Floating Head Pressure for Refrigeration Single Compressor Systems Michele Friedrich, PE – Sr. Engineer Dustin Bailey – Engineer PECI 11/2/2010.

Slides:



Advertisements
Similar presentations
Add Doors to Open Multi-deck Cases: Provisional UES RTF Meeting August 30,
Advertisements

GrocerSmart 4.0 redesign -request for rtf input- February 25, 2010.
CHARGING BY SUPERHEAT.
Advanced Heat Pump Water Heater Research Conducted by WSU Energy Program Funded by Bonneville Power Administration BPA Technology Innovation Project #292.
EXPANSION VALVE SYSTEM
C oncerns Ltd ool Energy Efficient Refrigeration Jane Gartshore, Cool Concerns Ltd.
COMMERCIAL REFRIGERATION
Evaluation of Energy Savings for Strip Curtains Presented To RTF Scott Moore PECI Sr. Engineer June 2, 2009.
Out-Of-Compliance Grocery UES Measure Recommendations Regional Technical Forum June 17, 2014.
AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS
COMMERCIAL REFRIGERATION
Grocery Measure: LEDs for Reach-In Display Cases Regional Technical Forum July 21 st, 2015 Mohit Singh-Chhabra.
Evaporators For Air Conditioning
LED Case Lighting With and Without Motion Sensors Michele Friedrich – Sr. Engineer PECI 1/5/2010.
Today’s “Game Plan” Two Trial-Runs of a new deemed measure review process – Deemed measure analysis and review Developed by … – (consultant, RTF member/staff,
1 Proposed Changes to the RTF’s Heat Pump Specifications Impact on Estimated Deemed Savings and C&R Discount Program Credits.
1 Air Source Heat Pumps Potential Changes in the RTF’s Specifications & Savings Estimates and Their Impact on C&R Discount Program Credits.
Night Covers on Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30,
© 2001 The Gas Company. All copyright and trademark rights reserved. High Efficiency Unit Heaters Workpaper Presentation Prepared for Cal TF Presentation.
Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30,
Plans to bring Out-of-Compliance UES Measures back into Compliance: 1. Agricultural Irrigation Hardware UES 2. Agricultural Motors UES Regional Technical.
Air Handler Terminology
Community Water Supply Efficiency Improvements Potential Savings for the 6 th Power Plan September 30 th, 2008 Regional Technical Forum.
Out-Of-Compliance Grocery UES Measure Recommendations Regional Technical Forum March 18, 2014.
LED Case Lighting in Vertical and Semi-Vertical Open Refrigerated Cases Eric Mullendore – Energy Analyst PECI 6/29/2010.
EnergySmart Grocer Program Evaluation Findings Summary PWP, Inc.
Grocery Measure: EC Motors for Display Cases Regional Technical Forum July 21 st, 2015 Mohit Singh-Chhabra.
Grocery Measure: EC Motors for Display Cases Regional Technical Forum June 16 th, 2015 Mohit Singh-Chhabra.
Strip Curtains for Refrigerated Walk-in Boxes Michele Friedrich, PE – Sr. Engineer Eric Mullendore – Energy Analyst PECI 8/3/2010.
Air Handler Terminology
David Garvin Product Manager EarthDirEX Geothermal Copyright © 2015 Nortek Inc. All rights reserved.
July 26, 2014 Refrigeration Subcommittee Proposed Revision of Refrigeration Provisional Data Requirements.
Deemed Savings Update: ECMs in Display Cases Ben Cartwright PECI January 5, 2009.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee February 22, 2012 Mira Vowles, P.E., CEM.
EER Analysis Results Regional Technical Forum March 18, 2014.
New Refrigeration Measures - FHP Status Report- & -Request for Input- September 21, 2010.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee June 12, 2014 Mira Vowles, P.E., CEM Emerging.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee February 27, 2013 Mira Vowles, P.E., CEM.
1 NORTHWEST ENERGY EFFICIENCY ALLIANCE DHP Costs & NEBs Ecotope, Inc. August 20, 2013.
EnergySmart Grocer. 2 BPA background  The Bonneville Power Administration contracted Cascade Energy Engineering, Inc. to evaluate the GrocerSmart audit.
GrocerSmart™ 4.0 RTF Approval of Software and Adherence to RTF Guidelines April 5, 2011.
Measurement and Verification of Refrigeration Measures in 4 Grocery Stores in Pacific County Presented to the Regional Technical Forum August 8 th, 2006.
Beyond NEMA Premium Using CEE Motors List 1. Savings Summary Worksheet 2.
High Efficiency Evaporator Coils for Medium Temperature Cases Dustin Bailey, Engineer PECI Jan 5, 2010.
Grocery Store Issues RTF April 10, Need Recommendations PECI: Energy Smart Grocer Program Savings method for interactive measures Savings method.
Out-Of-Compliance Grocery UES Measure Recommendations Regional Technical Forum July 15, 2014.
Grocery VSD Measure Deemed Savings Reid Hart, PE & Ken Anderson September 28, 2010.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee July 24, 2013 Mira Vowles, P.E., CEM Emerging.
GrocerSmart TM Energy Modeling Software -Revision Status Report- & -Request For Input- July 13, 2010.
Chapter 11 Refrigeration Cycles Study Guide in PowerPoint to accompany Thermodynamics: An Engineering Approach, 8th edition by Yunus A. Çengel.
PNW RoofTop Unit Working Group - RTUG – RTU Savings Research Project Phase 3 December 15, 2009.
BasicRefrigerationSystem 4 Component Flow Diagram.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump Sub-Committee Road-Mapping Session BPA Energy Efficiency.
HW2 AHU problems: Book: 8.5, 8.25, 8.27, 8.28, 8.22 Cooling Cycles Problems: - Book: 3.1 (page 69), - Book: 3.5 ((page 70), - Out of book: Same like 3.5.
GrocerSmart™ 4.0 RTF Approval of Software and Adherence to RTF Guidelines April 5, 2011.
Best practice small scale commercial refrigeration, optimisation strategies and simple maintenance Michael Bellstedt, Minus40 Pty Ltd.
New Refrigeration Measures -Status Report- & -Request for Input- September 13, 2010.
AIR CONDITIONING (COOLING)
WELCOME. Glycol Refrigeration A most basic definition of refrigeration is taking heat from someplace we don’t want it and moving it to someplace where.
Section 2: Safety, Tools and Equipment, and Shop Practices
TXV Devices.
AdaptaPAK The sustainable, energy-efficient outdoor refrigeration solution.
Objectives Learn about Cooling towers Cooling cycles.
By: JAGDEEP SANGWAN Refrigeration Basics 101.
Objectives Solve one more example related to the psychometrics in AHU and building systems Learn about the psychometrics related to the cooling towers.
Presentation transcript:

Floating Head Pressure for Refrigeration Single Compressor Systems Michele Friedrich, PE – Sr. Engineer Dustin Bailey – Engineer PECI 11/2/2010

Acknowledgements We would like to thank the following for their support: Avista Utilities Bonneville Power Administration Puget Sound Energy RTF refrigeration subcommittee

Purpose Approval for new deemed measures for floating head pressure on refrigeration single compressor systems

4 Agenda Proposed Measures Technology Overview Calculation Methodology Cost Effective Useful Life Market Potential Program Specifications Program Summary

Proposed Measures Measure Application Energy Savings (kWh/yr- HP) EUL (yr) Measure Cost ($/HP ) Benefit Cost Ratio Floating head Pressure Single- Med Temp Condensing Unit Floating head Pressure Single- Low Temp Condensing Unit Floating head Pressure Single- Med Temp Remote Condenser Floating head Pressure Single- Low Temp Remote Condenser

Technology Overview Current measure for FHP on multi-plex systems excludes single compressors. Two types of Single Compressor systems: Condensing Units (~85-90%) & Remote Condensers. Allows condenser to operate at a lower temp. and pressure depending on ambient conditions. Lower condenser temperature = less compressor work due to lower compression ratio.

Head Pressure Control

Technology Overview Refrigeration System Diagram

Technology Overview This measure requires using adjustable head pressure control valve which is adjusted to equivalent pressure of 70F saturation. Replaces fixed valve set at 180 psig by factory (~94.3F for R22). Expansion valve is retrofitted to balanced port valve or a device is installed to supplement refrigerant feed at lower condensing pressures.

Calculation Methodology eQUEST model 1.Set at “typical” specifications for convenience store refrigeration system. 2.Condensing Unit modeled as 1 compressor and 1 condenser with fan ON when compressor is ON. Min Condensing P set by flood-back control valve (head pressure control valve). 3.Remote Condenser modeled as 4 compressors and 4 fans that are controlled to come ON staged with Outside Air Temperature (OAT). Minimum Condensing P set by flood-back control valve (head pressure control valve).

Calculation Methodology eQUEST model 4.Conduct sensitivity analysis for each type of Single Compressor system: Condensing Unit and Remote Condenser. a)Condensing Unit highest sensitivity to Compressor efficiency and Compressor/condenser over-sizing (split into LT and MT before sensitivity analysis). b)Remote Condenser highest sensitivity to condenser set point and suction temperature.

Calculation Methodology Presented to RTF refrigeration subcommittee for direction and input. Condensing Set Point: fixed head pressure control valve set at factory to 180 psig +/- 5 psig. For R22 this is 94.3 o F +/- 1.8 o F. Assume that there are as many at – 5 psig as at +5 psig. Suction Temperature: Split into LT and MT measures Compressor/Condenser over sizing: used refrigeration schedules for single compressor systems to find median value of compressor and condenser over sizing

Calculation Methodology Weighted for compressor motor efficiency for Condensing units by weighting by motor size (efficiency a function of size for 0.5 HP to 7.5 HP). Motor size from GrocerSmart database audits in PNW for single compressor systems. Weighted for climate zone (different savings for east vs. west side of cascades) using store population in GrocerSmart in PNW. Remote Condenser picked 1 HP fans (0.5 HP fans are quieter, 1.5 HP fans are cheaper: designers pick in between.) Picked # fans per condenser from catalogue after condenser size was found. Refrigeration schedule review median value for # fans was 3.5.

Cost $ per evaporator –Balance Port Valve and labor $ per condenser –Adjustable head pressure valve, filter drier, bypass valve and labor. Unknown extended life on compressor from lower operating hours. *Cost data from Grainger, Sporlan and HVAC/R wholesaler

Effective Useful Life 15 years Same as FHP on Multiplex. Equipment life = 15 years.

Market Potential 100% penetration of PNW GrocerSmart audited stores with Single Compressors = 1.8 aMW

Program Specifications Install adjustable head pressure control valve (flood- back control valve) to lower minimum condensing head pressure. Field calibrated to pressure equivalent of 70 F saturated temperature or lower using NIST certified calibration of +/- 5 PSI pressure gauge or transducer. Measure applicable only to refrigeration systems having single compressor systems of 1 HP motor or larger either in condensing unit or in remote condenser. Must install either balanced-port valve or EEV that is sized to meet the load requirement at 70 degree condensing temperature, if not currently installed, or install device to supplement refrigerant feed to each evaporator attached to condenser that is reducing head pressure.

Summary

Proposed Measures Measure Application Energy Savings (kWh/yr- HP) EUL (yr) Measure Cost ($/HP ) Benefit Cost Ratio Floating head Pressure Single- Med Temp Condensing Unit Floating head Pressure Single- Low Temp Condensing Unit Floating head Pressure Single- Med Temp Remote Condenser Floating head Pressure Single- Low Temp Remote Condenser