Presentation is loading. Please wait.

Presentation is loading. Please wait.

Grounded Wye-Delta Transformer Bank Backfeed Short-Circuit Currents W. H. Kersting & Wayne Carr Milsoft Utility Solutions.

Similar presentations


Presentation on theme: "Grounded Wye-Delta Transformer Bank Backfeed Short-Circuit Currents W. H. Kersting & Wayne Carr Milsoft Utility Solutions."— Presentation transcript:

1 Grounded Wye-Delta Transformer Bank Backfeed Short-Circuit Currents W. H. Kersting & Wayne Carr Milsoft Utility Solutions

2 Introduction Wye-Delta Transformer Bank – Serving a three-phase load A three-phase transformer Or three single-phase transformers – Serving single-phase and three-phase loads One centered tapped lighting transformer Two power transformers Question: To ground or not to ground the Wye connection.

3 Wye-Delta Transformer Connection

4 Ungrounded Wye-Delta Transformer Bank

5 Grounded Wye-Delta Transformer Bank

6 So What? Ungrounded Y-D – No backfeed short circuit current – Lose one phase and bank becomes single-phase Grounded Y-D – Backfeed current possible – Lose one phase and have open Y-D bank – Need to compute all short circuit currents for A-G fault

7 Test System Used to Compute Backfeed SC Currents for Grounded Y-D Bank

8 Overhead Lines

9 Overhead Line Phase Impedances

10 Methods of Analysis Symmetrical Components – Old fashion way to demonstrate backfeed Basic circuit and transformer analysis – Analysis of total three-phase circuit Reduced 8x8 matrix analysis – Reduce total analysis to just what is needed

11 Symmetrical Component Method

12 Overhead Line Sequence Impedances

13 Sequence Networks Connection Phase a-g Fault at Node 12

14 The Minus 3 Error Doc. Crosno (NMSU) was a stickler for accurate calculations when I was a student When he found an error it was an automatic -3 error (red rubber stamp) out of 10 points on the problem When I was preparing for this presentation I found a -3 error on the symmetrical component analysis. I used transformer impedance referred to secondary rather than primary side. Please ignore the results in the paper

15 Correct Sequence Network Analysis Results

16 Now What? The symmetrical component method has demonstrated – There is a backfeed current of 91.48 amps/phase – This method assumes a balanced three-phase system (ignored the off diagonal terms of the sequence impedance matrix) Need to evaluate the short circuit currents with a total unbalanced three-phase system

17 Unbalanced Three-Phase System

18 Observations to Note

19 A-G Fault at Node 12

20 A-G Fault at Node 12 Results

21 Reduced Three-Phase Circuit Analysis Primary concern – Currents in the fault – Currents from the source – Backfeed currents from the transformer bank Recognize the three backfeed currents are equal Apply basic algebra to reduce to 8 equations and 8 unknowns

22 Reduced Analysis 8x8 Matrix

23 8x8 Matrix for A-G Fault at Node 12

24 8x8 Matrix Results

25 Comparisons of Results

26 WindMil Results Using Loop Flow Method

27 Ungrounded Wye-Delta Connection Analysis methods – 7x7 matrix – Set Zg = 999999 Results

28 Short Circuit Current vs. Rated Current Transformer Rated Currents – 100 kVA: 13.8 amps – 50 kVA: 6.9 amps With Zg = 5 ohms backfeed = 91.7 amps – 100 kVA: 564% over rated current – 50 kVA: 1,229% over rated current With Zg = 50 ohms backfeed = 19.3 amps – 100 kVA: 39.9% over rated current – 50 kVA: 79.9 % over rated current

29 Short Circuit Protection

30 Substation Transformer Primary Fuses Primary responsibility is to open on transformer faults Backup responsibility to open if low side breaker fails to open for downstream fault Transformer fuse must lie between inrush current and maximum melt curves

31 Primary A-G Short Circuit Current

32 Substation Transformer Fuses

33 Primary Fuse Curves Referred to Secondary for LG Fault

34 Primary Curves Referred to Secondary For LG Fault

35 Recloser and Xfm Fuses

36 Total Protection

37 Three Downstream Transformers 8x8 equivalent matrix method of analysis doesn’t work Symmetrical component model developed and analysis run WindMil using the loop flow method was developed and analysis run Symmetrical components and loop flow methods match very closely

38 Three Downstream Transformers WindMil Solution

39 Summary Grounded Wye-Delta Short Circuit Analysis – Symmetrical Components – Exact Circuit Analysis – Reduced Circuit Analysis Ungrounded Wye-Delta Short Circuit Analysis Short Circuit Protection – Primary Fuses – Recloser – Distribution Transformer Fuses

40 Conclusions Grounded wye-delta transformer banks provide backfeed currents for upstream faults involving ground Ungrounded wye-delta does not provide backfeed currents Backfeed currents can blow transformer fuses for upstream ground faults


Download ppt "Grounded Wye-Delta Transformer Bank Backfeed Short-Circuit Currents W. H. Kersting & Wayne Carr Milsoft Utility Solutions."

Similar presentations


Ads by Google