1 Distributed Generation and Power Quality. 2 Relaying considerations DG infeed may reduce the reach of overcurrent relays –DG feeds fault, so utility.

Slides:



Advertisements
Similar presentations
Chapter 12 Transformers. Chapter 12 Transformers.
Advertisements

Announcements Be reading Chapters 9 and 10 HW 8 is due now.
New Energy Horizons Opportunities and Challenges Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25,
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
ENERGY CONVERSION ONE (Course 25741)
GENERATOR PROTECTION.
Stray Current Investigations A Method of Troubleshooting Stray Current on Underground Residential Distribution (URD) Loops Stacey Mighty Malcolm Distribution.
1 Pacific Gas & Electric Company MTS: Evolution of the Electric Distribution System Manho Yeung, Senior Director, System Planning and Reliability PG&E.
Lecture 26 Distribution Systems Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
1 Distributed Generation and Power Quality. 2 Distributed Generation Distributed generation (DG) or distributed generation resources (DR) –Backup generation.
CIGRE 7-10 September 2009, Moscow
Transformer Voltage Regulation Fact: As the load current is increased, the voltage (usually) drops. Transformer voltage regulation is defined as:
Announcements Be reading Chapter 3
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
SHUNT CAPACITOR FUNDAMENTALS AND PROTECTION
Disconnect Switches There are many purposes for disconnect switches in substations and power lines. They are used to isolate or deenergize equipment for.
Three Phase Power Three Phase Motors
PowerPoint ® Presentation Chapter 12 Utility Interconnection Distributed Generation Generators Inverters Interconnection Codes and Standards Interconnection.
Substations. Substations Chapter 4 Substations Major types of equipment found in most transmission and distribution substations with their purpose,
Interconnect Protection of Dispersed Generators
F. Ferrandis_SP_ALPHA 2_BLOCK 2_Paper 35_Presentation Barcelona May POWER FACTOR CORRECTION WITHIN INDUSTRIAL SITES EXPERIENCES REGARDING.
By A.D.Thirumoorthy Tamil Nadu Electricity Board India.
Transient Overvoltages
Section 3 TRANSMISSION & DISTRIBUTION US Bulk Power Transmission System Transmission & Distribution (T&D) Components New T& D Technologies This product.
2. Terms and definitions1 # Terms and Definitions # Voltage Sags and Interruptions.
STEADY-STATE POWER ANALYSIS
1.6 Real Single-Phase Transformer.
Electrical Distribution Systems
Transformer Taking the ratio of the two equations
Assumption University Thailand EE4503 Electrical Systems Design Main Circuit 1.
CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION.
Power Quality Impacts of Distributed Generation Roger C. Dugan Sr. Consultant Electrotek Concepts, Inc. Tennessee Tech. February 9, 2004.
Queensland University of Technology CRICOS No J Protection of distributed generation connected networks with coordination of overcurrent relays.
By: Dr Rosemizi Abd Rahim
Electrical Transformer 1 By: Dr Rosemizi Abd Rahim Click here to watch the electrical transformer animation video
Transformer Protection Over-current protection in the form of fuses may be the only protection provided to a small 100 kVA, 11 kV/440 V distribution transformer.
Chapter 2 Transformers Edit by Chi-Shan Yu Electric Machinery.
1 Distributed Generation and Power Quality-Continued.
EECE 887 Distribution System Engineering CHAPTER 1 Power Delivery Systems.
Introduction to switchgears
Distribution Systems-General
SERVICE ENTRANCE EQUIPMENT
Transformer DKT Introduction to Transformer.  Transformer is a device that changes ac electrical power at one voltage level to ac electric.
A SEMINAR ON 400 KV GSS(RRVPNL) BIKANER.
Transformer DKT Introduction to Transformer.  Transformer is a device that changes ac electrical power at one voltage level to ac electric.
DISTRIBUTED GENERATION ISSUES Technical Issues Non-Technical Issues.
ECE 498HZ: Power Distribution System Analysis
Protection of Power Systems
This project on Primary sub station of Visakhapatnam port trust at Visakhapatnam. It is 132kv/11kv substation with incoming feeder from APTransco and 11.
Grounded Wye-Delta Transformer Bank Backfeed Short-Circuit Currents W. H. Kersting & Wayne Carr Milsoft Utility Solutions.
AC Machines. BOOSTER Basic Function:- -Sometimes when we use electrical power we need different voltage level to main supply. It is provided by Booster.
Impact of Distributed Generation on Fault Induced Transients: A Case Study Sukumar Brahma Adly Girgis Clemson University Electric Power Research Association.
Power System Protective Relaying-Part One
Protection of Power Systems
STUDY OF ELEMENTS OF A 220/132/33KV SUBSTATION
Auto Transformer Current Flow. Principles of Auto Transformers H X H0/X0.
Protection of Power Systems
Interconnect Protection of Dispersed Generators
GUJARAT POWER OF ENGINEERING AND RESEARCH INSTITUTE (104)
Distribution Feeder Voltage Regulation and Control
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
Chapter 7 System Protection
A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Power Plants By: Stephanie Mercer.
Power transmission Energy is lost in transmission lines
Utilizing the ring operation mode of MV distribution feeders
Three Phase Transformers
CHAPTER – 41 A.C. TRANSMISSION AND DISTRIBUTION
Substation Equipment's
Presentation transcript:

1 Distributed Generation and Power Quality

2 Relaying considerations DG infeed may reduce the reach of overcurrent relays –DG feeds fault, so utility current is fault current minus DG contribution –Sympathetic tripping of feeder breakers –Defeat fuse saving

3 115 kV kV Put recloser here DISTRIBUTION Radial Line DG Only one DG: obvious solution to several problems

4 115 kV kV DG “Sympathetic” tripping of this circuit breaker (not desired) due to backfeed from DG Fault Solution is to use directional overcurrent relays at substation

5 DG Since DG feeds the fault (backfeed), it will likely defeat fuse saving Fault on tap

6 DG V distance Voltage Regulation

7 DG V distance Feeder trips and recloses DG disconnects Low voltage

8 DG V distance Feeder trips and recloses DG disconnects VR steps

9 DG V distance Feeder trips and recloses DG disconnects VR steps DG reconnects

10 Sequence –First we see interruption and reclosure with a voltage sag due to DG disconnect –Then voltage returns to normal (station step regulator or LTC) –Then DG reconnects, and we see a voltage swell –Then voltage returns to normal (station step regulator or LTC) Obviously needs to have coordinated voltage control –Limits to how much DG one feeder can stand

11 Power flow reversal in voltage regulators If excess DG during low load causes power to flow in reverse direction through voltage regulators misoperation is possible –Modern controls recognize this and change to reverse power mode (regulate in opposite direction so that controls operate correctly)

12 Wind generation case study 32 step V Reg switched capacitor a b cuntransposed line construction (typical) wind farm singly-fed induction gen

13 Detailed 3-phase study shows: –as wind generation increases, one outside phase voltage rises while the other drops –feeder has problems with frequent capacitor switching and/or votlage regulator stepping events –Cases like this may need dedicated feeder or doubly-fed generator to avoid power quality problems for other customers –If DG can generate reactive power, capacitor controls needs coordination with reactive generation

14 DG Transformer Connections Order used here is HV : LV feeding DG 1. Y gnd : Y gnd interconnects HV and LV grounds 2.  : Y gnd isolates LV ground from HV ground 3.  :  used on existing installations 4.Y :  used on existing installations 5.Y gnd :  similar to utility units

15 DG Transformer Connections 1.Y gnd : Y gnd interconnects HV and LV grounds. DG may need a neutral reactor to limit 1 phase to ground short circuit currents. DG may need 2/3 pitch winding to avoid large third harmonic votlages (which can cause third harmonic currents on HV and LV sides). - No phase shift between primary and secondary voltage.

Generator voltage harmonics Windings are distributed and often short-pitched (or chorded): –each coil spans a pitch of less than 2  /p where p is the number of poles, to reduce the time harmonic voltage induced

3-phase 6-pole 36-slot full-pitch stator winding

Development of stator winding

One coil of the winding: conductors in top of slot 1 return in bottom of slot 7, coil pitch = pole pitch, so a full-pitch winding

One coil of the winding: conductors in top of slot 1 return in bottom of slot 6, coil pitch = 5/6 pole pitch, so a 5/6-pitch winding

What’s so great about a 2/3-pitch coil anyway? Third harmonic flux linking a full-pitch (blue), 5/6-pitch (green), and 2/3-pitch (red) coils. Notice that the flux linkage (net area enclosed) is zero at the 2/3-pitch coil.

Third harmonics The third harmonic flux will not link a stator winding with a 2/3 pitch If third harmonic voltages are present, third harmonic circulating currents can be quite large if generator is solidly grounded

23 DG Transformer Connections  : Y gnd isolates LV ground from HV ground. DG may need 2/3 pitch winding to avoid third harmonic voltages, but third harmonic currents are contained on LV side. Some utility faults hard to detect due to phase shift.

24 DG Transformer Connections  :  used on existing installations. 4.Y :  used on existing installations. Ungrounded, unless DG provides ground. Some utility faults hard to detect due to phase shift.

25 DG Transformer Connections 5.Y gnd :  similar to utility units, isolated grounds, avoids problem with third harmonic currents.

26 Expected single-phase to ground fault currents on a radial distribution feeder

27 DG transformer showing possible zero-sequence currents