Dynamic Reduced-order Model for the Air Temperature Field Inside a Data Center G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology.

Slides:



Advertisements
Similar presentations
CFD ANALYSIS OF CROSS FLOW AIR TO AIR TUBE TYPE HEAT EXCHANGER
Advertisements

O.Yoshida, M.Andou Tokyo Gas Co., Ltd.
Clair Christofersen Mentor – Aaron Andersen August 2, 2012
1 Application of for Predicting Indoor Airflow and Thermal Comfort.
CFD _CAST-Tilted -New mesh generation E. Da Riva.
Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Data Centre Best Practises Workshop 17 th March 2009.
Coupling a Network HVAC Model to a Computational Fluid Dynamics Model Using Large Eddy Simulation Jason Floyd Hughes Associates, Inc Fire + Evacuation.
University of Western Ontario
Model predictive control for energy efficient cooling and dehumidification Tea Zakula Leslie Norford Peter Armstrong.
CFD and Thermal Stress Analysis of Helium-Cooled Divertor Concepts Presented by: X.R. Wang Contributors: R. Raffray and S. Malang University of California,
Who Wants to Be a CFD Expert? In the ME 566 course title, CFD for Engineering Design, what does the acronym CFD stand for? A.Car Free Day B.Cash Flow Diagram.
Reliability Prediction of a Return Thermal Expansion Joint O. Habahbeh*, D. Aidun**, P. Marzocca** * Mechatronics Engineering Dept., University of Jordan,
1 Design of Gridded-Tube Structures for the 805 MHz RF Cavity Department of Mechanical, Materials, and Aerospace Engineering M. Alsharoa (PhD candidate)
Experimental and Numerical Study of the Effect of Geometric Parameters on Liquid Single-Phase Pressure Drop in Micro- Scale Pin-Fin Arrays Valerie Pezzullo,
Project Motivation: Opportunity to explore building efficiency technology and the engineering design process Improving the thermal efficiency will save.
Copyright 2001, J.E. Akin. All rights reserved. CAD and Finite Element Analysis Most ME CAD applications require a FEA in one or more areas: –Stress Analysis.
Simulation of Air-Cooling for the Gear Unit in Pump and Turbine Generator Systems M. Fujino* and T. Sakamoto** *Information Technology Center, Nippon Institute.
Air-Water Heat Exchanger Lab In this lab, YOU will design, conduct, and analyze your experiment. The lab handout will not tell you exactly what to measure.
Experimental Verification of Gas- Cooled T-Tube Divertor Performance L. Crosatti, D. Sadowski, S. Abdel-Khalik, and M. Yoda ARIES Meeting, UCSD (June 14-15,
Chamber Dynamic Response Modeling Zoran Dragojlovic.
1 THERMAL LOADING OF A DIRECT DRIVE TARGET IN RAREFIED GAS B. R. Christensen, A. R. Raffray, and M. S. Tillack Mechanical and Aerospace Engineering Department.
M. Yoda, S. I. Abdel-Khalik, D. L. Sadowski and M. D. Hageman Woodruff School of Mechanical Engineering Extrapolating Experimental Results for Model Divertor.
Effect of Rack Server Population on Temperatures in Data Centers CEETHERM Data Center Laboratory G.W. Woodruff School of Mechanical Engineering Georgia.
Ph.D. Proposal Presentation
AIAA SciTech 2015 Objective The objective of the present study is to model the turbulent air flow around a horizontal axis wind turbine using a modified.
Performance of SolarWalls in Minnesota
CFD team supports CERN development 19 May M.Battistin CERN May 19 th 2011 C omputational F luid D ynamics team C omputational F luid D ynamics team.
Lecture Objectives Discuss specific class of problems
Sensor-Based Fast Thermal Evaluation Model For Energy Efficient High-Performance Datacenters Q. Tang, T. Mukherjee, Sandeep K. S. Gupta Department of Computer.
1 BROOKHAVEN SCIENCE ASSOCIATES CFAC Review – Chris Channing P.E. Sr Project Engineer NSLS-II Conventional Facilities - Thermal Stability May 8, 2007.
August 28th, 2015, Lavrion Technological and Cultural Park (LTCP), Attica NANO-HVAC GA no : Novel Nano-enabled Energy Efficient and Safe HVAC ducts.
Variable-Speed Heat Pump Model for a Wide Range of Cooling Conditions and Loads Tea Zakula Nick Gayeski Leon Glicksman Peter Armstrong.
School of Aerospace Engineering MITE MITE PROGRAM OVERVIEW AND ACCOMPLISHMENTS (MITE-Multidisciplinary University Research Initiative on Intelligent Turbine.
The Use of Computational Fluid Dynamics (CFD) in Achieving Energy Reductions in New Zealand’s Industrial Energy Consumption Energy Research Group Department.
Thermal Model of MEMS Thruster Apurva Varia Propulsion Branch Code 597.
Summer Report Xi He Golisano College of Computing and Information Sciences Rochester Institute of Technology Rochester, NY
Thermal-aware Issues in Computers IMPACT Lab. Part A Overview of Thermal-related Technologies.
Dealing with Hotspots in Datacenters Caused by High-Density Computing Peter Hannaford Director of Business Development EMEA.
Thermal Aware Data Management in Cloud based Data Centers Ling Liu College of Computing Georgia Institute of Technology NSF SEEDM workshop, May 2-3, 2011.
Reduced-order Modeling Framework for Improving Spatial Resolution of Data Center Transient Air Temperatures Rajat Ghosh, Yogendra Joshi Georgia Institute.
School of Mechanical Engineering FACULTY OF ENGINEERING School of Mechanical Engineering FACULTY OF ENGINEERING Aerodynamic Design Optimization Harvey.
Interdisciplinary Project with South Texas Project Funded by The Nuclear Power Institute 1.
PRESENTATION OF CFD ACTIVITIES IN CV GROUP Daniel Gasser.
Bulatom Confernce June 2007
Transient thermal + fatigue analysis in ASONIKA. Specify a name for the project.
CAD and Finite Element Analysis Most ME CAD applications require a FEA in one or more areas: –Stress Analysis –Thermal Analysis –Structural Dynamics –Computational.
AIAA th AIAA/ISSMO Symposium on MAO, 09/05/2002, Atlanta, GA 0 AIAA OBSERVATIONS ON CFD SIMULATION UNCERTAINTIES Serhat Hosder, Bernard.
Heat Transfer System By Team Awesome: Sub-team Awesomer.
All content in this presentation is protected – © 2008 American Power Conversion Corporation Row Cooling.
Date of download: 5/27/2016 Copyright © ASME. All rights reserved. From: Experimentally Validated Computational Fluid Dynamics Model for a Data Center.
PIC port d’informació científica First operational experience from a compact, highly energy efficient data center module V. Acín, R. Cruz, M. Delfino,
1 PCE 2.1: The Co-Relationship of Containment and CFDs Gordon Johnson Senior CFD Manager at Subzero Engineering CDCDP (Certified Data Center Design Professional)
Mi9 Some experimental measurements of the Diffuser flow in a Ducted Wind Turbine assisted by two ejectors Kypros F. Milidonis Department of Mechanical.
1 Copyright © 2016, The Green Grid The webcast will begin shortly Today’s live session will be recorded.
CFD Simulation & Consulting Services Hi-Tech CFD | Voice: Optimizing Designs of Industrial Pipes, Ducts and.
Forecasting with Cyber-physical Interactions in Data Centers (part 3)
O.Yoshida, M.Andou Tokyo Gas Co., Ltd.
Chamber Dynamic Response Modeling
Investigation of Heat Transfer in Stationary and Rotating Internal Cooling Channels with High Rotation Numbers Mandana Sheikhzad Saravani Saman Beyhaghi.
Using Heat to Increase Cooling George Hannah BEng (Hons) CEng MIMechE
Xiaomin Pang, Yanyan Chen, Xiaotao Wang, Wei Dai, Ercang Luo
Effects of Ventilation Systems on Ammonia Concentration Distributions in Manure-Belt Egg Layer Houses Using Computational Fluid Dynamics Xinjie Tong1.
Date of download: 11/2/2017 Copyright © ASME. All rights reserved.
International Conference on Hydrogen Safety
Date of download: 11/9/2017 Copyright © ASME. All rights reserved.
Date of download: 12/25/2017 Copyright © ASME. All rights reserved.
Experimental Investigation of
The application of an atmospheric boundary layer to evaluate truck aerodynamics in CFD “A solution for a real-world engineering problem” Ir. Niek van.
AIAA OBSERVATIONS ON CFD SIMULATION UNCERTAINTIES
Thermal behavior of the LHCb PS VFE Board
Presentation transcript:

Dynamic Reduced-order Model for the Air Temperature Field Inside a Data Center G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology Atlanta, GA Rajat Ghosh and Yogendra Joshi

Project Objective Development of experimentally validated reduced order modeling framework for dynamic energy usage optimization of data centers and telecoms  Dynamic reduced order modeling framework development  Experimental validation of dynamic reduced order modeling framework Implementation and generalization of modeling approach in data centers and telecom test sites  Assessment and refinement of approach at a selected facility  Development of data center thermal design software 2

Accomplishments Developed a CFD/HT model for predicting transient temperature field Developed an experimental setup for measuring transient temperature field Utilizing a reduced-order model to generate new temperature data from an existing temperature ensemble obtained from CFD/HT simulations or experiments 3

Modeling Algorithm 4 POD coefficient calculation Interpolation Ensemble generation POD mode calculation Number of principal components determination CFD/HT simulation Reduced-order temperature computation Error estimation

Case Study for CFD/HT Simulation CRAC A1 A2 A3 A4 B4B3B2B1 Cold aisle Hot aisle Row X Y X Z Row B Row A 1218 Plenum CRAC Adiabatic Symmetry plane Insulated room wall Initial condition -T(x, y, z; t=0)=15 0 C - V(x, y, z; t=0)=0 Heat load/ rack = 5 KW Air flow rate from CRAC= 5500 CFM Grid Size - 182,000 - Adaptive meshing With hexagonal grid-cells

Row Inlet at a Known Time (t=30s) 6 X Z  POD model can reproduce CFD/HT data accurately Row A inlet Error~1% POD temp. FieldCFD temp. fieldDeviation~1 % Velocity field Row B inlet

Temperature at an Intermediate Instant (t=15 s) 7 POD based model can efficiently generate temperature data at t=15 s from existing CFD/HT temperature ensemble, obviating need for independent simulation X Z POD temp. field ~4 s CFD temp. field ~8 min Deviation~1 % Row A inlet Row B inlet

Experimental Validation CFM CRAC unit 14 kW racks Parameters -Eight 14 kW racks arranged symmetrically about cold aisle -CFM from CRAC unit=12700 Transient Condition Sudden shutdown of CRAC unit for 2 min -Observe following transient temperature field at cold aisle for 200 s at 10 s interval

Temperature Measurement at Rack A Inlet 9 t=0 st=30 s t=60 st=90 s X Z

Validation of POD based Interpolation 10 POD temperature field ~4sExperimental temperature field ~ 3 min Error between POD and Experimental temperature field~1% Temperature data at t=45 s are not included in original temperature ensemble generated by experiments POD based model can generate temperature data at t=45 s from existing temperature ensemble generated by experiments,, obviating need for independent experiment POD based model is significantly faster than experiments without compromising accuracy X Z

Validation of POD-based Extrapolation X Z POD temperature field ~4s Experimental temperature field ~ 6 min Error between POD and Experimental temperature field~1% Temperature data at t=205 s are outside the temperature range t=0-200 s POD based model can generate temperature data at t=205 s from existing experimental observations, obviating need for independent experiment POD based model is significantly faster than experiments without compromising accuracy

Publication/ Presentation Conference Proceedings Ghosh, R., and Joshi, Y., 2011,”Dynamic Reduced Order Thermal Modeling of Data Center Air Temperature”, ASME InterPack 2011 Conference Poster Presentation Ghosh, R., and Joshi, Y., 2010 " Dynamic Reduced Order Modeling of Convective transports in Data Centers" at NSF I/UCRC meeting 12

Plan for Next Quarter Refining POD based model – Designing more representative experiments with distributed temperature measuring facility Capable of measuring instantaneous room level temperature field Developing thermal design software for data centers 13

Acknowledgement We acknowledge support for this work from IBM Corporation as a sub-contract on Department of Energy funds 14