions) Not subject to thermal decomposition form no byproducts. electrically non-conductive

5 Physiological Effects
Primary health concern effect of reduced oxygen concentration on occupants reduced oxygen extensively researched & studied Many countries granted health & safety approval for use of inert gases in occupied areas in the workplace One product contains 8% carbon dioxide intended to increase blood oxygenation & cerebral blood flow in low oxygen atmospheres

6 Physiological Effects
Inert gas agent IG-541 (Inergen) contains 8% carbon dioxide & approved by the U.S. EPA SNAP rules safe alternative to halon total flooding systems At elevated concentrations carbon dioxide not safe for human exposure & lethal at fire extinguishing concentrations

7 Physiological Effects
Generic Name Trade Name Maximum Exposure Concentration 5 minutes Maximum Exposure Concentration 3 minutes Maximum Exposure Concentration Above 53% (Volume %) IG-01 Argotec 43 52 (*4) IG-55 Argonite IG-100 NN-100 IG-541 Inergen

8 Notes 1: Nominal maximum discharge time is 60 seconds in all cases
2: Inert gas systems designed to concentrations below 43 percent (corresponding to an oxygen concentration of 12 percent, sea level equivalent of oxygen) shall be permitted, where means are provided to limit exposure to no longer than 5 minutes. 3: Inert gas systems designed to concentrations between 43 and 52 percent (corresponding to between 12 and 10 percent oxygen, sea level equivalent of oxygen) shall be permitted, where means are provided to limit exposure to no longer than 3 minutes. 4: Inert gas systems designed to concentrations between 52 and 62 (corresponding to between 10 and 8 percent oxygen, sea level equivalent of oxygen) shall be permitted given the following: (a) The space is normally unoccupied. (b) Where personnel could possibly be exposed, means are provided to limit the exposure to less than 30 seconds. (c) Inert gas systems designed to concentrations above 62 percent (corresponding to 8 percent oxygen or below, sea level equivalent of oxygen) shall only be used in unoccupied areas where personnel are not exposed to such oxygen depletion.

9 Environmental Factors
Inert gas agents are neither ozone depleting substances nor greenhouse gases pose no risk to the environment

10 Environmental Factors
Generic Trade Ozone Global Name Depletion Warming Potential (100 year) IG-01 Argotec IG-55 Argonite IG-100 NN-100 IG-541 Inergen

11 Specific Volume (m3/kg)
Physical Properties Generic Name IG-541 IG-55 IG-01 IG-100 Trade Name Inergen Argonite Argotec NN100 Agent Composition Nitrogen 52% 50% - 100% Argon 40% Carbon Dioxide 8% Properties k1 (m3/kg) 0.6598 0.5612 0.7998 k2 (m3/kg) Specific Volume (m3/kg) 0.697 0.708 0.602 0.858 Gas Density 20oC, 1 atm kg/m3 1.434 1.412 1.661 1.165

12 Extinguishing Design Concentration
Physical Properties Generic Name IG-541 IG-55 IG-01 IG-100 Trade Name Inergen Argonite Argotec NN100 Extinguishing Design Concentration (% Vol.) Minimum Class A fire (% Vol.) 36.7 41.1 39.9 39.0 Oxygen (% Vol.) 13.3 12.3 12.6 12.8 Class B Heptane (% Vol.) 31.7 36.5 39.3 33.6 Minimum Class B fire (% Vol.) 41.2 47.5 51.1 43.7 11.0 10.2 11.8 Inerting - Methane/Air (% Vol.) 47.3 * 61.4 41.7 - 8.1 12.2 * Not Reported

13 Flooding Factor Calculation (X)
X - volume of inert gas ONLY added at 14.7 psia, 70oF (1.013 bar, 21oC) per volume hazard space (ft3/ft3 or m3/m3) VS - specific volume at 70oF (21oC) at 14.7 psia (1.013 bar) (ft3/lb or m3/kg) sV - specific volume at lowest temperature at 1 atmosphere t - minimum anticipated temperature (oF or oC) c - inert gas design concentration (%)

14 Specific Volume Inert gas k1 k2 Unit type SI English IG-01 (Argotec
0.5612 IG-55 (Argonite) 9.8809 IG-100 (Nitrogen) 0.7997 11.973 0.0261 IG-541 (Inergen) 0.659 0.0024 9.858 0.0214

15 Flooding Factors (X) The calculation result in a series of flooding factors required to achieve various inert gas concentrations.

16 Flooding Factors (X) 36 36.1 36.2 36.3 36.4 36.5 36.6 36.7 36.8 36.9 37 37.1 37.2 37.3 37.4 37.5 37.6 37.7 37.8 37.9 38 38.1 38.2 38.3 38.4 38.5 38.6 38.7 38.8 38.9 39 39.1 39.2 39.3 39.4 39.5 39.6 39.7 39.8 39.9 40 40.1 40.2 40.3 40.4 40.5 40.6 40.7 40.8 40.9 41 41.1 41.2 41.3 41.4 41.5 41.6 41.7 41.8 41.9 42 42.1 42.2 42.3 42.4 42.5 42.6 42.7 42.8 42.9 43 43.1 43.2 43.3 43.4 43.5 43.6 43.7 43.8 43.9 44 44.1 44.2 44.3 44.4 44.5 44.6 44.7 44.8 44.9 45 45.1 45.2 45.3 45.4 45.5 45.6 45.7 45.8 45.9 46 46.1 46.2 46.3 46.4 46.5 46.6 46.7 46.8 46.9 47 47.1 47.2 47.3 47.4 47.5 47.6 47.7 47.8 47.9 48 48.1 48.2 48.3 48.4 48.5 48.6 48.7 48.8 48.9 49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5 50.6 50.7 50.8 50.9 51 51.1 51.2 51.3 51.4 51.5 51.6 51.7 51.8 51.9 52 52.1 52.2 52.3 52.4 52.5 52.6 52.7 52.8 52.9

17 Sample Calculation - Inert Gas
Room houses electronic equipment Ambient temperature is 70° F Room Dimensions are: Length: 40 feet Width: 20 feet Height: 10 feet Room Volume = L x W x H = 40 x 20 x 10 = 8000 cubic feet

18 Amount of Agent A = V x X where A is amount of agent (m3 or ft3)
V is volume of space (m3 or ft3) X is flooding factor of space from calculation or chart (m3/m3 or ft3/ft3)

19 Sample Calculation - Inert Gas
Using IG-541 Inergen Class A design concentration is: 39.9% Maximum Human Exposure Concentration for 5 minutes is: 42.8% Maximum Human Exposure Concentration for 3 minutes is: 52.3% Available cylinder sizes for Inergen are: 205 ft3, 266 ft3, 355 ft3 and 439 ft3 Flooding factor for 39.9% concentration is: Amount /Volume of Inergen required to create a 39.9% concentration in an 8000 ft3 enclosure is: A = V x X = 8000 x = 4074 ft3 of Inergen

20 Sample Calculation - Inert Gas
Cylinder Selection Round up to ft3 cylinders AACTUAL = NumberCYLINDERS x CylinderSIZE = 10 x 439 = 4390 ft3

21 Sample Calculation - Inert Gas
Check to determine the actual concentration that will be achieved, by looking at “Flooding Factors for Inert 70° F for selected concentrations. relates to a concentration of ≥ 42.2% but ≥ 42.3%. This is < maximum allowable concentration of 42.8% for 5 minute human exposure & > Class A design concentration 39.9% The quantity of Inergen is acceptable.


Download ppt "Inert Gas Fire Extinguishants"

Similar presentations


Ads by Google