Night Covers on Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1.

Similar presentations


Presentation on theme: "Night Covers on Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1."— Presentation transcript:

1 Night Covers on Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1

2 Thanks to All Participants 2

3 Measure Summary Retrofitting night covers to existing medium temperature open multi- deck cases Provisional savings estimate 44 kWh/lin ft and 5 therms/lin ft Based on a calibrated DOE2.2r simulation Requesting Provisional UES Status 3

4 Measure History Night Covers (first version): – Previously RTF-approved: March 2, 2009 – Includes separate savings values for applying night covers to vertical and horizontal refrigerated display cases – Calculation methodology: uncalibrated engineering calculations Vertical Night Covers – Updated UES to replace existing value, which is out-of- compliance 4

5 UES Analysis Summary 5

6 Appendix A: Provisional UES Checklist 6

7 7 Appendix B: UES Measure Summary

8 8

9 9

10 10

11 11

12 Implementation and Product Standards 12 No night cover may be present in baseline Minimum 1 year manufacturer’s warranty Minimum application of 6 hours/ 24 hour period

13 Estimation Procedure 13 Modeled using DOE 2.2R to capture interactive effects “Typical” store was built using GrocerSmart Audit Data Multiplex Baseline assumes Floating Head Pressure, T8 lamps, and EC motors are in place. Stand-alone system baseline assumes T8 lamps and EC motors. Infiltration, conduction, and radiation load based on manufacturer data, the ASHRAE Refrigeration Handbook, and SCE lab test report

14 Model Calibration: Whole Building 14

15 Model Calibration: Compressor Energy Use 15

16 Model Calibration- Baseline: Case Refrigeration Load 16 Total case load based on ANSI/ASHRAE 72 testing = 1600 btu/hr-ft ASHRAE data used to disaggregate load components

17 Model Calibration- Efficient Case: Case Refrigeration Load 17

18 Cost Estimates Cost estimate: $36/ft Unchanged from previously accepted cost value Supported by invoice levels observed by program 18

19 Measure Effective Useful Life EUL: 5 years Unchanged from previously accepted EUL Supported by 1 year warranty requirement 19

20 Reliable Efficient Case Data 20

21 Calibration Plan Collect Metered Data – Rack: Volts, Amps, PF – Condenser: Volts, Amps, PF – Hourly Natural Gas via Utility Interval Meter – Hourly Outside Air Temperature Minimum 3 weeks baseline Minimum 3-weeks post – This is a direct load measure. We expect less seasonal interaction than system measures like floating head pressure. 21

22 Calibration Plan Develop regressions for daily or hourly refrigeration use correlated to ambient temperature Annualize using TMY data – Pre, Post and Savings (Pre minus Post) 22

23 Calibration Plan Collect DOE2.2r inputs per data collection specifications Use inputs to run DOE2.2r for Baseline & Post estimates of total refrigeration energy Compare estimates of Baseline, Post & Savings estimates of refrigeration energy to best-practice estimates Modify DOE2.2r models and iterate tests until both baseline energy use, post energy use and energy savings at all sites are reasonable and there is no significant bias. 23

24 Proposed Provisional UES Value Measure Site Savings (kWh) Site Savings (therms) Measure Life (years) Capital Cost ($/unit) TRC B/C Ratio Night Covers- Retrofit to Open Vertical Case on Multiplex - Seattle, WA42.05.55$361.5 Night Covers- Retrofit to Open Vertical Case on Stand-alone - Seattle, WA44.75.55$361.6 Night Covers- Retrofit to Open Vertical Case on Multiplex - Spokane, WA41.65.25$361.5 Night Covers- Retrofit to Open Vertical Case on Stand-alone - Spokane, WA44.05.25$361.5 Night Covers- Retrofit to Open Vertical Case on Multiplex - Billings, MT45.74.95$361.5 Night Covers- Retrofit to Open Vertical Case on Stand-alone - Billings, MT47.84.95$361.6 Night Covers- Retrofit to Open Vertical Case - Average44.35.25$361.6

25 RTF Proposed Motion: “I _________ move that the RTF approve the UES for Night covers on Open Vertical Refrigerated Display Cases under provisional status with a sunset date of August 31 st, 2013.


Download ppt "Night Covers on Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1."