Thermal Performance of a "Cool Roof" Attic Design José B. Dávila Christian Brothers University Abstract This research consisted of analysis of a large.

Slides:



Advertisements
Similar presentations
Common Terminology Emittance Winter U-Factor or U-Value R-Value
Advertisements

Energy Efficient Heating Ventilating and Air Conditioning.
HEAT LOSS & HEAT GAIN HEAT FLOW. Heat flows from high temperature to low temperature There are 3 types/methods of heat flow/transfer: 1.Conduction- through.
Doing without and more with less
The Three Tiered Philosophy
Civil, Environmental, and Architectural Engineering The University of Kansas 1 “Radiant Barrier Technology – A Must in Green Architecture” Mario A. Medina,
9645 TTCSI “I AM” SECONDARY SCHOOLS COMPETITION CHALLENGE 9645.
Radiant Barrier. Problem (Summer Conditions): Solar radiation causes roof temperatures to reach 160 to 190 degrees Fahrenheit. Heat is conducted through.
The House as a System 1. Air Temperature and Water Vapor.
Heating energy calculation methods Anti Hamburg Lecture TTK-UAS.
Heat Loss & Gain Calculations 1. How Heat Moves in Homes Conduction is the transfer of heat through solid objects, such as the ceilings, walls, and floors.
Sea Ice Presented by: Dorothy Gurgacz.
A note to presenters: 1.This presentation contains extra notes about each slide including background and supplemental information. These are accessible.
Introduction to Thermodynamics
Chapter 27 Insulating Structures. Objectives After reading the chapter and reviewing the materials presented the students will be able to: List the ways.
Jamil Ibrahim Establishment Building Integration Thermal Collector BITC By Engineer Khaled Jazzar WEBCO sarl June 2014.
CBE 150A – Transport Spring Semester 2014 Heat Transfer Introduction.
Solar Radiation And it’s General Applications Nitin Jayswal.
Introduction to Thermodynamics
Introduction to Thermodynamics
Lesson: Heat Transfer Contributed by: Integrated Teaching and Learning Program, College of Engineering, University of Colorado at Boulder.
Environmental Controls I/IG Lecture 11 Passive Heating Photovoltaics and Active Solar Panels Lecture 11 Passive Heating Photovoltaics and Active Solar.
I-DEAS 11 TMG Thermal and ESC Flow New Features
Ductwork Systems and Supply Arch 432. What You Need To Know Become familiar with the materials sizing ductwork Understand sizing units.
CONSTRUCTION Objective You will need to write all the information down but you need to highlight, mark, or note that the items in yellow are important.
“Building Integrated photovoltaics with cost effective cooling” Karantagli Eleni (Ms Environmental Science Dep. University of Patras) Tripanagnostopoulos.
Energy Conservation February 8, Steve Wilson, MBA, CEM, CDSM, BEP The Energy Guy.
HVACR416 - Design Heat Loss / Heat Gain Part 1. Why? The primary function of Air Conditioning is to maintain conditions that are… o Conductive to human.
Armaflex Solutions High Temperature and Solar Installations.
PowerPoint ® Presentation Unit 52 Thermal Insulation and Other Insulating Methods Thermal Insulation Exterior Insulation and Finish Systems (EIFS) Roof.
UNIT THREE: Matter, Energy, and Earth  Chapter 8 Matter and Temperature  Chapter 9 Heat  Chapter 10 Properties of Matter  Chapter 11 Earth’s Atmosphere.
1 Energy Efficient Housing. 2 Why construct energy efficient structures? Bottom Line !!! Money It may save up to 60% of the cost to heat/cool the structure.
Energy conservation strategies Buildings energy consumption depends on building envelop, efficiency of HVAC and lighting systems, amount of required fresh.
HEAT 11.2.
Atmosphere: Structure and Temperature Bell Ringers:  How does weather differ from climate?  Why do the seasons occur?  What would happen if carbon.
Building Envelope. Physical separator between interior and exterior spaces – Walls – Floors – Roofs – Fenestrations (any opening in the structure) – Doors.
Chapter 6. Temperature related to the average kinetic energy of an object’s atoms or molecules Thermal energy the sum of kinetic & potential energy of.
Chris Benedict Chapter 15
17.1 Atmosphere Characteristics
Lecture Objectives: -Define the midterm project -Lean about eQUEST -Review exam problems.
Development of a new Building Energy Model in TEB Bruno Bueno Supervisor: Grégoire Pigeon.
WINTER RULE: ADD LAYERS FOR FLARES Bibhisha Uprety MEEN 340- Fall /30/2010.
Chapter 3.4 Notes Thermal Rates.  The amount of heat that is transferred per unit time is the heat flow rate  Equation for heat flow rate = heat / time.
INDEX Sr noTopic 1.Introduction 2.Advantages 3.Product Types 4.Thermal Insulating Materials 5.Applicatiion.
17 Chapter 17 The Atmosphere: Structure and Temperature.
GCSE ENERGY; THERMAL ENERGY TRANSFER 2
Earth’s Layers Geology Unit.
Atlas is pleased to present…. What Is a Radiant Barrier? The Turkey Analogy.
The Atmosphere: Structure & Temperature. Atmosphere Characteristics Weather is constantly changing, and it refers to the state of the atmosphere at any.
Part 16 Technician’s Guide & Workbook for Duct Diagnostics and Repair
MODUL KE LIMA TEKNIK MESIN FAKULTAS TEKNOLOGI INDUSTRI
PASSIVE SOLAR DESIGN ALTERNATIVE ENEGRY SOURCES.
Building Energy Code Requirements
Temperature Measurement
Thermal energy transfer: Cooling
MCMENT INC The Only Remodeling and Building/Construction Experts Specializing in the use of PCM Products for energy conservation and living comfort for.
From: Modeling Transmission Effects on Multilayer Insulation
Heat gain and heat loss in buildings
Heat Loss and Gain Heat Transfer Winter Heat Loss Summer Heat Gain
Section 2: Conduction, Convection, and Radiation
Zero Energy Homes Goal: Regulate Heat Transfer
Full-Building Radiation Shielding for Climate Control
Components of Construction
Heat Loss and Gain Heat Loss and Gain
Heat Loss and Gain Heat Loss and Gain
Heat Controlling Heat.
Environmental Controls
Heat Loss and Gain Heat Loss and Gain
HEAT EXCHANGE IN BUILDINGS. TERMINOLOGIES Thermal conductivity: is the rate of heat flow through a unit area of unit thickness of the material for a unit.
Presentation transcript:

Thermal Performance of a "Cool Roof" Attic Design José B. Dávila Christian Brothers University Abstract This research consisted of analysis of a large volume of temperature and heat flux data pertaining to the thermal performance of an improved attic design. The objective was to reduce the heating and cooling load of a conditioned zone located underneath the attic. Data obtained for the improved attic design were compared with those obtained for a standard-construction roof. The results show a significant reduction of both cooling and heating load.

A Tale of Two Attics Temperature and heat flux data were obtained, using thermocouples and heat flux transducers, at an outdoor multiple-lane roof facility at Oak Ridge National Laboratory, for two very different attic structures: the “cool roof” and the standard-construction (reference). The conditioned zone below the attic was maintained at a constant temperature. Start date: March 14, 2008 (the start of week 1) End date: March 19, 2009 (the end of week 53)

“Cool Roof” Attic an improved attic designed by the Building Envelopes Group of the Building Technologies and Research Center at ORNL The uppermost surface of the roof is made of metal sheets with a reflective surface. A roof board is installed between the above-mentioned metal sheets and the main attic plenum thus creating a circulation channel, vented at the top and bottom of the roof incline. A metal sheet is installed below the above-mentioned board to serve as a radiation shield. Twelve-inch thick layer of fiberglass insulation is laid on the floor board. The upper four inches of the insulation layer are laced with encapsulated phase-change material (PCM).

“Cool Roof” Schematic J. Kosny et al: “Theoretical and Experimental Thermal Performance Analysis of Building Shell Components Containing Blown Fiberglass Insulation Enhanced with Phase-Change Material (PCM),” ASHRAE Buildings IX, 2009.

Standard-construction Attic Standard shingle on roof board No vented circulation space No radiation shield No insulation No PCM

Measurements: Outdoor, plenum, base board, roof board, attic plenum and insulation temperatures. Base board and roof board heat flux. Interval: 15 minutes Heat flux integration over one-week periods.

Quantification of cooling load, according to ambient temperature and heat flux data: If ambient temperature is higher than 60 ºF, then heat flux is classified as “cooling load.” If flux is into the zone, then it is positive. That is, the zone gains heat (because of the hot weather), and therefore it requires cooling. If flux is out of the zone, then it is negative. That is, the zone loses heat (despite the hot weather, due to thermal mass effects and/or solar radiation), and therefore some of the cooling requirement is relieved.

Quantification of heating load, according to ambient temperature and heat flux data: If ambient temperature is lower than 60 ºF, then heat flux is classified as “heating load.” If flux is out of the zone, then it is positive. That is, the zone loses heat (because of the cold weather), and therefore it requires heating. If flux is into the zone, then it is negative. That is, the zone gains heat (despite the cold weather, due to thermal mass effects and/or solar radiation), and therefore some of the heating requirement is relieved.

Positive cooling load [Btu/ft 2 ] vs week number Negative cooling load [Btu/ft 2 ] vs week number

Positive heating load [Btu/ft 2 ] vs week number Negative heating load [Btu/ft 2 ] vs week number

Summary Energy [Btu] defective year (46 weeks) Cool RoofReference Roof Positive Cooling Load [Btu/ft 2 ] Negative Cooling Load [Btu/ft 2 ] Net Cooling Load [Btu/ft 2 ] Positive Heating Load [Btu/ft 2 ] Negative Heating Load [Btu/ft 2 ] 212 Net Heating Load [Btu/ft 2 ]

Observations and concluding Remarks The Cool Roof has reduced the cooling load, not merely by reducing the heat gain, but by reversing the net heat transmission through the roof. Compared to the net cooling load of the Reference Roof, the cooling load savings are 3313 Btu/ft 2. The reversal does not occur in the heating load. But the heating load savings are much larger: Btu/ ft 2, representing a reduction of 83.7 percent. The load reduction advantage of the Cool Roof over the Reference Roof was significant for both heating and cooling. The results suggest that Cool Roof can effectively eliminate the roof as a cooling load source, and substantially reduce the heating load.